Siemens SINAMICS V90 fault codes

The SINAMICS V90 is Siemens' basic servo drive, used with SIMOTICS S-1FL6 servo motors on packaging, printing, textile and handling machines. Faults show as F codes and alarms as A codes, for example F7801 for motor overcurrent or F30001 for power unit overcurrent.

Below is every fault and alarm in the list in Siemens' V90 operating instructions (edition 04/2014), with the cause and remedy given for each, and each fault's reaction and how it is acknowledged.

01 / Reading codes

Reading and clearing SINAMICS V90 codes

The BOP shows a fault or alarm with its number, for example F7011 or A5000, and marks the first one when several are active. The RDY LED flashes slowly in red. Faults take priority: while a fault is active, alarms are not shown until the fault is acknowledged.

A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type. An alarm takes no action on the motor and acknowledges itself once the cause is gone.

  • Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
  • Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
  • If the cause is not removed, the fault can come back after five seconds with no button pressed.
  • Alarms acknowledge themselves.

02 / Current and earth faults

Current and earth faults

CodeNameKind
F7410Current controller output limitedFault · Output phase loss
F7801Motor overcurrentFault · Overcurrent
F30001Power unit: OvercurrentFault · Overcurrent
F30015Phase failure motor cableFault · Output phase loss
F30021Ground faultFault · Earth fault
A30031Hardware current limiting in phase UAlarm · Overcurrent

03 / Voltage and supply

Voltage and supply

CodeNameKind
F7403Lower DC link voltage threshold reachedFault · DC bus undervoltage
F7404Upper DC link voltage threshold reachedFault · DC bus overvoltage
F30002DC link voltage, overvoltageFault · DC bus overvoltage
F30003DC link voltage, undervoltageFault · DC bus undervoltage
F30011Line phase failure in main circuitFault · Input phase loss
F30027Precharging DC link time monitoringFault · DC bus undervoltage
A30016Load supply switched offAlarm · DC bus undervoltage
A52901Braking resistor reaches alarm thresholdAlarm · Braking resistor

04 / Temperature and overload

Temperature and overload

CodeNameKind
F7011Motor overtemperatureFault · Motor overload or overtemperature
F30004Drive heat sink overtemperatureFault · Drive overtemperature
F30005Power unit: Overload I2tFault · Drive overload
F30036Internal overtemperatureFault · Drive overtemperature
A1009Control module overtemperatureAlarm · Drive overtemperature
A5000Drive heat sink overtemperatureAlarm · Drive overtemperature
A7012Motor temperature model 1/3 overtemperatureAlarm · Motor overload or overtemperature

05 / Motor and load

Motor and load

CodeNameKind
F7450Standstill monitoring has respondedFault · Motor stall
F7452Following error too highFault · Motor stall
F7475EPOS: Target position < start of traversing rangeThe target position for relative traversing is outside the traversing range. Correct the target position.Fault · Overtravel
F7476EPOS: Target position > end of the traversing rangeThe target position for relative traversing is outside the traversing range. Correct the target position.Fault · Overtravel
F7481EPOS: Axis position < software limit switch minusFault · Overtravel
F7482EPOS: Axis position > software limit switch plusFault · Overtravel
F7491STOP cam minus reachedFault · Overtravel
F7492STOP cam plus reachedFault · Overtravel
F7900Motor blocked/speed controller at its limitFault · Motor stall
F7901Motor overspeedThe maximum permissible speed was exceeded. Check and correct the maximum speed (p1082).Fault · Load monitoring
A7469EPOS: Traversing block < target position < software limit switch minusAlarm · Overtravel
A7470EPOS: Traversing block > target position > software limit switch plusAlarm · Overtravel
A7473EPOS: Beginning of traversing range reachedThe axis reached the traversing range limit. Move away in the positive direction.Alarm · Overtravel
A7474EPOS: End of traversing range reachedThe axis reached the traversing range limit. Move away in the negative direction.Alarm · Overtravel
A7477EPOS: Target position < software limit switch minusAlarm · Overtravel
A7478EPOS: Target position > software limit switch plusAlarm · Overtravel
A7479EPOS: Software limit switch minus reachedAlarm · Overtravel
A7480EPOS: Software limit switch plus reachedAlarm · Overtravel

