The VFD-E is Delta Electronics' compact AC drive with Modbus over RS485. Most models have a built-in PLC function; the VFDxxxExxC models have CANopen instead.
VFD-E codes are short letter codes on the keypad, such as oc, ov, GFF or ocA. Below is every fault and warning in Delta's VFD-E user manual that the manual gives a text code for, with the cause and the action Delta lists.
01 / Reading codes
Reading and clearing VFD-E codes
The digital keypad shows the fault as a short code, for example oc for over-current or GFF for ground fault. The five most recent faults are stored in parameters Pr.06.08 to Pr.06.12 and can be read from the keypad or over communication.
A fault activates the drive's protective function and stops its output to the motor until the fault is reset. A warning (CExx, FbE, AUE) is shown on the keypad. What the drive does next depends on its settings: Pr.09.02 for communication errors and Pr.10.09 for PID feedback errors.
- Remove the cause first, then reset in one of three ways: press the RESET key on the keypad, switch on a terminal set to RESET (one of Pr.04.05 to Pr.04.08 set to 05), or send a RESET command over communication.
- Wait 5 seconds after a fault has cleared before resetting from the keypad or an input terminal.
- Make sure the RUN command is off before resetting, or the drive may start straight away.
02 / Current and earth faults
Current and earth faults
03 / Voltage and supply
Voltage and supply
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| oH1 | IGBT overheat | Fault · Drive overtemperature |
| oH2 | Power board overheat | Fault · Drive overtemperature |
| oL | Overload | Fault · Drive overload |
| oL1 | Overload 1 | Fault · Motor overload or overtemperature |
| oL2 | Overload 2 | Fault · Motor overload or overtemperature |
| cF3.4 | IGBT overheat (temperature sensor)A temperature sensor error. Delta's instruction is to return the drive to the factory. | Fault · Temperature sensor signal |
| cF3.5 | Power board overheat (temperature sensor)A temperature sensor error. Delta's instruction is to return the drive to the factory. | Fault · Temperature sensor signal |
| PtC1 | Motor PTC overheat protection | Fault · Motor overload or overtemperature |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| FbE | PID feedback signal error | Alarm · Process limit |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| EF | External fault | Fault · External fault |
| AErr | ACI signal error | Fault · Analog signal loss |
| PGEr | PG feedback signal error | Fault · Encoder signal |
| cE01 | Illegal function codeThe Modbus master sent a function code the drive does not support. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring. | Alarm · Communication loss |
| cE02 | Illegal data addressThe Modbus master sent a data address the drive does not have. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring. | Alarm · Communication loss |
| cE03 | Illegal data valueThe Modbus master sent a data value the drive cannot accept. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring. | Alarm · Communication loss |
| cE04 | Slave device failureThe drive could not carry out the action the master requested. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring. | Alarm · Communication loss |
| cE10 | Communication time-out | Alarm · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| HPF1 | CC, OC hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| HPF2 | OV hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| HPF3 | GFF hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| HPF4 | OC hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| cFA | Auto accel/decel failure | Fault · Setup |
| codE | Software protection failureThe software or password protection tripped. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| cF1.0 | Power board CPU write failureThe internal EEPROM could not be written. Delta's instruction is to return the drive to the factory. | Fault · Parameter memory |
| cF1.1 | Control board CPU write failureThe internal EEPROM could not be written. Delta's instruction is to return the drive to the factory. | Fault · Parameter memory |
| cF2.0 | Power board CPU read failureThe internal EEPROM could not be read. Press RESET to set all parameters back to factory settings. | Fault · Parameter memory |
| cF2.1 | Control board CPU read failureThe internal EEPROM could not be read. Press RESET to set all parameters back to factory settings. | Fault · Parameter memory |
| cF3.0 | U-phase errorAn internal error on output phase U. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| cF3.1 | V-phase errorAn internal error on output phase V. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| cF3.2 | W-phase errorAn internal error on output phase W. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| cF3.3 | DC bus errorAn internal over- or under-voltage error on the DC bus. Delta's instruction is to return the drive to the factory. | Fault · Internal drive fault |
| CP10 | Control board and power board communication time-outCommunication between the control board and the power board timed out. Press RESET to set all parameters back to factory settings. | Fault · Internal drive fault |
| ACL | Abnormal communication loop | Fault · Internal drive fault |
| AUE | Auto tuning error | Alarm · Motor identification |
Related
Related pages
Source
Delta Electronics, VFD-E Series User Manual, Revision Jan. 2012 (08EE), Chapter 6, Fault Code Information and Maintenance.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.