The SINAMICS G120 is Siemens' modular inverter: a Power Module with a separate Control Unit. These codes are for the G120 with the CU240B-2 and CU240E-2 Control Units, the common general-purpose versions.
Faults show as Fxxxxx and alarms as Axxxxx, for example F30001 for overcurrent or F07801 for motor overcurrent. Below are the alarms and faults Siemens lists as the most important in the G120 operating instructions, with the remedy given for each. Siemens' separate List Manual has the complete list.
01 / Reading codes
Reading and clearing SINAMICS G120 codes
The operator panel shows a fault as Fxxxxx and an alarm as Axxxxx; a fault also lights the RDY LED. The fault buffer shows the fault code (r0945) and a fault value with more detail (r0949). The fault history holds up to 56 faults and the alarm history up to 56 alarms; setting p0952 to 0 clears the fault buffer and history.
A fault generally switches the motor off, and it must be acknowledged before the inverter runs again. An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.
- Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
- Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
- Alarms need no acknowledgement: they disappear once the cause is removed.
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| A07409 | V/f control, current limiting controller active | Alarm · Overcurrent |
| F07801 | Motor overcurrent | Fault · Overcurrent |
| F07807 | Short-circuit detected | Fault · Output short circuit |
| F30001 | Overcurrent | Fault · Overcurrent |
| F30015 | Motor cable phase failure | Fault · Output phase loss |
| F30021 | Ground fault | Fault · Earth fault |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| A07400 | DC-link voltage maximum controller active | Alarm · DC bus overvoltage |
| F07806 | Regenerative power limit exceeded | Fault · Braking resistor |
| F30002 | DC-link voltage overvoltage | Fault · DC bus overvoltage |
| F30003 | DC-link voltage undervoltage Check the line voltage (p0210). | Fault · DC bus undervoltage |
| F30011 | Line phase failure | Fault · Input phase loss |
| F30027 | Time monitoring for DC link pre-charging | Fault · DC bus undervoltage |
| A30502 | DC-link overvoltage | Alarm · DC bus overvoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| A03520 | Temperature sensor fault Check the sensor is connected correctly. | Alarm · Temperature sensor signal |
| A05000 | Power Module overtemperature | Alarm · Drive overtemperature |
| A05001 | Power Module overtemperature Check the ambient temperature is within its limits. | Alarm · Drive overtemperature |
| A05002 | Power Module overtemperature Check the ambient temperature is within its limits. | Alarm · Drive overtemperature |
| A05004 | Power Module overtemperature Check the ambient temperature is within its limits. | Alarm · Drive overtemperature |
| A05006 | Power Module overtemperature Check the ambient temperature is within its limits. | Alarm · Drive overtemperature |
| F07011 | Motor overtemperature | Fault · Motor overload or overtemperature |
| A07012 | I2t motor model overtemperature | Alarm · Motor overload or overtemperature |
| A07015 | Motor temperature sensor alarm | Alarm · Temperature sensor signal |
| F07016 | Motor temperature sensor fault | Fault · Temperature sensor signal |
| A07805 | Drive: Power unit overload I2t | Alarm · Drive overload |
| A07910 | Motor overtemperature | Alarm · Motor overload or overtemperature |
| F30004 | Inverter overtemperature | Fault · Drive overtemperature |
| F30005 | I2t inverter overload | Fault · Drive overload |
| F30035 | Overtemperature, intake air | Fault · Drive overtemperature |
| F30036 | Overtemperature, inside area | Fault · Drive overtemperature |
| F30037 | Rectifier overtemperature | Fault · Drive overtemperature |
| A30049 | Internal fan defective Check the internal fan and replace it if needed. | Alarm · Cooling fan |
| F30059 | Internal fan defective Check the internal fan and replace it if needed. | Fault · Cooling fan |
| A30920 | Temperature sensor fault Check the sensor is connected correctly. | Alarm · Temperature sensor signal |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| F07426 | Technology controller actual value limited | Fault · Process limit |
| A07444 | PID autotuning is activated None needed: the alarm disappears once autotuning of the PID controller (p2350 > 0) is complete. | Alarm · Process limit |