06 / Signals and communication

Signals and communication

CodeNameKind
F1030Sign-of-life failure for master controlWith PC master control active, no sign of life arrived within the monitoring time. Contact the Siemens hotline.Fault · Communication loss
F1611SI CU: Defect detectedFault · Safety input
F7412Commutation angle incorrect (motor model)Fault · Encoder signal
F7430Changeover to open-loop torque controlled operation not possibleFault · Encoder signal
F7431Changeover to encoderless operation not possibleFault · Encoder signal
F7443Reference point coordinate not in the permissible rangeThe reference point coordinate received when adjusting the encoder through connector input p2599 is outside half the encoder range, so it cannot be set as the actual axis position. Set the reference point coordinate below the value given in the fault value (see p2599). For a motor with an absolute encoder, the largest permissible encoder range is (4096 × p29247) / 2.Fault · Reference position
F7453Position actual value preprocessing errorAn error occurred while preprocessing the actual position value. Check the encoder used for the actual position value.Fault · Encoder signal
F7458EPOS: Reference cam not foundFault · Reference position
F7459Zero mark not detectedFault · Reference position
F7460EPOS: End of reference cam not foundFault · Reference position
F7599Encoder 1: Adjustment not possibleThe maximum encoder value, converted from increments to length units, went beyond the range for showing the actual position (-2147483648 to 2147483647). Fault · Encoder signal
F31100Zero mark distance errorFault · Encoder signal
F31110Serial communications errorA serial protocol transfer error between the encoder and the evaluation module. Contact the Siemens hotline.Fault · Encoder signal
F31112Error bit set in the serial protocolThe encoder sends an error bit through the serial protocol. Contact the Siemens hotline.Fault · Encoder signal
F31117Inversion error signals A/B/RFault · Encoder signal
F31130Zero mark and position error from the coarse synchronizationFault · Encoder signal
F31150Initialization errorFault · Encoder signal
F52980Absolute encoder motor changedThe servo motor with absolute encoder was changed: the motor ID differs from the commissioned one. Acknowledge the fault: the servo motor is then configured automatically.Fault · Encoder signal
F52981Absolute encoder motor mismatchedThe connected absolute encoder motor cannot be run: the servo drive does not support its motor ID. Use a suitable absolute encoder motor.Fault · Encoder signal
F52983No encoder detectedFault · Encoder signal
F52984Incremental encoder motor not configuredCommissioning of the servo motor failed: the incremental encoder motor is connected but could not be commissioned. Configure the motor ID in p29000.Fault · Encoder signal
F52985Absolute encoder motor wrongFault · Encoder signal
F52987Absolute encoder replacedThe absolute encoder data is incorrect. Contact the Siemens hotline.Fault · Encoder signal
A1920Drive Bus: Receive setpoints after ToAlarm · Communication loss
A1932Drive Bus clock cycle synchronization missing for DSCDynamic Servo Control (DSC) is selected, but there is no clock synchronisation or clock-synchronous sign of life. Set clock synchronisation in the bus configuration and transfer a clock-synchronous sign of life.Alarm · Communication loss
A7461EPOS: Reference point not setA traversing block or direct setpoint started with no reference point set. Reference the system: search for reference, flying referencing, or set the reference point.Alarm · Reference position
A7576Encoderless operation due to a fault activeAlarm · Encoder signal
A31411Absolute encoder signals internal alarmsThe absolute encoder's fault word has alarm bits set. Replace the encoder.Alarm · Encoder signal
A31412Error bit set in the serial protocolAlarm · Encoder signal
A52902Emergency missingServo on was given while the emergency input (EMGS) was off. Switch on the emergency input (EMGS), then give servo on.Alarm · Safety input

