MachineryFix

AC drive (VFD) · 64 codes

Siemens MICROMASTER 440 fault codes

The MICROMASTER 440 (MM440) is Siemens' vector-control inverter from the MICROMASTER 4 range. Siemens has since replaced it with the SINAMICS G120, but MM440 drives are still running on conveyors, pumps, extruders and machine tools in many Indian plants, which is why its codes are still searched every day.

An MM440 fault code starts with F and a four-digit number (F0001); alarms start with A (A0501). Below is every fault and alarm in Siemens' MM440 parameter list, with the causes and checks Siemens gives.

01 / Reading codes

Reading and clearing MICROMASTER 440 codes

The BOP or AOP shows the fault as F followed by four digits, for example F0001, and alarms as A followed by four digits, for example A0501.

On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset. An alarm is a warning the inverter shows while it keeps running; some alarms reduce the output or pulse frequency to protect the inverter.

  • Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

02 / Current and earth faults

Current and earth faults

CodeNameKind
F0001OvercurrentFault · Overcurrent
F0021Ground faultFault · Earth fault
F0022Hardware monitoring activeFault · Overcurrent
F0023Output faultFault · Output phase loss
F0422No load applied to inverterNo load is connected to the inverter, so some functions may not work as they would under normal load. Fault · Output phase loss
A0501Current limit valueAlarm · Overcurrent
A0523Output faultAlarm · Output phase loss
A0922No load at the inverterAlarm · Output phase loss

03 / Voltage and supply

Voltage and supply

CodeNameKind
F0002OvervoltageFault · DC bus overvoltage
F0003UndervoltageFault · DC bus undervoltage
F0020Line supply phase missingFault · Input phase loss
A0502Overvoltage limit valueAlarm · DC bus overvoltage
A0503Undervoltage limit valueAlarm · DC bus undervoltage
A0535Brake resistor hotAlarm · Braking resistor
A0910Vdc-max controller disabled/switched-outAlarm · DC bus overvoltage
A0911Vdc-max controller activeAlarm · DC bus overvoltage
A0912Vdc-min controller activeAlarm · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
F0004Inverter overtemperatureFault · Drive overtemperature
F0005Inverter I2TFault · Drive overload
F0011Motor overtemperatureFault · Motor overload or overtemperature
F0012No inverter temperature signalFault · Temperature sensor signal
F0015No motor temperature signalFault · Temperature sensor signal
F0024Rectifier temperature too highFault · Drive overtemperature
F0030Fan failedFault · Cooling fan
A0504Inverter overtemperatureAlarm · Drive overtemperature
A0505Inverter I2TAlarm · Drive overload
A0506Inverter load duty cycleAlarm · Drive overtemperature
A0511Motor overtemperatureAlarm · Motor overload or overtemperature
A0520Rectifier overtemperatureAlarm · Drive overtemperature
A0521Ambient temperature too highAlarm · Drive overtemperature

05 / Motor and load

Motor and load

CodeNameKind
F0221PID feedback below the minimum valueFault · Process limit
F0222PID feedback above maximum valueFault · Process limit
F0452Load torque fault detectedFault · Load monitoring
F0453Motor stalledFault · Motor stall
A0952Load fault detectedAlarm · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
F0070CB setpoint faultFault · Communication loss
F0071USS (BOP link) setpoint faultFault · Communication loss
F0072USS (COMM link) setpoint faultFault · Communication loss
F0080ADC input signal lostFault · Analog signal loss
F0085External faultFault · External fault
F0090Signal loss, encoderFault · Encoder signal
A0590Alarm, no signals from the speed encoderAlarm · Encoder signal
A0700CB alarm 1Specific to the communications board (CB) fitted. A0701 to A0709 (CB alarms 2 to 10) are the same kind of alarm. Refer to the user manual for the communications board fitted.Alarm · Communication loss
A0710CB communications errorAlarm · Communication loss
A0711CB communications errorAlarm · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
F0035Restart after nFault · Automatic restart limit
F0040Fault, for automatic calibrationFault · Internal drive fault
F0041Failure, motor data identificationFault · Motor identification
F0042Fault/error when optimizing the speed controllerr0949 = 0: the time slice ran out while waiting for a stable speed. Fault · Motor identification
F0051Parameter EEPROM faultFault · Parameter memory
F0052Power stack faultFault · Internal drive fault
F0053I/O EEPROM faultFault · Internal drive fault
F0054Incorrect I/O moduleFault · Internal drive fault
F0060Asic time slice overflowFault · Internal drive fault
F0101Stack overflowFault · Internal drive fault
F0450Failure BIST testsFault · Internal drive fault
A0522Read I2C, time exceededCyclic access to UCE values and power module data over the I2C bus is faulted (frame sizes FX and GX only). Alarm · Internal drive fault
A0541Motor data identification routine activeMotor data identification (P1910) is selected and running. Alarm · Setup
A0542Speed controller optimization runningSpeed controller optimisation (P1960) is selected and running. Alarm · Setup
A0600RTOS data loss alarmA time slice overflow was detected. Use a lower baud rate for USS.Alarm · Internal drive fault
A0920ADC parameters not correctly setAnalog input parameters are set to identical values, which gives illogical results. Alarm · Setup
A0921DAC parameters not set properlyThe analog output parameters P0777 and P0779, or P0778 and P0780, have identical values. Make sure P0777 and P0779 are different, and P0778 and P0780 are different.Alarm · Setup
A0923JOG counter-clockwise as well as JOG clockwise are requestedJOG clockwise and JOG counter-clockwise (P1055/P1056) are both requested, so the output frequency is frozen. Alarm · Setup
A0936PID auto tuning activePID autotuning (P2350) is selected or running. The alarm resets when autotuning is complete.Alarm · Setup

Related

Related pages

Source

Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007