| F07445 | PID autotuning canceledThe inverter canceled the PID controller's autotuning because of a fault. Increase p2355 and restart the autotuning. | Fault · Process limit |
| A07891 | Load monitoring, pump/fan blocked | Alarm · Load monitoring |
| A07892 | Load monitoring, pump/fan without load | Alarm · Load monitoring |
| A07893 | Load monitoring, pump leakage | Alarm · Load monitoring |
| F07894 | Load monitoring, pump/fan blocked | Fault · Load monitoring |
| F07895 | Load monitoring, pump/fan without load | Fault · Load monitoring |
| F07896 | Load monitoring, pump leakage | Fault · Load monitoring |
| F07900 | Motor blocked | Fault · Motor stall |
| F07901 | Motor overspeed | Fault · Load monitoring |
| F07902 | Motor stalled | Fault · Motor stall |
| A07903 | Motor speed deviation | Alarm · Motor stall |
| A07920 | Torque/speed too low | Alarm · Load monitoring |
| A07921 | Torque/speed too high | Alarm · Load monitoring |
| A07922 | Torque/speed out of tolerance | Alarm · Load monitoring |
| F07923 | Torque/speed too low | Fault · Load monitoring |
| F07924 | Torque/speed too high | Fault · Load monitoring |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| F01600 | STOP A initiated Select the STO safety function and then deselect it again. | Fault · Safety input |
| F01625 | Sign-of-life error in the Safety data | Fault · Safety input |
| F01650 | Acceptance test required | Fault · Safety input |
| F01659 | Write task for parameter rejected | Fault · Safety input |
| A01666 | Static 1 signal at the F-DI for safe acknowledgement Set the fail-safe digital input F-DI to a logical 0 signal. | Alarm · Safety input |
| A01698 | Commissioning mode active for safety functions None needed: the inverter withdraws the alarm once safety commissioning is complete. | Alarm · Safety input |
| A01699 | Switch-off signal path test required None needed: the inverter withdraws the message the next time the STO safety function is deselected. | Alarm · Safety input |
| A01900 | PROFIBUS: Configuration telegram faultyA PROFIBUS master is trying to connect with a faulty configuration telegram. Check the bus configuration on the master and slave side. | Alarm · Communication loss |
| A01910 | Setpoint timeout | Alarm · Communication loss |
| F01910 | Setpoint timeout | Fault · Communication loss |
| A01920 | PROFIBUS: Cyclic connection interruptThe cyclic connection to the PROFIBUS master is interrupted. Establish the PROFIBUS connection and switch the PROFIBUS master to cyclic operation. | Alarm · Communication loss |
| F03505 | Analog input, wire break | Fault · Analog signal loss |
| A07850 | External alarm 1 Remove the cause of the alarm. | Alarm · External fault |
| A07851 | External alarm 2 Remove the cause of the alarm. | Alarm · External fault |
| A07852 | External alarm 3 Remove the cause of the alarm. | Alarm · External fault |
| F07860 | External fault 1 Remove the external cause of the fault. | Fault · External fault |
| F07861 | External fault 2 Remove the external cause of the fault. | Fault · External fault |
| F07862 | External fault 3 Remove the external cause of the fault. | Fault · External fault |
| F08501 | Setpoint timeout | Fault · Communication loss |
| F08502 | Monitoring time, sign-of-life expired Check the PROFINET connection. | Fault · Communication loss |
| F08510 | Send configuration data not valid Check the PROFINET configuration. | Fault · Communication loss |
| A08511 | Receive configuration data not valid Check the PROFINET configuration. | Alarm · Communication loss |
| A08526 | No cyclic connection | Alarm · Communication loss |
| A08565 | Consistency error affecting adjustable parameters | Alarm · Communication loss |
| F08700 | Communications error | Fault · Communication loss |
| F30600 | STOP A triggered Select the STO safety function and then deselect it again. | Fault · Safety input |
| A50001 | PROFINET configuration errorA PROFINET controller is trying to connect with an incorrect configuration telegram. Check whether Shared Device is activated (p8929 = 2). | Alarm · Communication loss |
| A50010 | PROFINET name of station invalid Correct the station name (p8920) and activate it (p8925 = 2). | Alarm · Communication loss |
| A50020 | PROFINET: Second control missingShared Device is activated (p8929 = 2), but only one PROFINET controller is connected. | Alarm · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| F01000 | Software error in the CU Replace the Control Unit. | Fault · Internal drive fault |
