AC drive (VFD) · 43 codes

Delta VFD-E fault codes

The VFD-E is Delta Electronics' compact AC drive with Modbus over RS485. Most models have a built-in PLC function; the VFDxxxExxC models have CANopen instead.

VFD-E codes are short letter codes on the keypad, such as oc, ov, GFF or ocA. Below is every fault and warning in Delta's VFD-E user manual that the manual gives a text code for, with the cause and the action Delta lists.

01 / Reading codes

Reading and clearing VFD-E codes

The digital keypad shows the fault as a short code, for example oc for over-current or GFF for ground fault. The five most recent faults are stored in parameters Pr.06.08 to Pr.06.12 and can be read from the keypad or over communication.

A fault activates the drive's protective function and stops its output to the motor until the fault is reset. A warning (CExx, FbE, AUE) is shown on the keypad. What the drive does next depends on its settings: Pr.09.02 for communication errors and Pr.10.09 for PID feedback errors.

  • Remove the cause first, then reset in one of three ways: press the RESET key on the keypad, switch on a terminal set to RESET (one of Pr.04.05 to Pr.04.08 set to 05), or send a RESET command over communication.
  • Wait 5 seconds after a fault has cleared before resetting from the keypad or an input terminal.
  • Make sure the RUN command is off before resetting, or the drive may start straight away.

02 / Current and earth faults

Current and earth faults

CodeNameKind
ocOver-currentFault · Overcurrent
ocAOver-current during accelerationFault · Overcurrent
ocdOver-current during decelerationFault · Overcurrent
ocnOver-current during constant speedFault · Overcurrent
GFFGround faultFault · Earth fault

03 / Voltage and supply

Voltage and supply

CodeNameKind
ovOver-voltageFault · DC bus overvoltage
LvLow voltageFault · DC bus undervoltage
PHLPhase lossFault · Input phase loss
dEbDeceleration energy backup errorFault · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
oH1IGBT overheatFault · Drive overtemperature
oH2Power board overheatFault · Drive overtemperature
oLOverloadFault · Drive overload
oL1Overload 1Fault · Motor overload or overtemperature
oL2Overload 2Fault · Motor overload or overtemperature
cF3.4IGBT overheat (temperature sensor)A temperature sensor error. Delta's instruction is to return the drive to the factory.Fault · Temperature sensor signal
cF3.5Power board overheat (temperature sensor)A temperature sensor error. Delta's instruction is to return the drive to the factory.Fault · Temperature sensor signal
PtC1Motor PTC overheat protectionFault · Motor overload or overtemperature

05 / Motor and load

Motor and load

CodeNameKind
FbEPID feedback signal errorAlarm · Process limit

06 / Signals and communication

Signals and communication

CodeNameKind
EFExternal faultFault · External fault
AErrACI signal errorFault · Analog signal loss
PGErPG feedback signal errorFault · Encoder signal
cE01Illegal function codeThe Modbus master sent a function code the drive does not support. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring.Alarm · Communication loss
cE02Illegal data addressThe Modbus master sent a data address the drive does not have. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring.Alarm · Communication loss
cE03Illegal data valueThe Modbus master sent a data value the drive cannot accept. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring.Alarm · Communication loss
cE04Slave device failureThe drive could not carry out the action the master requested. Check the RS485 connection between the drive and the master for loose wires and correct pin wiring.Alarm · Communication loss
cE10Communication time-outAlarm · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
HPF1CC, OC hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
HPF2OV hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
HPF3GFF hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
HPF4OC hardware protection failureThe drive's hardware protection circuit tripped. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
cFAAuto accel/decel failureFault · Setup
codESoftware protection failureThe software or password protection tripped. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
cF1.0Power board CPU write failureThe internal EEPROM could not be written. Delta's instruction is to return the drive to the factory.Fault · Parameter memory
cF1.1Control board CPU write failureThe internal EEPROM could not be written. Delta's instruction is to return the drive to the factory.Fault · Parameter memory
cF2.0Power board CPU read failureThe internal EEPROM could not be read. Press RESET to set all parameters back to factory settings.Fault · Parameter memory
cF2.1Control board CPU read failureThe internal EEPROM could not be read. Press RESET to set all parameters back to factory settings.Fault · Parameter memory
cF3.0U-phase errorAn internal error on output phase U. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
cF3.1V-phase errorAn internal error on output phase V. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
cF3.2W-phase errorAn internal error on output phase W. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
cF3.3DC bus errorAn internal over- or under-voltage error on the DC bus. Delta's instruction is to return the drive to the factory.Fault · Internal drive fault
CP10Control board and power board communication time-outCommunication between the control board and the power board timed out. Press RESET to set all parameters back to factory settings.Fault · Internal drive fault
ACLAbnormal communication loopFault · Internal drive fault
AUEAuto tuning errorAlarm · Motor identification

Related

Related pages

Source

Delta Electronics, VFD-E Series User Manual, Revision Jan. 2012 (08EE), Chapter 6, Fault Code Information and Maintenance.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007