Allen-Bradley PowerFlex 525 fault codes

The PowerFlex 525 is Rockwell Automation's compact AC drive with built-in EtherNet/IP and safe torque off, sold under the Allen-Bradley name; the PowerFlex 523 is its simpler sibling. Both use one fault table, and Rockwell marks the few codes that only the 525 can show.

PowerFlex 520-series fault codes are an F followed by three digits. Below is every fault in Rockwell's PowerFlex 520-series quick start guide, with the action Rockwell gives for each.

01 / Reading codes

Reading and clearing PowerFlex 525 codes

The drive's LCD keypad shows the fault number after an F, for example F004, with the fault's name scrolling beside it.

A fault stops the drive; it will not restart until the fault is cleared.

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

02 / Current and earth faults

Current and earth faults

CodeNameKind
F012HW OverCurrentFault · Overcurrent
F013Ground FaultFault · Earth fault
F021Output Ph LossFault · Output phase loss
F038Phase U to GndFault · Earth fault
F039Phase V to GndFault · Earth fault
F040Phase W to GndFault · Earth fault
F041Phase UV ShortFault · Output short circuit
F042Phase UW ShortFault · Output short circuit
F043Phase VW ShortFault · Output short circuit
F063SW OverCurrentFault · Overcurrent

03 / Voltage and supply

Voltage and supply

CodeNameKind
F003Power LossFault · DC bus undervoltage
F004UnderVoltageFault · DC bus undervoltage
F005OverVoltageFault · DC bus overvoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
F007Motor OverloadFault · Motor overload or overtemperature
F008Heatsink OvrTmpFault · Drive overtemperature
F009CC OvrTmpFault · Drive overtemperature
F064Drive OverloadFault · Drive overload

05 / Motor and load

Motor and load

CodeNameKind
F006Motor StalledFault · Motor stall
F015Load LossFault · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
F002Auxiliary InputFault · External fault
F029Analog In LossFault · Analog signal loss
F059Safety OpenFault · Safety input
F071DSI Net LossFault · Communication loss
F072Opt Net LossFault · Communication loss
F073EN Net LossFault · Communication loss
F081DSI Comm LossFault · Communication loss
F082Opt Comm LossFault · Communication loss
F083EN Comm LossFault · Communication loss
F091Encoder LossFault · Encoder signal
F094Function LossFault · External fault
F111Safety HardwareFault · Safety input

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
F033Auto Rstrt TriesFault · Automatic restart limit
F048Params DefaultedFault · Parameter memory
F070Power UnitFault · Internal drive fault
F080Autotune FailureFault · Motor identification
F100Parameter ChksumFault · Parameter memory
F101External Storage Set P053 [Reset To Defalts] to 2 "Factory Rset".Fault · Parameter memory
F105C Connect ErrFault · Internal drive fault
F106Incompat C-PFault · Internal drive fault
F107Replaced C-PFault · Internal drive fault
F109Mismatch C-P Set P053 [Reset To Defalts] to 3 "Power Reset".Fault · Internal drive fault
F110Keypad Membrane Cycle power.Fault · Internal drive fault
F114uC FailureFault · Internal drive fault
F122I/O Board FailFault · Internal drive fault
F125Flash Update Req Perform a firmware flash update to load a valid set of firmware.Fault · Internal drive fault
F126NonRecoverablErrFault · Internal drive fault
F127DSIFlashUpdatReq Perform a firmware flash update over DSI communications to load a valid set of firmware.Fault · Internal drive fault

Related

Related pages

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007