How does an electromagnetic flow meter work, and why is its reading unstable?

A flow meter with no moving parts that measures the flow of conductive liquids by the voltage they generate moving through a magnetic field.

01 / Definition

What a Electromagnetic Flow Meter is

An electromagnetic flow meter uses Faraday's law of induction. Coils mounted on the flow tube drive a magnetic field across the pipe, and any conductive liquid flowing through it acts like a moving conductor: it generates a voltage between two electrodes set into the pipe wall, and that voltage is proportional to the average flow velocity. The converter multiplies velocity by the bore area to give flow rate, and totalises it. There are no moving parts and no obstruction, so the meter handles dirty water, slurries and chemicals that would wear out a turbine meter.

The meter only works if three things are true: the liquid conducts (most water-based liquids do; oils and pure demineralised water do not), the pipe is completely full, and the liquid is at the same electrical potential as the meter. When readings jump or drift, the usual causes are air in the line, a partly empty pipe, coated electrodes, or missing earthing rings on a plastic or lined pipe.

Also called

magnetic flow metermagflowelectromagnetic flowmeter

02 / Anatomy

The parts that matter

The components a technician reaches for when this machine stops working.

Flow tube and liner

A non-magnetic tube with an insulating liner (rubber, PTFE) chosen for the liquid and temperature.

Field coils

Produce the magnetic field across the pipe; pulsed DC excitation keeps the zero stable.

Electrodes

Pick up the induced voltage; their material must suit the liquid.

Earthing rings or electrodes

Tie the liquid to the meter's reference potential, essential on plastic or lined pipe.

Converter (transmitter)

Excites the coils, measures the signal and outputs 4–20 mA, pulses or a fieldbus signal.

03 / Applications

Where it is used

Water and effluent lines, ETP and STP plants, chemical dosing, dairy and beverage lines, slurries and pulp.

04 / Failure modes

How it fails

What actually goes wrong on Indian shop floors, and what each fault looks like to the operator.

FM_01

Empty or partly full pipe

Air or a partly full pipe gives a high, noisy or zero reading; many meters flag 'empty pipe'.

FM_02

Electrode coating

Grease, scale or deposits insulate the electrodes and the reading drifts or freezes.

FM_03

Poor earthing

Noisy, jumping readings, worst near drives and welding sets.

FM_04

Liner damage

Abrasion, heat or vacuum collapse the liner and the meter fails.

FM_05

Wrong configuration

A wrong pipe size or calibration factor entered in the converter gives a steady but wrong flow.

05 / Onsite

What our technician checks

A methodical path to root cause, not a scattergun of part swaps.

  1. 01Confirm the pipe is full at the meter and that it is not at a high point where air collects
  2. 02Check earthing rings and bonding straps on both flanges
  3. 03Check the converter's diagnostics for empty-pipe, coil or electrode alarms
  4. 04Inspect and clean the electrodes if deposits are suspected
  5. 05Verify the configured size and calibration factor against the meter's nameplate
  6. 06Check the upstream and downstream straight pipe lengths against the maker's requirement

06 / Get it fixed

Related services

The MachineryFix services that cover this equipment.

07 / Questions

Frequently asked questions

Can a magnetic flow meter measure oil or diesel?+

No. The liquid must be electrically conductive. Oils, fuels and very pure water need another principle, such as Coriolis, turbine or ultrasonic meters.

Why does the flow meter show flow when the pump is off?+

Usually the pipe is partly empty or full of air, or the earthing is poor, so the meter picks up noise. Many meters have a low-flow cutoff and an empty-pipe detection setting to suppress this.

Does a mag meter need straight pipe?+

Yes, a few diameters of straight run upstream and downstream, per the maker's figures, so that the flow profile is even.

Why do the readings jump near a VFD?+

Electrical noise reaching the electrodes, typically from missing earthing rings, poor bonding or signal cables run beside motor cables.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007