Siemens SINAMICS G120 fault codes

The SINAMICS G120 is Siemens' modular inverter: a Power Module with a separate Control Unit. These codes are for the G120 with the CU240B-2 and CU240E-2 Control Units, the common general-purpose versions.

Faults show as Fxxxxx and alarms as Axxxxx, for example F30001 for overcurrent or F07801 for motor overcurrent. Below are the alarms and faults Siemens lists as the most important in the G120 operating instructions, with the remedy given for each. Siemens' separate List Manual has the complete list.

01 / Reading codes

Reading and clearing SINAMICS G120 codes

The operator panel shows a fault as Fxxxxx and an alarm as Axxxxx; a fault also lights the RDY LED. The fault buffer shows the fault code (r0945) and a fault value with more detail (r0949). The fault history holds up to 56 faults and the alarm history up to 56 alarms; setting p0952 to 0 clears the fault buffer and history.

A fault generally switches the motor off, and it must be acknowledged before the inverter runs again. An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.

  • Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
  • Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
  • Alarms need no acknowledgement: they disappear once the cause is removed.

02 / Current and earth faults

Current and earth faults

CodeNameKind
A07409V/f control, current limiting controller activeAlarm · Overcurrent
F07801Motor overcurrentFault · Overcurrent
F07807Short-circuit detectedFault · Output short circuit
F30001OvercurrentFault · Overcurrent
F30015Motor cable phase failureFault · Output phase loss
F30021Ground faultFault · Earth fault

03 / Voltage and supply

Voltage and supply

CodeNameKind
A07400DC-link voltage maximum controller activeAlarm · DC bus overvoltage
F07806Regenerative power limit exceededFault · Braking resistor
F30002DC-link voltage overvoltageFault · DC bus overvoltage
F30003DC-link voltage undervoltage Check the line voltage (p0210).Fault · DC bus undervoltage
F30011Line phase failureFault · Input phase loss
F30027Time monitoring for DC link pre-chargingFault · DC bus undervoltage
A30502DC-link overvoltageAlarm · DC bus overvoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
A03520Temperature sensor fault Check the sensor is connected correctly.Alarm · Temperature sensor signal
A05000Power Module overtemperatureAlarm · Drive overtemperature
A05001Power Module overtemperature Check the ambient temperature is within its limits.Alarm · Drive overtemperature
A05002Power Module overtemperature Check the ambient temperature is within its limits.Alarm · Drive overtemperature
A05004Power Module overtemperature Check the ambient temperature is within its limits.Alarm · Drive overtemperature
A05006Power Module overtemperature Check the ambient temperature is within its limits.Alarm · Drive overtemperature
F07011Motor overtemperatureFault · Motor overload or overtemperature
A07012I2t motor model overtemperatureAlarm · Motor overload or overtemperature
A07015Motor temperature sensor alarmAlarm · Temperature sensor signal
F07016Motor temperature sensor faultFault · Temperature sensor signal
A07805Drive: Power unit overload I2tAlarm · Drive overload
A07910Motor overtemperatureAlarm · Motor overload or overtemperature
F30004Inverter overtemperatureFault · Drive overtemperature
F30005I2t inverter overloadFault · Drive overload
F30035Overtemperature, intake airFault · Drive overtemperature
F30036Overtemperature, inside areaFault · Drive overtemperature
F30037Rectifier overtemperatureFault · Drive overtemperature
A30049Internal fan defective Check the internal fan and replace it if needed.Alarm · Cooling fan
F30059Internal fan defective Check the internal fan and replace it if needed.Fault · Cooling fan
A30920Temperature sensor fault Check the sensor is connected correctly.Alarm · Temperature sensor signal

