The C2000 is Delta Electronics' vector control AC drive, built in 230 V, 460 V, 575 V and 690 V series. Its faults show on the KPC-CC01 keypad as short codes such as ocA, ovd, GFF or oH1, and the drive records them by number.
Below is every fault in chapter 14 of Delta's C2000 user manual, with the description, the causes and the corrective actions Delta lists for each, and how each one resets.
01 / Reading codes
Reading and clearing C2000 codes
The KPC-CC01 digital keypad shows the fault code, for example ocA for over-current during acceleration; its backlight blinks until the fault is cleared. The six most recent faults are kept in Pr. 06-17 (the present fault) to Pr. 06-22, and the keypad's Fault Record menu shows the DC bus voltage, output current and output voltage at the time of each fault.
A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop. Several faults can be set as warnings instead, through their fault treatment parameter (for example Pr. 06-29 for oH3, Pr. 06-06 for ot1, Pr. 06-45 for OPHL). Set as a warning, the drive keeps running and the warning clears itself once the condition is gone.
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| ocA | Over-current during acceleration | Fault · Overcurrent |
| ocd | Over-current during deceleration | Fault · Overcurrent |
| ocn | Over-current during steady operation | Fault · Overcurrent |
| GFF | Ground fault | Fault · Earth fault |
| occ | IGBT short circuit between upper bridge and lower bridge | Fault · Output short circuit |
| ocS | Over-current at stop | Fault · Overcurrent |
| OPHL | Output phase loss | Fault · Output phase loss |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| ovA | Over-voltage during acceleration | Fault · DC bus overvoltage |
| ovd | Over-voltage during deceleration | Fault · DC bus overvoltage |
| ovn | Over-voltage at constant speed | Fault · DC bus overvoltage |
| ovS | Over-voltage at stop | Fault · DC bus overvoltage |
| LvA | Low-voltage during acceleration | Fault · DC bus undervoltage |
| Lvd | Low-voltage during deceleration | Fault · DC bus undervoltage |
| Lvn | Low-voltage at constant speed | Fault · DC bus undervoltage |
| LvS | Low-voltage at stop | Fault · DC bus undervoltage |
| OrP | Phase loss protection | Fault · Input phase loss |
| bF | Brake transistor error | Fault · Braking resistor |
| dEb | Deceleration energy backup error | Fault · DC bus undervoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| oH1 | IGBT overheating | Fault · Drive overtemperature |
| oH2 | Heatsink overheating | Fault · Drive overtemperature |
| tH1o | IGBT temperature detection failureA hardware failure in IGBT temperature detection: a broken NTC or a wiring failure. Wait 10 minutes, then switch the power off and on. | Fault · Temperature sensor signal |
| tH2o | Capacitor hardware errorA hardware failure in capacitor temperature detection: a broken NTC or a wiring failure. Wait 10 minutes, then switch the power off and on. | Fault · Temperature sensor signal |
| oL | Over load | Fault · Drive overload |
| EoL1 | Electronic thermal relay 1 protection | Fault · Motor overload or overtemperature |
| EoL2 | Electronic thermal relay 2 protection | Fault · Motor overload or overtemperature |
| oH3 | Motor overheating | Fault · Motor overload or overtemperature |
| oL3 | Overload protection at low frequency | Fault · Drive overload |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| ot1 | Over torque 1 | Fault · Load monitoring |
| ot2 | Over torque 2 | Fault · Load monitoring |
| uC | Under current | Fault · Load monitoring |
| oSL | Over slip error | Fault · Motor stall |
| SdRv | Reverse direction of the speed feedback | Fault · Motor stall |
| SdOr | Over speed rotation feedback | Fault · Motor stall |
| SdDe | Large deviation of speed feedback | Fault · Motor stall |
| SfLK | PMLess shaft lock | Fault · Motor stall |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| LMIT | Limit error | Fault · External fault |
| AFE | PID loss ACI | Fault · Analog signal loss |
| PGF1 | PG feedback error | Fault · Encoder signal |
| PGF2 | PG feedback loss | Fault · Encoder signal |
| PGF3 | PG feedback stall | Fault · Encoder signal |
| PGF4 | PG slip error | Fault · Encoder signal |
| ACE | ACI loss | Fault · Analog signal loss |
