The MICROMASTER 440 (MM440) is Siemens' vector-control inverter from the MICROMASTER 4 range. Siemens has since replaced it with the SINAMICS G120, but MM440 drives are still running on conveyors, pumps, extruders and machine tools in many Indian plants, which is why its codes are still searched every day.
An MM440 fault code starts with F and a four-digit number (F0001); alarms start with A (A0501). Below is every fault and alarm in Siemens' MM440 parameter list, with the causes and checks Siemens gives.
01 / Reading codes
Reading and clearing MICROMASTER 440 codes
The BOP or AOP shows the fault as F followed by four digits, for example F0001, and alarms as A followed by four digits, for example A0501.
On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset. An alarm is a warning the inverter shows while it keeps running; some alarms reduce the output or pulse frequency to protect the inverter.
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| F0001 | Overcurrent | Fault · Overcurrent |
| F0021 | Ground fault | Fault · Earth fault |
| F0022 | Hardware monitoring active | Fault · Overcurrent |
| F0023 | Output fault | Fault · Output phase loss |
| F0422 | No load applied to inverterNo load is connected to the inverter, so some functions may not work as they would under normal load. | Fault · Output phase loss |
| A0501 | Current limit value | Alarm · Overcurrent |
| A0523 | Output fault | Alarm · Output phase loss |
| A0922 | No load at the inverter | Alarm · Output phase loss |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| F0002 | Overvoltage | Fault · DC bus overvoltage |
| F0003 | Undervoltage | Fault · DC bus undervoltage |
| F0020 | Line supply phase missing | Fault · Input phase loss |
| A0502 | Overvoltage limit value | Alarm · DC bus overvoltage |
| A0503 | Undervoltage limit value | Alarm · DC bus undervoltage |
| A0535 | Brake resistor hot | Alarm · Braking resistor |
| A0910 | Vdc-max controller disabled/switched-out | Alarm · DC bus overvoltage |
| A0911 | Vdc-max controller active | Alarm · DC bus overvoltage |
| A0912 | Vdc-min controller active | Alarm · DC bus undervoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| F0004 | Inverter overtemperature | Fault · Drive overtemperature |
| F0005 | Inverter I2T | Fault · Drive overload |
| F0011 | Motor overtemperature | Fault · Motor overload or overtemperature |
| F0012 | No inverter temperature signal | Fault · Temperature sensor signal |
| F0015 | No motor temperature signal | Fault · Temperature sensor signal |
| F0024 | Rectifier temperature too high | Fault · Drive overtemperature |
| F0030 | Fan failed | Fault · Cooling fan |
| A0504 | Inverter overtemperature | Alarm · Drive overtemperature |
| A0505 | Inverter I2T | Alarm · Drive overload |
| A0506 | Inverter load duty cycle | Alarm · Drive overtemperature |
| A0511 | Motor overtemperature | Alarm · Motor overload or overtemperature |
| A0520 | Rectifier overtemperature | Alarm · Drive overtemperature |
| A0521 | Ambient temperature too high | Alarm · Drive overtemperature |
05 / Motor and load
Motor and load
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| F0070 | CB setpoint fault | Fault · Communication loss |
| F0071 | USS (BOP link) setpoint fault | Fault · Communication loss |
| F0072 | USS (COMM link) setpoint fault | Fault · Communication loss |
| F0080 | ADC input signal lost | Fault · Analog signal loss |
| F0085 | External fault | Fault · External fault |
| F0090 | Signal loss, encoder | Fault · Encoder signal |
| A0590 | Alarm, no signals from the speed encoder | Alarm · Encoder signal |
| A0700 | CB alarm 1Specific to the communications board (CB) fitted. A0701 to A0709 (CB alarms 2 to 10) are the same kind of alarm. Refer to the user manual for the communications board fitted. | Alarm · Communication loss |
| A0710 | CB communications error | Alarm · Communication loss |
| A0711 | CB communications error | Alarm · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| F0035 | Restart after n | Fault · Automatic restart limit |
| F0040 | Fault, for automatic calibration | Fault · Internal drive fault |
| F0041 | Failure, motor data identification | Fault · Motor identification |
| F0042 | Fault/error when optimizing the speed controllerr0949 = 0: the time slice ran out while waiting for a stable speed. | Fault · Motor identification |
| F0051 | Parameter EEPROM fault | Fault · Parameter memory |
| F0052 | Power stack fault | Fault · Internal drive fault |
| F0053 | I/O EEPROM fault | Fault · Internal drive fault |
| F0054 | Incorrect I/O module | Fault · Internal drive fault |
| F0060 | Asic time slice overflow | Fault · Internal drive fault |
| F0101 | Stack overflow | Fault · Internal drive fault |
| F0450 | Failure BIST tests | Fault · Internal drive fault |
| A0522 | Read I2C, time exceededCyclic access to UCE values and power module data over the I2C bus is faulted (frame sizes FX and GX only). | Alarm · Internal drive fault |
| A0541 | Motor data identification routine activeMotor data identification (P1910) is selected and running. | Alarm · Setup |
| A0542 | Speed controller optimization runningSpeed controller optimisation (P1960) is selected and running. | Alarm · Setup |
| A0600 | RTOS data loss alarmA time slice overflow was detected. Use a lower baud rate for USS. | Alarm · Internal drive fault |
| A0920 | ADC parameters not correctly setAnalog input parameters are set to identical values, which gives illogical results. | Alarm · Setup |
| A0921 | DAC parameters not set properlyThe analog output parameters P0777 and P0779, or P0778 and P0780, have identical values. Make sure P0777 and P0779 are different, and P0778 and P0780 are different. | Alarm · Setup |
| A0923 | JOG counter-clockwise as well as JOG clockwise are requestedJOG clockwise and JOG counter-clockwise (P1055/P1056) are both requested, so the output frequency is frozen. | Alarm · Setup |
| A0936 | PID auto tuning activePID autotuning (P2350) is selected or running. The alarm resets when autotuning is complete. | Alarm · Setup |
Related
Related pages
Source
Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007