The WJ200 is Hitachi's compact AC inverter, built for single-phase 200 V, three-phase 200 V and three-phase 400 V supplies. When it trips, the display shows an error code in the form E xx, such as E01 for over-current or E07 for over-voltage.
Below is every error code in the table in Hitachi's WJ200 instruction manual, with the cause Hitachi gives for each. The manual lists causes only; the general checks for each kind of fault are on this site's category guides.
01 / Reading codes
Reading and clearing WJ200 codes
The display shows the error automatically when a fault trips the inverter, in the form E xx. The inverter records each trip in its trip history; setting B084 to 00 clears the trip history and keeps the other settings.
A trip switches the inverter's output off, the way a circuit breaker trips on over-current, and the error code stays on the display until it is reset.
- Remove the cause, then press the STOP/RESET key or switch on an input terminal set as RS (reset).
- Reset is not accepted for 10 seconds after a trip.
- For E08, E14 and E30, reset by RS or STOP/RESET is not accepted: switch the power off and on. If the same error comes back, initialise the inverter.
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| E01 | Over-current event while at constant speedThe inverter output was short-circuited, or the motor shaft is locked or heavily loaded: the excessive current makes the inverter switch its output off. | Fault · Overcurrent |
| E02 | Over-current event during decelerationThe inverter output was short-circuited, or the motor shaft is locked or heavily loaded: the excessive current makes the inverter switch its output off. | Fault · Overcurrent |
| E03 | Over-current event during accelerationThe inverter output was short-circuited, or the motor shaft is locked or heavily loaded: the excessive current makes the inverter switch its output off. | Fault · Overcurrent |
| E04 | Over-current event during other conditionsThe inverter output was short-circuited, or the motor shaft is locked or heavily loaded: the excessive current makes the inverter switch its output off. | Fault · Overcurrent |
| E14 | Ground faultA ground fault between the inverter output and the motor was detected during the power-up test. The feature protects the inverter, not people. | Fault · Earth fault |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| E06 | Braking resistor overload protectionThe braking resistor (BRD) operation rate went above the setting in b090, so the inverter switched its output off. | Fault · Braking resistor |
| E07 | Over-voltage protectionThe DC bus voltage went above its threshold, from energy regenerated by the motor. | Fault · DC bus overvoltage |
| E09 | Under-voltage errorThe internal DC bus voltage fell below its threshold, causing a control circuit fault. Low voltage can also overheat the motor or reduce its torque. | Fault · DC bus undervoltage |
| E15 | Input over-voltageThe input voltage was too high when tested after the inverter had been in Stop mode for 100 seconds. Once the condition clears, the inverter can run again. | Fault · DC bus overvoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| E05 | Overload protectionThe electronic thermal function detected a motor overload, so the inverter tripped and switched its output off. | Fault · Motor overload or overtemperature |
| E21 | Inverter thermal tripThe inverter's internal temperature went above its threshold: the thermal sensor in the inverter module detected the power devices running too hot. | Fault · Drive overtemperature |
| E35 | ThermistorA thermistor connected to terminals [5] and [L] sensed too high a temperature. | Fault · Motor overload or overtemperature |
| E38 | Low-speed overload protectionAn overload while the motor was running at very low speed. | Fault · Drive overload |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| E81 | Excessive speedThe motor speed reached the maximum frequency (A004) times the over-speed detection level (P026), or more. | Fault · Load monitoring |
| E83 | Positioning range errorThe current position went beyond the position range (P072 to P073). | Fault · Overtravel |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| E12 | External tripAn input terminal set as EXT (external trip) received a signal. | Fault · External fault |
| E36 | Braking errorWith brake control enabled (b120 = 01), the brake confirmation signal did not arrive within the wait time (b124) after the brake release signal was output. | Fault · External fault |
| E37 | Safe StopThe safe stop signal was given. | Fault · Safety input |
| E40 | Operator connectionThe connection between the inverter and the operator keypad failed. | Fault · Communication loss |
