The Altivar Machine ATV320 is Schneider Electric's drive for asynchronous and synchronous motors on machines such as packaging, conveying and material handling. Its error codes are short letter codes such as OCF for overcurrent, OBF for DC bus overvoltage or SCF1 for motor short circuit.

Below is every error code in the diagnostics chapter of Schneider's ATV320 programming manual (edition 04/2025), with the probable cause and remedy Schneider gives, and how each code is cleared.

01 / Reading codes

Reading and clearing Altivar ATV320 codes

The drive's display shows the error code, for example OCF or OBF. On the graphic display terminal, the Diagnostics menu (DGT-) shows detected errors and their cause in plain text, and can be used to run tests.

A detected error stops the drive until it is cleared, in the way the manual gives for that code.

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

02 / Current and earth faults

Current and earth faults

CodeNameKind
HDFIGBT desaturation errorA short circuit or ground fault at the drive. Check the cables between the drive and the motor, and the motor's insulation.Fault · Output short circuit
OCFOvercurrent errorFault · Overcurrent
OPF1Single output phase loss errorOne phase is lost at the drive output. Check the connections from the drive to the motor.Fault · Output phase loss
OPF2Output phase loss errorFault · Output phase loss
SCF1Motor short circuit errorFault · Output short circuit
SCF3Ground short circuit errorFault · Earth fault
SCF5Motor short circuit errorFault · Output short circuit

03 / Voltage and supply

Voltage and supply

CodeNameKind
OBFDC bus overvoltage errorFault · DC bus overvoltage
OSFSupply mains overvoltage errorFault · DC bus overvoltage
PHFInput phase loss errorFault · Input phase loss
USFSupply mains undervoltage errorFault · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
INFBInternal error 11 (Temperature)Fault · Temperature sensor signal
OHFDrive overheating errorThe drive's temperature is too high. Check the motor load, the drive's ventilation and the ambient temperature, and let the drive cool before restarting.Fault · Drive overtemperature
OLFMotor overload errorExcessive motor current. Check the motor thermal protection setting and the motor load, and let the motor cool before restarting.Fault · Motor overload or overtemperature
OTFLDI6=PTC overheat errorFault · Motor overload or overtemperature
PTFLDI6=PTC probe errorThe PTC probe on input DI6 is open or short-circuited. Check the PTC probe and its wiring to the motor and drive.Fault · Temperature sensor signal
TJFIGBT overheatingFault · Drive overtemperature

05 / Motor and load

Motor and load

CodeNameKind
ANFLoad slipping errorFault · Motor stall
DLFDynamic load detected errorFault · Load monitoring
OLCProcess overload errorFault · Load monitoring
SOFMotor overspeed errorFault · Load monitoring
SSFTorque limitation errorFault · Motor stall
ULFProcess underload errorFault · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
BLFBrake control errorFault · External fault
BRFBrake feedback errorFault · External fault
CNFFieldbus module communication interruption errorFault · Communication loss
COFCANopen communication interruption errorFault · Communication loss
EPF1External errorAn event triggered by an external device, as the user set it up. Check the device that triggered it, then reset.Fault · External fault
EPF2Fieldbus external detected errorAn event triggered by a communication network. Find the cause of the trigger, then reset.Fault · External fault
FCF1Output contactor closed errorFault · External fault
FCF2Output contactor opened errorFault · External fault
LCFInput contactor errorFault · External fault
LFF3AI3 4-20mA loss errorThe 4 to 20 mA reference on analog input AI3 was lost. Check the connection on the analog inputs.Fault · Analog signal loss
SAFFSafety function detected errorFault · Safety input
SLF1Modbus communication interruption errorFault · Communication loss
SLF2PC communication interruption errorFault · Communication loss
SLF3HMI communication interruption errorFault · Communication loss
SPFEncoder feedback loss errorFault · Encoder signal

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
ASFAngle errorDuring the phase-shift angle measurement, a motor phase is disconnected or the motor's inductance is too high. Check the motor phases and the maximum current the drive allows.Fault · Motor identification
CFFIncorrect configuration errorFault · Setup
CFIInvalid configuration errorFault · Setup
CFI2Configuration transfer errorFault · Setup
CRF1Precharge capacitor errorFault · Internal drive fault
CSFChannel switching detected errorA switch to channels that are not valid. Check the function parameters.Fault · Setup
EEF1EEprom control errorFault · Parameter memory
EEF2EEprom power errorFault · Parameter memory
FBEFunction block errorA function block error. See the function block error parameter (FBFT) for details.Fault · Setup
FBESFunction block stop errorThe function blocks were stopped while the motor was running. Check the function block motor stop type (FBSM) setting.Fault · Setup
HCFBoards compatibility errorFault · Setup
ILFInternal link errorFault · Internal drive fault
INF1Internal error 1 (Rating)The power board differs from the one stored. Check the power board's reference.Fault · Internal drive fault
INF2Internal error 2 (Soft)The power board is not compatible with the control block. Check the power board's reference and its compatibility.Fault · Internal drive fault
INF3Internal error 3 (Intern Comm)Fault · Internal drive fault
INF4Internal error 4 (Manufacturing)The internal data is inconsistent. The drive needs recalibrating, which Schneider Electric Product Support does.Fault · Internal drive fault
INF6Internal error 6 (Option)Fault · Internal drive fault
INF9Internal error 9 (Measure)Fault · Internal drive fault
INFAInternal error 10 (Mains)The input stage is not working correctly. Contact Schneider Electric Product Support.Fault · Internal drive fault
INFEInternal error 14 (CPU)Fault · Internal drive fault
SCF4IGBT short circuit errorA power component error. Contact Schneider Electric Product Support.Fault · Internal drive fault
TNFAutotuning detected errorFault · Motor identification

Related

Related pages

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

Altivar ATV320 fault you can't clear?

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.