| EF | External faultAn input set as an external fault (EF) switched on. Clear the external fault, then press RESET. | Fault · External fault |
| EF1 | Emergency stopAn input set as emergency stop (EF1) switched on. Check the system is back to normal, then press RESET. | Fault · External fault |
| bb | External base blockAn input set as base block (bb) switched on. Check the system is back to normal, then press RESET. | Fault · External fault |
| CE1 | Illegal command | Fault · Communication loss |
| CE2 | Illegal data address | Fault · Communication loss |
| CE3 | Illegal data value | Fault · Communication loss |
| CE4 | Data is written to read-only address | Fault · Communication loss |
| CE10 | MODBUS transmission time-out | Fault · Communication loss |
| ydc | Y-connection / Δ-connection switch error | Fault · External fault |
| PGF5 | Hardware error of PG card | Fault · Encoder signal |
| STL1 | STO Loss 1 | Fault · Safety input |
| S1 | Emergency stop for external safety | Fault · Safety input |
| Brk | External brake error | Fault · External fault |
| STO | Safety Torque Off function active | Fault · Safety input |
| STL2 | STO Loss 2 | Fault · Safety input |
| STL3 | STO Loss 3 | Fault · Safety input |
| AboF | PG ABZ line off | Fault · Encoder signal |
| UvoF | PG UVW line off | Fault · Encoder signal |
| FStp | Force to stop | Fault · External fault |
| CGdE | CANopen guarding error | Fault · Communication loss |
| CHbE | CANopen heartbeat error | Fault · Communication loss |
| CbFE | CANopen bus off error | Fault · Communication loss |
| CIdE | CANopen index errorThe CANopen index is set wrongly. Reset CANopen (Pr. 00-02 = 7). | Fault · Communication loss |
| CAdE | CANopen station address errorThe CANopen station address is set wrongly (only 1 to 127 is allowed). Disable CANopen (Pr. 09-36 = 0). | Fault · Communication loss |
| CFrE | CANopen memory errorA CANopen internal memory error, for example after the control board's firmware was updated without the internal data changing. Disable CANopen (Pr. 09-36 = 0). | Fault · Communication loss |
| ictE | InrCOM time-out error | Fault · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| cF1 | EEPROM write errorThe internal EEPROM cannot be written. Press RESET or reset the parameters to their defaults. If it is still there, Delta's instruction is to return the drive to the factory for repair. | Fault · Parameter memory |
| cF2 | EEPROM read errorThe internal EEPROM cannot be read. Press RESET or reset the parameters to their defaults. If it is still there, Delta's instruction is to return the drive to the factory for repair. | Fault · Parameter memory |
| cd1 | U-phase errorA hardware failure in the drive. Switch the power off and on again. | Fault · Internal drive fault |
| cd2 | V-phase errorA hardware failure in the drive. Switch the power off and on again. | Fault · Internal drive fault |
| cd3 | W-phase errorA hardware failure in the drive. Switch the power off and on again. | Fault · Internal drive fault |
| Hd0 | cc hardware failureA hardware failure in the drive. Switch the power off and on again. | Fault · Internal drive fault |
| Hd1 | oc hardware errorA hardware failure in the drive. Switch the power off and on again. | Fault · Internal drive fault |
| Hd2 | ov hardware errorA hardware failure in the drive. Switch the power off and on again. | Fault · Internal drive fault |
| Hd3 | occ hardware errorA hardware failure in the drive. Switch the power off and on again. | Fault · Internal drive fault |
| AUE | Auto-tuning error | Fault · Motor identification |
| Pcod | Password is locked | Fault · Setup |
| ryF | Electric valve switch error | Fault · Internal drive fault |
| WDTT | Watchdog errorHardware interference. Check the control-circuit wiring and the main-circuit wiring and grounding, to keep interference out. | Fault · Internal drive fault |
| RoPd | Rotor position detection error | Fault · Internal drive fault |
| TRAP | CPU error 0 | Fault · Internal drive fault |
| AUE1 | Auto-tune error 1 | Fault · Motor identification |
| AUE2 | Auto-tune error 2 | Fault · Motor identification |
| AUE3 | Auto-tune error 3 | Fault · Motor identification |
| AUE4 | Auto-tune error 4 | Fault · Motor identification |
| CBM | C/B mismatchThe wrong control board is fitted. Fit the correct control board. If CBM stays, contact Delta. | Fault · Internal drive fault |