| E41 | Modbus communication errorWith "trip" selected for a communication error (C076 = 00), a communication timeout occurred. | Fault · Communication loss |
| E50 | EzSQ user trip 0A user-defined trip (0) in the EzSQ program. | Fault · External fault |
| E51 | EzSQ user trip 1A user-defined trip (1) in the EzSQ program. | Fault · External fault |
| E52 | EzSQ user trip 2A user-defined trip (2) in the EzSQ program. | Fault · External fault |
| E53 | EzSQ user trip 3A user-defined trip (3) in the EzSQ program. | Fault · External fault |
| E54 | EzSQ user trip 4A user-defined trip (4) in the EzSQ program. | Fault · External fault |
| E55 | EzSQ user trip 5A user-defined trip (5) in the EzSQ program. | Fault · External fault |
| E56 | EzSQ user trip 6A user-defined trip (6) in the EzSQ program. | Fault · External fault |
| E57 | EzSQ user trip 7A user-defined trip (7) in the EzSQ program. | Fault · External fault |
| E58 | EzSQ user trip 8A user-defined trip (8) in the EzSQ program. | Fault · External fault |
| E59 | EzSQ user trip 9A user-defined trip (9) in the EzSQ program. | Fault · External fault |
| E60 | Option error (DeviceNet communications error)A Bus-Off disconnection or a timeout occurred while running on DeviceNet commands. How the inverter trips is set in P045 and P048. | Fault · Communication loss |
| E61 | Option error (duplicated MAC ID)Two or more devices with the same MAC ID were found on the same network. | Fault · Communication loss |
| E62 | Option error (external trip)The Force Fault/Trip bit (attribute 17, instance 1 of the Control Supervisory object) was set to 1. | Fault · External fault |
| E69 | Option error (inverter communication error)A timeout in communication between the inverter and the DeviceNet option board. | Fault · Communication loss |
| E80 | Encoder disconnectionThe encoder wiring is disconnected, an encoder connection error was found, the encoder failed, or the encoder does not support line driver output. | Fault · Encoder signal |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| E08 | EEPROM errorThe built-in EEPROM memory has a problem, from electrical noise or excessive temperature. | Fault · Parameter memory |
| E10 | Current detection errorAn error in the inverter's internal current detection system. | Fault · Internal drive fault |
| E11 | CPU errorThe built-in CPU malfunctioned. | Fault · Internal drive fault |
| E13 | USPUnattended Start Protection (USP) is on, and power was applied while a Run signal was present. The inverter does not go into Run until the error is cleared. | Fault · Setup |
| E22 | CPU communication errorCommunication between the inverter's two CPUs failed. | Fault · Internal drive fault |
| E25 | Main circuit errorThe inverter could not confirm the power supply was established, because of a malfunction from electrical noise or damage to a main circuit element. | Fault · Internal drive fault |
| E30 | Driver errorAn internal error in the safety protection circuit between the CPU and the main driver unit, possibly from excessive electrical noise. The inverter switched off the IGBT module output. | Fault · Internal drive fault |
| E43 | EzSQ invalid instructionThe program stored in the inverter's memory is corrupted, or the PRG terminal was switched on with no program downloaded. | Fault · Setup |
| E44 | EzSQ nesting count errorSubroutines, if statements or for-next loops are nested more than eight levels deep. | Fault · Setup |
| E45 | EzSQ instruction errorThe inverter found a command it cannot execute. | Fault · Setup |
| E63 | Option errorThe inverter found an error in the option board in the option slot. The option board's own manual gives the details. | Fault · Internal drive fault |
| E64 | Option errorThe inverter found an error in the option board in the option slot. The option board's own manual gives the details. | Fault · Internal drive fault |
| E65 | Option errorThe inverter found an error in the option board in the option slot. The option board's own manual gives the details. | Fault · Internal drive fault |
| E66 | Option errorThe inverter found an error in the option board in the option slot. The option board's own manual gives the details. | Fault · Internal drive fault |
| E67 | Option errorThe inverter found an error in the option board in the option slot. The option board's own manual gives the details. | Fault · Internal drive fault |
| E68 | Option errorThe inverter found an error in the option board in the option slot. The option board's own manual gives the details. | Fault · Internal drive fault |
Related
Related pages
Source
Hitachi Industrial Equipment Systems, WJ200 Series Inverter Instruction Manual, May 2010, NT325X, Chapter 6, Monitoring Trip Events, History, & Conditions (Error Codes).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Hitachi and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007