| F01001 | Floating point exception Switch the Control Unit off and on again. | Fault · Internal drive fault |
| F01015 | Software error in the CU Upgrade the firmware or contact technical support. | Fault · Internal drive fault |
| F01018 | Power-up aborted more than once | Fault · Internal drive fault |
| A01028 | Configuration errorThe parameter settings on the memory card were created on a different type of module (article number, MLFB). Check the module parameters and commission again if needed. | Alarm · Setup |
| F01033 | Switching over units: Reference parameter value invalid Set the reference parameter to a value other than 0.0 (p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004). | Fault · Setup |
| F01034 | Switching over units: Calculation of the parameter values after reference value change unsuccessful Choose the reference parameter values so the parameters involved can be calculated in per-unit notation (p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004). | Fault · Setup |
| F01040 | Parameters must be saved | Fault · Parameter memory |
| F01044 | Error loading data from memory card Replace the memory card or the Control Unit. | Fault · Parameter memory |
| A01053 | System overload measured | Alarm · Internal drive fault |
| F01054 | System limit exceeded | Fault · Internal drive fault |
| A01101 | Memory card not available Insert a memory card, or deactivate alarm A01101. | Alarm · Parameter memory |
| F01105 | CU: Insufficient memory Reduce the number of data sets. | Fault · Parameter memory |
| F01122 | Frequency at the probe input too high Reduce the frequency of the pulses at the probe input. | Fault · Setup |
| F01205 | CU: Time slice overflow Contact technical support. | Fault · Internal drive fault |
| F01250 | CU hardware fault Replace the Control Unit. | Fault · Internal drive fault |
| F01512 | An attempt has been made to establish a conversion factor for scaling which does not exist Create the scaling, or check the transferred value. | Fault · Setup |
| A01590 | Motor maintenance interval elapsed Carry out the maintenance and reset the maintenance interval (p0651). | Alarm · Setup |
| F01662 | Error, internal communications | Fault · Internal drive fault |
| F06310 | Supply voltage (p0210) incorrectly set | Fault · Setup |
| F07086 | Switching over units: Parameter limit violation Check the adapted parameter values and correct them if needed. | Fault · Setup |
| F07088 | Switching over units: Parameter limit violation Check the adapted parameter values and correct them if needed. | Fault · Setup |
| F07320 | Automatic restart aborted | Fault · Automatic restart limit |
| A07321 | Automatic restart active None needed: the drive switches back on by itself once the voltage recovers or the causes of pending faults are removed. | Alarm · Automatic restart limit |
| F07330 | Search current measured too low | Fault · Setup |
| A07927 | DC braking active None needed. | Alarm · Setup |
| A07980 | Rotary measurement activated None needed. | Alarm · Motor identification |
| A07981 | No enabling for rotary measurement | Alarm · Motor identification |
| A07991 | Motor identification activated Switch on the motor to identify the motor data. | Alarm · Motor identification |
| F13100 | Know-how protection: Copy protection error | Fault · Parameter memory |
| F13101 | Know-how protection: Copy protection cannot be activated Insert a valid memory card. | Fault · Parameter memory |
| F30022 | Power Module: Monitoring UCE Check or replace the Power Module. | Fault · Internal drive fault |
| F30052 | Incorrect Power Module data Replace the Power Module, or upgrade the Control Unit firmware. | Fault · Internal drive fault |
| F30053 | Error in FPGA data Replace the Power Module. | Fault · Internal drive fault |
| F30074 | Communications error between Control Unit and Power Module | Fault · Internal drive fault |
| F30662 | CU hardware fault Switch the Control Unit off and on again, upgrade the firmware, or contact technical support. | Fault · Internal drive fault |
| F30664 | CU power up aborted Switch the Control Unit off and on again, upgrade the firmware, or contact technical support. | Fault · Internal drive fault |
| F30850 | Software fault in the Power Module Replace the Power Module, or contact technical support. | Fault · Internal drive fault |
Related
Related pages
Source
Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.