The SINAMICS V20 is Siemens' compact general-purpose inverter, sold in single-phase 230 V and three-phase 400 V versions for pumps, fans, conveyors and simple machines. Many Indian plants run it in place of the older MICROMASTER 420.
On the V20 a fault code starts with F and stops the motor; a code starting with A is an alarm, a warning the inverter shows while it keeps running. Below is every fault and alarm in Siemens' operating instructions, with the causes and checks Siemens gives for each.
01 / Reading codes
Reading and clearing SINAMICS V20 codes
The built-in operator panel (BOP) shows the fault number after an F, for example F1, or the alarm number after an A, for example A501. If several are active, all faults are shown first, then all alarms.
A fault stops the inverter's output; the motor will not run again until the fault is cleared. An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.
- Clear or acknowledge a fault from the BOP, or externally if the inverter is set up for it.
- Holding the function key for more than two seconds shows the inverter's status at the moment of the fault.
- Some faults (F64, F350) can only be cleared by switching the power off and on, and F5 cannot be cleared until the inverter's overload utilisation has fallen below its warning level.
02 / Current and earth faults
Current and earth faults
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| F2 | Overvoltage | Fault · DC bus overvoltage |
| F3 | Undervoltage | Fault · DC bus undervoltage |
| F20 | DC ripple too high | Fault · Input phase loss |
| A502 | Overvoltage limit | Alarm · DC bus overvoltage |
| A503 | Undervoltage limit | Alarm · DC bus undervoltage |
| A535 | Braking resistor overload | Alarm · Braking resistor |
| A910 | Vdc_max controller deactivated | Alarm · DC bus overvoltage |
| A911 | Vdc_max controller active | Alarm · DC bus overvoltage |
| A912 | Vdc_min controller active | Alarm · DC bus undervoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| F4 | Inverter overtemperature | Fault · Drive overtemperature |
| F5 | Inverter I2t | Fault · Drive overload |
| F6 | Chip temperature rise exceeds critical levels | Fault · Drive overtemperature |
| F11 | Motor overtemperature | Fault · Motor overload or overtemperature |
| F12 | Inverter temperature signal lost | Fault · Temperature sensor signal |
| A504 | Inverter overtemperature | Alarm · Drive overtemperature |
| A505 | Inverter I2t | Alarm · Drive overload |
| A506 | IGBT junction temperature rise warning | Alarm · Drive overtemperature |
| A507 | Inverter temperature signal lost | Alarm · Temperature sensor signal |
| A511 | Motor overtemperature I2t | Alarm · Motor overload or overtemperature |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| F221 | PID feedback below minimum value | Fault · Process limit |
| F222 | PID feedback above maximum value | Fault · Process limit |
| F410 | Cavitation protection failure | Fault · Process limit |
| F452 | Load monitoring trip | Fault · Load monitoring |
| A930 | Cavitation protection warn | Alarm · Process limit |
| A952 | Load monitoring warning | Alarm · Load monitoring |
06 / Signals and communication
Signals and communication
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| F35 | Maximum number of auto restart attempts exceeded | Fault · Automatic restart limit |
| F41 | Motor data identification failure | Fault · Motor identification |
| F51 | Parameter EEPROM fault | Fault · Parameter memory |
| F52 | Inverter software fault | Fault · Internal drive fault |
| F60 | Asic timeout | Fault · Internal drive fault |
| F61 | SD card parameter cloning failedr0949 = 0: no SD card, the wrong card type, or the card failed to initialise. Use an SD card formatted FAT16 or FAT32, and check it is not full. | Fault · Parameter memory |
| F62 | Parameter cloning contents invalidThe clone file exists but its contents are not valid. Copy the file again and make sure the operation completes. | Fault · Parameter memory |
| F63 | Parameter cloning contents incompatibleThe clone file is from a different inverter type. Clone only from a compatible inverter type. | Fault · Parameter memory |
| F64 | Inverter attempted to do an automatic clone during startupThere is no Clone00.bin file in /USER/SINAMICS/DATA on the card. If an automatic clone is wanted, insert the card with the correct file and power-cycle. | Fault · Parameter memory |
| F100 | Watchdog reset | Fault · Internal drive fault |
| F101 | Stack overflow | Fault · Internal drive fault |
| F200 | Script errorThe inverter's internal program script stopped because of a script error. Check the script and correct it. | Fault · Internal drive fault |
| F350 | Configuration vector for the inverter failed | Fault · Internal drive fault |
| F395 | Acceptance test/confirmation pending | Fault · Parameter memory |
| A541 | Motor data identification activeMotor data identification (P1900) is selected or running. | Alarm · Setup |
| A600 | RTOS overrun warningAn internal time slice overrun. Contact Siemens service. | Alarm · Internal drive fault |
| A921 | Analog output parameters not set properlyThe analog output parameters P0777 and P0779 are set to the same value. Set P0777 and P0779 to different values. | Alarm · Setup |
| A923 | Both JOG left and JOG right are requestedJOG right and JOG left (P1055/P1056) have both been requested, which freezes the output frequency where it is. Do not request JOG right and left at the same time. | Alarm · Setup |
| A936 | PID autotuning activePID autotuning (P2350) is selected or running. The alarm clears when autotuning finishes. | Alarm · Setup |
Related
Related pages
Source
Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.