The PowerFlex 525 is Rockwell Automation's compact AC drive with built-in EtherNet/IP and safe torque off, sold under the Allen-Bradley name; the PowerFlex 523 is its simpler sibling. Both use one fault table, and Rockwell marks the few codes that only the 525 can show.
PowerFlex 520-series fault codes are an F followed by three digits. Below is every fault in Rockwell's PowerFlex 520-series quick start guide, with the action Rockwell gives for each.
01 / Reading codes
Reading and clearing PowerFlex 525 codes
The drive's LCD keypad shows the fault number after an F, for example F004, with the fault's name scrolling beside it.
A fault stops the drive; it will not restart until the fault is cleared.
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| F012 | HW OverCurrent | Fault · Overcurrent |
| F013 | Ground Fault | Fault · Earth fault |
| F021 | Output Ph Loss | Fault · Output phase loss |
| F038 | Phase U to Gnd | Fault · Earth fault |
| F039 | Phase V to Gnd | Fault · Earth fault |
| F040 | Phase W to Gnd | Fault · Earth fault |
| F041 | Phase UV Short | Fault · Output short circuit |
| F042 | Phase UW Short | Fault · Output short circuit |
| F043 | Phase VW Short | Fault · Output short circuit |
| F063 | SW OverCurrent | Fault · Overcurrent |
03 / Voltage and supply
Voltage and supply
04 / Temperature and overload
Temperature and overload
05 / Motor and load
Motor and load
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| F002 | Auxiliary Input | Fault · External fault |
| F029 | Analog In Loss | Fault · Analog signal loss |
| F059 | Safety Open | Fault · Safety input |
| F071 | DSI Net Loss | Fault · Communication loss |
| F072 | Opt Net Loss | Fault · Communication loss |
| F073 | EN Net Loss | Fault · Communication loss |
| F081 | DSI Comm Loss | Fault · Communication loss |
| F082 | Opt Comm Loss | Fault · Communication loss |
| F083 | EN Comm Loss | Fault · Communication loss |
| F091 | Encoder Loss | Fault · Encoder signal |
| F094 | Function Loss | Fault · External fault |
| F111 | Safety Hardware | Fault · Safety input |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| F033 | Auto Rstrt Tries | Fault · Automatic restart limit |
| F048 | Params Defaulted | Fault · Parameter memory |
| F070 | Power Unit | Fault · Internal drive fault |
| F080 | Autotune Failure | Fault · Motor identification |
| F100 | Parameter Chksum | Fault · Parameter memory |
| F101 | External Storage Set P053 [Reset To Defalts] to 2 "Factory Rset". | Fault · Parameter memory |
| F105 | C Connect Err | Fault · Internal drive fault |
| F106 | Incompat C-P | Fault · Internal drive fault |
| F107 | Replaced C-P | Fault · Internal drive fault |
| F109 | Mismatch C-P Set P053 [Reset To Defalts] to 3 "Power Reset". | Fault · Internal drive fault |
| F110 | Keypad Membrane Cycle power. | Fault · Internal drive fault |
| F114 | uC Failure | Fault · Internal drive fault |
| F122 | I/O Board Fail | Fault · Internal drive fault |
| F125 | Flash Update Req Perform a firmware flash update to load a valid set of firmware. | Fault · Internal drive fault |
| F126 | NonRecoverablErr | Fault · Internal drive fault |
| F127 | DSIFlashUpdatReq Perform a firmware flash update over DSI communications to load a valid set of firmware. | Fault · Internal drive fault |
Related
Related pages
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.