MachineryFix

AC drive (VFD) · 117 codes

ABB ACS355 fault codes

The ACS355 is ABB's compact AC drive, built in frame sizes R0 to R4 with safe torque off (STO) on board and optional fieldbus adapters.

ACS355 codes come in three sets: faults from the drive (F0001 to F1017), alarms from the drive (A2001 to A2035), and alarms the basic control panel raises about itself (A5001 to A5092). Below is every one in ABB's ACS355 user's manual, with the cause and the action ABB gives.

01 / Reading codes

Reading and clearing ACS355 codes

The basic control panel shows a fault as F and four digits, for example F0011, and an alarm as A and four digits, for example A2019. Alarms only appear on the panel when parameter 1610 DISPLAY ALARMS is set to 1 (YES). With no panel attached, a red LED on the drive means a fault and a blinking green LED means an alarm.

A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset. An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.

  • Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
  • If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
  • Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.

02 / Current and earth faults

Current and earth faults

CodeNameKind
F0001OVERCURRENTFault · Overcurrent
F0004SHORT CIRCFault · Output short circuit
F0016EARTH FAULTFault · Earth fault
F0034MOTOR PHASEFault · Output phase loss
A2001OVERCURRENTAlarm · Overcurrent

03 / Voltage and supply

Voltage and supply

CodeNameKind
F0002DC OVERVOLTFault · DC bus overvoltage
F0006DC UNDERVOLTFault · DC bus undervoltage
F0022SUPPLY PHASEFault · Input phase loss
F0035OUTP WIRINGFault · Power wiring
A2002OVERVOLTAGEAlarm · DC bus overvoltage
A2003UNDERVOLTAGEAlarm · DC bus undervoltage
A2026INPUT PHASE LOSSAlarm · Input phase loss
A5031Drive is not ready for operation, for example because of low DC voltage Check the input power supply.Alarm · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
F0003DEV OVERTEMPFault · Drive overtemperature
F0009MOT OVERTEMPFault · Motor overload or overtemperature
F0018THERM FAILFault · Temperature sensor signal
F0037CB OVERTEMPFault · Drive overtemperature
A2009DEVICE OVERTEMPAlarm · Drive overtemperature
A2010MOTOR TEMPAlarm · Motor overload or overtemperature

05 / Motor and load

Motor and load

CodeNameKind
F0012MOTOR STALLFault · Motor stall
F0017UNDERLOADFault · Load monitoring
F0024OVERSPEEDFault · Load monitoring
A2011UNDERLOADAlarm · Load monitoring
A2012MOTOR STALLAlarm · Motor stall
A2018PID SLEEPThe PID sleep function has put the drive into sleep mode. See parameter groups 40 PROCESS PID SET 1 and 41 PROCESS PID SET 2.Alarm · Process limit

