MachineryFix

Power Electronics

Industrial power electronics repair.

Behind every drive, servo amplifier, soft starter and power supply is the same chain of power electronics: a rectifier, a DC bus, a switching stage and the boards that control them. When one part of that chain fails, the fault code on the front rarely names it. Repair means finding which stage failed, and why, at component level.

  • Phone answered 24/7

    Call at any hour to report a breakdown.

  • 1 to 12 month warranty

    Depends on the repair. The term is confirmed before work starts.

  • Verified, experienced technicians

    Identity checked before a technician is sent to your plant.

  • Pickup available

    A unit that needs bench repair can be collected from the plant.

01 / Inside the unit

Where power electronics fail

The stages of a typical drive, and what each one's failure looks like from outside.

Rectifier and pre-charge

Turns the AC supply into DC. A shorted diode or thyristor bridge trips the incoming breaker; a failed pre-charge resistor or relay leaves the drive dead or showing undervoltage.

DC bus capacitors

Smooth the DC and store energy. They age with heat and time; tired capacitors show up as overvoltage trips, ripple faults and drives that fail after a power cut.

IGBT output stage

Switches the DC into variable-frequency AC for the motor. A shorted IGBT trips on overcurrent or short circuit the moment the drive runs, and often takes its gate driver with it.

Gate drivers

Fire each IGBT at the right moment, with isolation from the control side. A weak or failed gate driver makes an IGBT fail again soon after it is replaced.

Switch-mode power supply

Makes the low voltages the control board and fans need from the DC bus. A failed SMPS gives a drive or controller with no display at all.

Control and interface boards

Run the firmware, read the inputs and talk to the PLC. Faults here look like lost communication, wrong readings or a drive that will not accept a run command.

02 / Method

How a power electronics fault is found

  1. 01Record the fault code and history, and what the drive or machine was doing when it failed.
  2. 02Isolate the supply and wait for the DC bus to discharge, confirmed with a meter.
  3. 03Test the motor and cable, so a drive that is correctly reporting an outside fault is not condemned.
  4. 04Check the power stage cold: rectifier, IGBTs and DC bus, with the board out of circuit where needed.
  5. 05Trace the cause, not only the failed part: a blown IGBT is often the result of a gate driver, cooling or capacitor problem.
  6. 06After repair, power up through a current-limited supply where possible, then run the unit on load before it goes back on the machine.

03 / Before you call

What to have ready

The make and model from the rating plate, the fault code and a photo of the display, what the machine was doing when it failed, and whether the drive was recently worked on. If the unit has no display at all, say so: that alone points to the power supply side. Then call or WhatsApp +91 70133 33007; the phone is answered 24/7.

04 / Questions

Power electronics repair: common questions

Is it worth repairing a drive with a blown IGBT?+

Often yes, when the control board is healthy and replacement IGBTs are available, and especially for drives that are no longer sold. If the power stage and control board are both badly damaged, or parts cannot be found, replacement can be the better choice, and you are told which before work starts.

Why did the new IGBT fail again?+

Usually because the cause was not fixed: a failing gate driver, poor cooling, degraded DC bus capacitors, or a motor or cable insulation fault. These are checked as part of the repair, not only the part that blew.

Can power electronics be repaired on site?+

Diagnosis, testing of the motor and cable, fan, capacitor and many board swaps can be done on site. A board that needs component-level rework goes to the bench; pickup is available, and you are told before anything leaves the plant.

Which equipment does this cover?+

VFDs and AC drives, servo amplifiers, DC drives, soft starters, UPS and power supplies, and the control boards inside CNC machines, compressors and special-purpose machines.

What does a power electronics repair cost?+

It depends on what has failed. A fan or a power supply is a small job; a destroyed power stage is a large one. The cost is confirmed before any work starts. Whether the diagnosis visit itself is charged depends on where the plant is, so ask when you call.

Related

Repairs and guides

Board-level fault on a drive?

Send the make, the model and the fault code. We'll match a technician who works on that equipment.