The Altivar Machine ATV320 is Schneider Electric's drive for asynchronous and synchronous motors on machines such as packaging, conveying and material handling. Its error codes are short letter codes such as OCF for overcurrent, OBF for DC bus overvoltage or SCF1 for motor short circuit.
Below is every error code in the diagnostics chapter of Schneider's ATV320 programming manual (edition 04/2025), with the probable cause and remedy Schneider gives, and how each code is cleared.
01 / Reading codes
Reading and clearing Altivar ATV320 codes
The drive's display shows the error code, for example OCF or OBF. On the graphic display terminal, the Diagnostics menu (DGT-) shows detected errors and their cause in plain text, and can be used to run tests.
A detected error stops the drive until it is cleared, in the way the manual gives for that code.
- Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
- Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
- For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| HDF | IGBT desaturation errorA short circuit or ground fault at the drive. Check the cables between the drive and the motor, and the motor's insulation. | Fault · Output short circuit |
| OCF | Overcurrent error | Fault · Overcurrent |
| OPF1 | Single output phase loss errorOne phase is lost at the drive output. Check the connections from the drive to the motor. | Fault · Output phase loss |
| OPF2 | Output phase loss error | Fault · Output phase loss |
| SCF1 | Motor short circuit error | Fault · Output short circuit |
| SCF3 | Ground short circuit error | Fault · Earth fault |
| SCF5 | Motor short circuit error | Fault · Output short circuit |
03 / Voltage and supply
Voltage and supply
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| INFB | Internal error 11 (Temperature) | Fault · Temperature sensor signal |
| OHF | Drive overheating errorThe drive's temperature is too high. Check the motor load, the drive's ventilation and the ambient temperature, and let the drive cool before restarting. | Fault · Drive overtemperature |
| OLF | Motor overload errorExcessive motor current. Check the motor thermal protection setting and the motor load, and let the motor cool before restarting. | Fault · Motor overload or overtemperature |
| OTFL | DI6=PTC overheat error | Fault · Motor overload or overtemperature |
| PTFL | DI6=PTC probe errorThe PTC probe on input DI6 is open or short-circuited. Check the PTC probe and its wiring to the motor and drive. | Fault · Temperature sensor signal |
| TJF | IGBT overheating | Fault · Drive overtemperature |
05 / Motor and load
Motor and load
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| BLF | Brake control error | Fault · External fault |
| BRF | Brake feedback error | Fault · External fault |
| CNF | Fieldbus module communication interruption error | Fault · Communication loss |
| COF | CANopen communication interruption error | Fault · Communication loss |
| EPF1 | External errorAn event triggered by an external device, as the user set it up. Check the device that triggered it, then reset. | Fault · External fault |
| EPF2 | Fieldbus external detected errorAn event triggered by a communication network. Find the cause of the trigger, then reset. | Fault · External fault |
| FCF1 | Output contactor closed error | Fault · External fault |
| FCF2 | Output contactor opened error | Fault · External fault |
| LCF | Input contactor error | Fault · External fault |
| LFF3 | AI3 4-20mA loss errorThe 4 to 20 mA reference on analog input AI3 was lost. Check the connection on the analog inputs. | Fault · Analog signal loss |
| SAFF | Safety function detected error | Fault · Safety input |
| SLF1 | Modbus communication interruption error | Fault · Communication loss |
| SLF2 | PC communication interruption error | Fault · Communication loss |
| SLF3 | HMI communication interruption error | Fault · Communication loss |
| SPF | Encoder feedback loss error | Fault · Encoder signal |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| ASF | Angle errorDuring the phase-shift angle measurement, a motor phase is disconnected or the motor's inductance is too high. Check the motor phases and the maximum current the drive allows. | Fault · Motor identification |
| CFF | Incorrect configuration error | Fault · Setup |
| CFI | Invalid configuration error | Fault · Setup |
| CFI2 | Configuration transfer error | Fault · Setup |
| CRF1 | Precharge capacitor error | Fault · Internal drive fault |
| CSF | Channel switching detected errorA switch to channels that are not valid. Check the function parameters. | Fault · Setup |
| EEF1 | EEprom control error | Fault · Parameter memory |
| EEF2 | EEprom power error | Fault · Parameter memory |
| FBE | Function block errorA function block error. See the function block error parameter (FBFT) for details. | Fault · Setup |
| FBES | Function block stop errorThe function blocks were stopped while the motor was running. Check the function block motor stop type (FBSM) setting. | Fault · Setup |
| HCF | Boards compatibility error | Fault · Setup |
| ILF | Internal link error | Fault · Internal drive fault |
| INF1 | Internal error 1 (Rating)The power board differs from the one stored. Check the power board's reference. | Fault · Internal drive fault |
| INF2 | Internal error 2 (Soft)The power board is not compatible with the control block. Check the power board's reference and its compatibility. | Fault · Internal drive fault |
| INF3 | Internal error 3 (Intern Comm) | Fault · Internal drive fault |
| INF4 | Internal error 4 (Manufacturing)The internal data is inconsistent. The drive needs recalibrating, which Schneider Electric Product Support does. | Fault · Internal drive fault |
| INF6 | Internal error 6 (Option) | Fault · Internal drive fault |
| INF9 | Internal error 9 (Measure) | Fault · Internal drive fault |
| INFA | Internal error 10 (Mains)The input stage is not working correctly. Contact Schneider Electric Product Support. | Fault · Internal drive fault |
| INFE | Internal error 14 (CPU) | Fault · Internal drive fault |
| SCF4 | IGBT short circuit errorA power component error. Contact Schneider Electric Product Support. | Fault · Internal drive fault |
| TNF | Autotuning detected error | Fault · Motor identification |
Related
Related pages
Source
Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.