06 / Signals and communication

Signals and communication

CodeNameKind
F0007AI1 LOSSFault · Analog signal loss
F0008AI2 LOSSFault · Analog signal loss
F0010PANEL LOSSFault · Communication loss
F0014EXT FAULT 1Fault · External fault
F0015EXT FAULT 2Fault · External fault
F0023ENCODER ERRFault · Encoder signal
F0028SERIAL 1 ERRFault · Communication loss
F0029EFB CON FILEThe embedded fieldbus could not read its configuration files. See the fieldbus user's manual.Fault · Communication loss
F0030FORCE TRIPThe fieldbus sent a trip command. The trip came from the fieldbus master; see the fieldbus user's manual.Fault · External fault
F0044SAFE TORQUE OFFFault · Safety input
F0045STO1 LOSTFault · Safety input
F0046STO2 LOSTFault · Safety input
A2005IO COMMAlarm · Communication loss
A2006AI1 LOSSAlarm · Analog signal loss
A2007AI2 LOSSAlarm · Analog signal loss
A2008PANEL LOSSAlarm · Communication loss
A2021START ENABLE 1 MISSINGAlarm · External fault
A2022START ENABLE 2 MISSINGAlarm · External fault
A2023EMERGENCY STOPAlarm · Safety input
A2024ENCODER ERRORAlarm · Encoder signal
A2035SAFE TORQUE OFFAlarm · Safety input
A5001Drive is not responding Check the panel connection.Alarm · Communication loss
A5002Incompatible communication profile Contact ABB.Alarm · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
F0011ID RUN FAILFault · Motor identification
F0021CURR MEASAn internal fault: the drive's current measurement is out of range. Replace the drive.Fault · Internal drive fault
F0027CONFIG FILEAn internal configuration file error. Replace the drive.Fault · Internal drive fault
F0036INCOMPATIBLE SWThe software loaded in the drive is not compatible with it. Contact ABB.Fault · Internal drive fault
F0101SERF CORRUPTAn internal drive error. Replace the drive.Fault · Internal drive fault
F0103SERF MACROAn internal drive error. Replace the drive.Fault · Internal drive fault
F0201DSP T1 OVERLOADAn internal drive error. If a fieldbus is in use, check the communication, its settings and its contacts.Fault · Internal drive fault
F0202DSP T2 OVERLOADAn internal drive error. If a fieldbus is in use, check the communication, its settings and its contacts.Fault · Internal drive fault
F0203DSP T3 OVERLOADAn internal drive error. If a fieldbus is in use, check the communication, its settings and its contacts.Fault · Internal drive fault
F0204DSP STACK ERRORAn internal drive error. If a fieldbus is in use, check the communication, its settings and its contacts.Fault · Internal drive fault
F0206CB ID ERRORAn internal drive error. Replace the drive.Fault · Internal drive fault
F1000PAR HZRPMFault · Setup
F1003PAR AI SCALEFault · Setup
F1004PAR AO SCALEThe analog output scaling is set wrongly. Check parameter group 15 ANALOG OUTPUTS: 1504 MINIMUM AO1 must be below 1505 MAXIMUM AO1.Fault · Setup
F1005PAR PCU 2Fault · Setup
F1006PAR EXT ROThe relay output extension parameters are set wrongly. Check the MREL-01 output relay module is connected (parameter 0181 EXTENSION).Fault · Setup
F1007PAR FBUSMISSFieldbus control has not been activated. Check the fieldbus parameter settings.Fault · Setup
F1009PAR PCU 1Fault · Setup
F1015PAR USER U/FThe voltage-to-frequency (U/f) ratio settings are wrong. Check parameters 2610 USER DEFINED U1 to 2617 USER DEFINED F4.Fault · Setup
F1017PAR SETUP 1Only two of these can be used at once: the MTAC-01 pulse encoder interface module, the frequency input and the frequency output. Turn one of them off: set the transistor output to digital mode (1804 TO MODE = 0), or select another source wherever the frequency input is used (groups 11, 40, 41 and 42), or disable the encoder (5002 ENCODER ENABLE) and remove the MTAC-01 module.Fault · Setup
A2004DIR LOCKA change of direction is not allowed. Check parameter 1003 DIRECTION.Alarm · Setup
A2013AUTORESETThe drive is about to reset a fault automatically. Check the settings in parameter group 31 AUTOMATIC RESET.Alarm · Automatic restart limit
A2019ID RUNThe motor identification run is in progress. This alarm is part of the normal start-up procedure. Wait until the drive shows the identification has finished.Alarm · Motor identification
A2025FIRST STARTThe motor identification magnetisation is in progress. This alarm is part of the normal start-up procedure. Wait until the drive shows the identification has finished.Alarm · Motor identification
A2029MOTOR BACK EMFAlarm · Setup