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
F1000Internal software errorFault · Internal drive fault
F1001FloatingPoint exceptionFault · Internal drive fault
F1002Internal software errorFault · Internal drive fault
F1003Acknowledgement delay when accessing the memoryFault · Internal drive fault
F1015Internal software errorFault · Internal drive fault
F1018Booting has been interrupted several timesFault · Internal drive fault
F7085Open-loop/closed-loop control parameters changedControl parameters had to be changed, because other parameters pushed them past their dynamic limits, or because the hardware lacks features they need. No change is needed: the parameters have already been limited correctly.Fault · Setup
F7442LR: Multiturn does not match the modulo rangeThe ratio between the multiturn resolution and the modulo range (p29246) is not a whole number, so the adjustment is reset: the actual position cannot be reproduced after a power cycle. Make the ratio a whole number. It is calculated as v = (4096 × p29247 × p29248) / (p29249 × p29246).Fault · Setup
F7490Enable signal withdrawn while traversingFault · Setup
F7493LR: Overflow of the value range for position actual valueFault · Setup
F7802Infeed or power unit not readyFault · Internal drive fault
F7815Power unit has been changedThe code number of the fitted power unit does not match the saved one. Connect the original power unit and power the Control Unit up again (POWER ON).Fault · Internal drive fault
F7995Motor identification failureA motor with an incremental encoder needs pole position identification at the first servo on; if the motor is already turning, for example pushed by an outside force, identification can fail. Stop the motor before switching the servo on.Fault · Motor identification
F3005024 V supply overvoltageFault · Internal drive fault
F52903Fault inconsistence between fault status and fault bufferThe fault status and the fault number buffer do not match. Power the drive off and on.Fault · Internal drive fault
F52904Control mode changeThe control mode was changed: the drive must be saved and restarted. Save and restart the drive.Fault · Setup
F52911Positive torque limitation value errorOne of the positive torque limit values (P29050) is below 0. Set all the positive torque limit values (P29050) to 0 or more.Fault · Setup
F52912Negative torque limitation value errorOne of the negative torque limit values (P29051) is above 0. Set all the negative torque limit values (P29051) to 0 or less.Fault · Setup
F52931Gear box limitThe electronic gear ratio (p29012[x] / p29013[x]) is outside the range 0.02 to 200. Set the electronic gear ratio within 0.02 to 200.Fault · Setup
A1019Writing to the removable data medium unsuccessfulWriting to the removable data medium failed. Remove and check the data medium, then run the data backup again.Alarm · Parameter memory
A1032All parameters must be savedOne drive object's parameters were saved, but there is no backup of all the drive system's parameters yet. The saved object-specific parameters will not load at the next power-up. Save all parameters.Alarm · Parameter memory
A1045Configuring data invalidAn error was found in the parameter files saved in non-volatile memory, so some saved values may not have been accepted. Save the parameters with "Copy RAM to ROM" in SINAMICS V-ASSISTANT, or on the BOP. This overwrites the bad files and the alarm goes.Alarm · Parameter memory
A7441LR: Save the position offset of the absolute encoder adjustmentThe absolute encoder adjustment changed, and the position offset (p2525) must be saved to keep it. None needed: the alarm disappears once the offset is saved.Alarm · Setup
A7456EPOS: Setpoint velocity limitedThe setpoint velocity is above the set maximum velocity, so it is limited. Reduce the setpoint velocity.Alarm · Setup
A7471EPOS: Traversing block target position outside the modulo rangeAlarm · Setup
A7472EPOS: Traversing block ABS_POS/ABS_NEG not possibleThe traversing block uses ABS_POS or ABS_NEG positioning without modulo correction activated. Correct the traversing block.Alarm · Setup
A7496SON enable missingIn PTI mode, or a compound mode with PTI, the drive is in the servo off state. Enable servo on for the drive.Alarm · Setup
A7585P-TRG or CLR activeIn PTI mode, or a compound mode with PTI, the P-TRG or CLR function is active. In PTI mode, deactivate P-TRG or CLR; in a compound mode with PTI, do not switch to other modes.Alarm · Setup
A7965Save requiredThe angular commutation offset was redefined but not yet saved. Save it to non-volatile memory to keep the new value; the alarm then disappears.Alarm · Setup
A7971Angular commutation offset determination activatedAutomatic determination of the angular commutation offset (encoder adjustment) is activated; it runs at the next power-on command. None needed: the alarm disappears once the determination is done.Alarm · Motor identification
A7991Motor data identification activatedAlarm · Motor identification
A52900Failure during data copyingAlarm · Parameter memory
A52932PTO max limitThe PTO frequency is above its limit, which the manual gives as 120K with an incremental encoder and 280K with an absolute encoder. Change the PTO ratio.Alarm · Setup

Related

Related pages

Source

Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SINAMICS V90 fault you can't clear?

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.