Drive faults traced to the failing stage, from IGBTs and DC bus capacitors to fans and control boards, then tested on load.

  • Phone answered 24/7

    Call at any hour to report a breakdown.

  • 1 to 12 month warranty

    Depends on the repair. The term is confirmed before work starts.

  • Verified, experienced technicians

    Identity checked before a technician is sent to your plant.

  • Pickup available

    A unit that needs bench repair can be collected from the plant.

Drives & Motor Control

What we do

Most VFD failures we see in Hyderabad fall into a handful of patterns: overcurrent trips (OC) from a failing IGBT leg, overvoltage (OV) from degraded DC bus capacitors or a braking resistor that has gone open, and overheat (OH) faults caused by clogged heatsinks in dusty plant environments. We diagnose to the component rather than swapping the whole drive, which is usually a fraction of replacement cost.

We work across the full range of low-voltage industrial drives — general-purpose, vector and regenerative types, single- and three-phase — with load testing carried out before the unit goes back on your line.

New to this equipment? How a VFD (Variable Frequency Drive) works

VFD Repair near me in Hyderabad · AC Drives & VFDs we repair, by model · VFD AMC Service

Fault codes by make, from the makers' manuals: Siemens SINAMICS V20 · Siemens SINAMICS G120 · Siemens MICROMASTER 440 · Allen-Bradley PowerFlex 525 · ABB ACS355 · Delta VFD-E · Delta C2000 · Hitachi WJ200 · Schneider Electric Altivar ATV320 · INVT Goodrive20 (GD20) · Yaskawa V1000 · Yaskawa A1000 · Yaskawa GA500 · Siemens MICROMASTER 420 · Siemens MICROMASTER 430 · Siemens SINAMICS G110 · INVT Goodrive200A (GD200A) · Mitsubishi Electric FR-D700 · Danfoss VLT Micro Drive FC 51

Onsite and bench

VFD Repair in Hyderabad

MachineryFix does VFD repair across Hyderabad's industrial estates. Trips, parameters and motor wiring are checked on site; a drive with a failed power section is collected for bench repair and load-tested before it goes back.

Factories elsewhere in India are matched to the nearest partner technician who works on that equipment. Call +91 70133 33007, answered 24/7, or book online.

Scope

What's covered

  • IGBT and power module replacement with matched-pair devices
  • DC bus capacitor ESR testing and bank replacement
  • Gate driver and firing circuit board repair
  • Rectifier bridge and pre-charge circuit diagnosis
  • Cooling fan, heatsink and thermal sensor replacement
  • Parameter re-tuning and motor auto-tune after repair

Failure modes

How VFD repair service faults usually show up

  • Overcurrent trips (OC)

    Trips during acceleration often come from a short ramp time or a mechanical load problem; trips at standstill or on start usually mean a failed IGBT, a damaged motor cable or a motor insulation fault.

  • Overvoltage on deceleration (OV)

    Regenerated energy from a slowing load has nowhere to go. An open braking resistor, a failed braking chopper or a deceleration time set too short are the usual causes.

  • Overheat (OH)

    Clogged heatsinks, failed cooling fans and hot panels cause most overheat trips in Hyderabad plants, especially from April to June. The drive is reporting a real condition, so cooling is fixed before the drive is blamed.

  • Undervoltage or ground fault

    Supply dips, a failing pre-charge circuit or degraded DC bus capacitors cause undervoltage trips; ground faults point to motor or cable insulation, measured with the motor disconnected.

  • Drive powers up but the motor won't run

    Missing run permissives, a wrong control source parameter or a failed control board are checked in that order, because the first two need no parts at all.

First checks

What you can check first, and what needs a specialist

Safe for a plant electrician

  • Read the fault code and the fault history from the keypad, and note the DC bus voltage and output current values the drive logged.
  • Check that the cooling fan runs and that the heatsink and panel filter are not packed with dust.
  • With the drive isolated and the DC bus discharged as the manual specifies, look for burnt smells, bulging capacitors and loose motor terminations.
  • Check the motor itself: disconnect it and test insulation to earth with a suitable insulation tester.

Needs lockout or a specialist

  • Any measurement inside the drive before the DC bus has discharged; capacitors can hold a lethal charge after isolation.
  • Replacing IGBT modules, capacitors or control boards.
  • Changing motor or control parameters on a drive that runs a process other machines depend on.

Local conditions

In Hyderabad plants

From April to June, panel temperatures in Hyderabad plants regularly exceed what drives are rated for at full output. Many overheat and overcurrent trips in summer are cooling problems: a fan that stopped, a filter nobody cleaned since winter, or drives mounted too close together. Fixing the panel's airflow often ends the trips without touching the drive.