A5010Corrupted panel parameter backup file Retry the parameter upload or download.Alarm · Parameter memory
A5011Drive is controlled from another source Change the drive to local control.Alarm · Setup
A5012Direction of rotation is locked Allow a change of direction: see parameter 1003 DIRECTION.Alarm · Setup
A5013Panel control is disabled because start inhibit is active Starting from the panel is not possible. Reset the emergency stop command or remove the 3-wire stop command first (parameters 1001, 1002 and 2109).Alarm · Setup
A5014Panel control is disabled because of a drive fault Reset the drive fault and retry.Alarm · Setup
A5015Panel control is disabled because local control lock is active Turn off the local control lock (parameter 1606 LOCAL LOCK) and retry.Alarm · Setup
A5018Parameter default value is not found Contact ABB.Alarm · Parameter memory
A5019Writing a non-zero parameter value is prohibited Only a parameter reset is allowed.Alarm · Setup
A5020Parameter or group does not exist, or the value is inconsistent Contact ABB.Alarm · Setup
A5021Parameter or parameter group is hidden Contact ABB.Alarm · Setup
A5022Parameter is write protected The value is read-only and cannot be changed.Alarm · Setup
A5023Parameter change is not allowed while the drive is running Stop the drive, then change the value.Alarm · Setup
A5024Drive is executing a task Wait until the task is finished.Alarm · Setup
A5025Software is being uploaded or downloaded Wait until the upload or download is finished.Alarm · Parameter memory
A5026Value is at or below the minimum limit Contact ABB.Alarm · Setup
A5027Value is at or above the maximum limit Contact ABB.Alarm · Setup
A5028Invalid value Contact ABB.Alarm · Setup
A5029Memory is not ready Retry.Alarm · Parameter memory
A5030Invalid request Contact ABB.Alarm · Setup
A5032Parameter error Contact ABB.Alarm · Setup
A5040Parameter download error: the selected set is not in the backup file Upload before downloading.Alarm · Parameter memory
A5041Parameter backup file does not fit into memory Contact ABB.Alarm · Parameter memory
A5042Parameter download error: the selected set is not in the backup file Upload before downloading.Alarm · Parameter memory
A5043No start inhibitAlarm · Setup
A5044Parameter backup file restoring error Check the file is compatible with the drive.Alarm · Parameter memory
A5050Parameter upload aborted Retry the upload.Alarm · Parameter memory
A5051File error Contact ABB.Alarm · Parameter memory
A5052Parameter upload has failed Retry the upload.Alarm · Parameter memory
A5060Parameter download aborted Retry the download.Alarm · Parameter memory
A5062Parameter download has failed Retry the download.Alarm · Parameter memory
A5070Panel backup memory write error Contact ABB.Alarm · Parameter memory
A5071Panel backup memory read error Contact ABB.Alarm · Parameter memory
A5080Operation not allowed: the drive is not in local control Switch to local control.Alarm · Setup
A5081Operation not allowed because of an active fault Find the cause of the fault and reset it.Alarm · Setup
A5083Operation not allowed because the parameter lock is on Check parameter 1602 PARAMETER LOCK.Alarm · Setup
A5084Operation not allowed while the drive is performing a task Wait until the task is finished and retry.Alarm · Setup
A5085Parameter download between drives failed Check both drives are the same type, ACS355 (see the type designation labels).Alarm · Parameter memory
A5086Parameter download between drives failed Check both drives have the same type designation (see the labels).Alarm · Parameter memory
A5087Parameter download between drives failed: parameter sets incompatible Check the drive information matches on both drives (parameter group 33 INFORMATION).Alarm · Parameter memory
A5088Operation failed because of a drive memory error Contact ABB.Alarm · Parameter memory
A5089Download failed because of a CRC error Contact ABB.Alarm · Parameter memory
A5090Download failed because of a data processing error Contact ABB.Alarm · Parameter memory
A5091Operation failed because of a parameter error Contact ABB.Alarm · Parameter memory
A5092Parameter download between drives failed: parameter sets incompatible Check the drive information matches on both drives (parameter group 33 INFORMATION).Alarm · Parameter memory

Related

Related pages

Source

ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.