Voltage swings and dips on industrial feeders show up as undervoltage and overvoltage trips. A drive tripping at the same time as other machines in the plant points to the supply, and the drive's own fault log shows the bus voltage at the moment of the trip.

Before the visit

What to have ready before the technician arrives

  1. 01Photograph the drive nameplate: make, model, power rating and input voltage.
  2. 02Note the fault code and, if the keypad allows, the fault history and the values logged at the trip.
  3. 03Write down when it trips: on start, while accelerating, at speed or while stopping.
  4. 04Check whether anything changed recently: a new motor, longer cable, changed parameters or a supply problem.
  5. 05Save or photograph the drive's parameter list if you can, or keep the drive powered so it can be read.

Verification

How the repair is checked before handover

  • Power devices and the DC bus are tested before the drive is powered, so a repaired drive is not destroyed by a fault that was missed.
  • The drive is run on the actual motor and load, not only on a test bench, and output current is checked on all three phases.
  • The original parameters are restored and the motor auto-tune is repeated where the drive uses it.
  • Temperature and current are watched through acceleration, running and deceleration before handover.

Parts

Boards and parts commonly involved

  • IGBT modules and gate driver boards
  • DC bus electrolytic capacitors
  • Input rectifier bridge and pre-charge resistor or relay
  • Cooling fans, heatsink thermistors and temperature sensors
  • Braking chopper transistors and external braking resistors
  • Control boards, keypads and current sensors

Job card

What the job card records

  • Drive make, model, rating and serial number
  • Fault code and fault history on arrival
  • Measured DC bus voltage and power-device test results
  • Components replaced and the reason for each
  • Parameter backup reference and any parameters changed
  • Load test readings: output current per phase and heatsink temperature

Questions

VFD Repair Service: common questions

My VFD keeps tripping on overcurrent (F0003 / OC). What causes that?+

Recurring overcurrent is usually a failing IGBT leg, a shorted motor winding, or acceleration ramps set too aggressively for the load. We meter the IGBT legs, megger the motor, and review the ramp and current-limit parameters before replacing anything — swapping the drive without finding the cause normally just repeats the fault.

Is it cheaper to repair a VFD or replace it?+

Component-level repair is typically a fraction of replacement cost, and for older or obsolete drives it is often the only option since the model is no longer sold. If the power stage and control board are both damaged, or spares are unobtainable, we will tell you replacement is the better call rather than quoting an uneconomic repair.

Is it worth repairing a VFD or should we buy a new one?+

For mid and large drives, component-level repair usually costs a fraction of replacement and avoids re-engineering the panel. For small drives where a replacement is cheap and in stock, replacement can make more sense. The technician tells you which applies after testing.

Why does our VFD trip only in summer?+

Panel temperatures in Hyderabad summers can push drives past their rated ambient. Blocked panel filters, failed fans and drives mounted without clearance are the usual causes; better panel ventilation often stops the trips without touching the drive.

Can you repair drives that show no display at all?+

Yes. A dead display usually means a failed internal power supply, a blown input stage or a failed pre-charge circuit. These are diagnosed with the drive isolated before any power is applied.

Will our settings be kept after the repair?+

Parameters are read and saved before work starts wherever the drive allows it, and restored afterwards. If the drive can't be read, the settings are rebuilt from the motor nameplate and the machine's requirements and recorded on the job card.

What does a VFD fault history tell the technician?+

Most drives store the last several faults with the DC bus voltage, output current, frequency and heatsink temperature at the moment of each trip. That record shows whether trips line up with acceleration, braking, heat or supply events, which narrows the search before the drive is opened.

How much does VFD repair cost?+

It depends on the drive's rating, which section has failed (IGBTs, DC bus capacitors, control card, fan or power supply) and whether parts for that model are available. The technician diagnoses first and explains the repair before any work starts. Whether the diagnosis visit itself is charged depends on where the plant is, so ask when you call.

Is there a warranty on VFD repair?+

Yes. VFD repair carries a 1 to 12 month warranty depending on the repair, confirmed before work starts.

Where can I get VFD repair or VFD service near me?+

In Hyderabad, MachineryFix technicians come to the plant across the city's industrial estates, from Uppal and Cherlapally to Jeedimetla and Patancheru. Elsewhere in India, the job goes to the nearest partner technician who works on that equipment. Call +91 70133 33007, answered 24/7, or send the fault code on WhatsApp.

Guides

Related guides

Related

Related services

Written & reviewed by MachineryFix

Last reviewed — questions? Call +91 70133 33007