05 / Motor and load

Motor and load

CodeNameKind
F07426Technology controller actual value limitedFault · Process limit
A07444PID autotuning is activated None needed: the alarm disappears once autotuning of the PID controller (p2350 > 0) is complete.Alarm · Process limit
F07445PID autotuning canceledThe inverter canceled the PID controller's autotuning because of a fault. Increase p2355 and restart the autotuning.Fault · Process limit
A07891Load monitoring, pump/fan blockedAlarm · Load monitoring
A07892Load monitoring, pump/fan without loadAlarm · Load monitoring
A07893Load monitoring, pump leakageAlarm · Load monitoring
F07894Load monitoring, pump/fan blockedFault · Load monitoring
F07895Load monitoring, pump/fan without loadFault · Load monitoring
F07896Load monitoring, pump leakageFault · Load monitoring
F07900Motor blockedFault · Motor stall
F07901Motor overspeedFault · Load monitoring
F07902Motor stalledFault · Motor stall
A07903Motor speed deviationAlarm · Motor stall
A07920Torque/speed too lowAlarm · Load monitoring
A07921Torque/speed too highAlarm · Load monitoring
A07922Torque/speed out of toleranceAlarm · Load monitoring
F07923Torque/speed too lowFault · Load monitoring
F07924Torque/speed too highFault · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
F01600STOP A initiated Select the STO safety function and then deselect it again.Fault · Safety input
F01625Sign-of-life error in the Safety dataFault · Safety input
F01650Acceptance test requiredFault · Safety input
F01659Write task for parameter rejectedFault · Safety input
A01666Static 1 signal at the F-DI for safe acknowledgement Set the fail-safe digital input F-DI to a logical 0 signal.Alarm · Safety input
A01698Commissioning mode active for safety functions None needed: the inverter withdraws the alarm once safety commissioning is complete.Alarm · Safety input
A01699Switch-off signal path test required None needed: the inverter withdraws the message the next time the STO safety function is deselected.Alarm · Safety input
A01900PROFIBUS: Configuration telegram faultyA PROFIBUS master is trying to connect with a faulty configuration telegram. Check the bus configuration on the master and slave side.Alarm · Communication loss
A01910Setpoint timeoutAlarm · Communication loss
F01910Setpoint timeoutFault · Communication loss
A01920PROFIBUS: Cyclic connection interruptThe cyclic connection to the PROFIBUS master is interrupted. Establish the PROFIBUS connection and switch the PROFIBUS master to cyclic operation.Alarm · Communication loss
F03505Analog input, wire breakFault · Analog signal loss
A07850External alarm 1 Remove the cause of the alarm.Alarm · External fault
A07851External alarm 2 Remove the cause of the alarm.Alarm · External fault
A07852External alarm 3 Remove the cause of the alarm.Alarm · External fault
F07860External fault 1 Remove the external cause of the fault.Fault · External fault
F07861External fault 2 Remove the external cause of the fault.Fault · External fault
F07862External fault 3 Remove the external cause of the fault.Fault · External fault
F08501Setpoint timeoutFault · Communication loss
F08502Monitoring time, sign-of-life expired Check the PROFINET connection.Fault · Communication loss
F08510Send configuration data not valid Check the PROFINET configuration.Fault · Communication loss
A08511Receive configuration data not valid Check the PROFINET configuration.Alarm · Communication loss
A08526No cyclic connectionAlarm · Communication loss
A08565Consistency error affecting adjustable parametersAlarm · Communication loss
F08700Communications errorFault · Communication loss
F30600STOP A triggered Select the STO safety function and then deselect it again.Fault · Safety input
A50001PROFINET configuration errorA PROFINET controller is trying to connect with an incorrect configuration telegram. Check whether Shared Device is activated (p8929 = 2).Alarm · Communication loss
A50010PROFINET name of station invalid Correct the station name (p8920) and activate it (p8925 = 2).Alarm · Communication loss
A50020PROFINET: Second control missingShared Device is activated (p8929 = 2), but only one PROFINET controller is connected. Alarm · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
F01000Software error in the CU Replace the Control Unit.Fault · Internal drive fault
F01001Floating point exception Switch the Control Unit off and on again.Fault · Internal drive fault
F01015Software error in the CU Upgrade the firmware or contact technical support.Fault · Internal drive fault
F01018Power-up aborted more than onceFault · Internal drive fault
A01028Configuration errorThe parameter settings on the memory card were created on a different type of module (article number, MLFB). Check the module parameters and commission again if needed.Alarm · Setup
F01033Switching over units: Reference parameter value invalid Set the reference parameter to a value other than 0.0 (p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).Fault · Setup
F01034Switching over units: Calculation of the parameter values after reference value change unsuccessful Choose the reference parameter values so the parameters involved can be calculated in per-unit notation (p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).Fault · Setup
F01040Parameters must be savedFault · Parameter memory
F01044Error loading data from memory card Replace the memory card or the Control Unit.Fault · Parameter memory
A01053System overload measuredAlarm · Internal drive fault
F01054System limit exceededFault · Internal drive fault
A01101Memory card not available Insert a memory card, or deactivate alarm A01101.Alarm · Parameter memory
F01105CU: Insufficient memory Reduce the number of data sets.Fault · Parameter memory
F01122Frequency at the probe input too high Reduce the frequency of the pulses at the probe input.Fault · Setup
F01205CU: Time slice overflow Contact technical support.Fault · Internal drive fault
F01250CU hardware fault Replace the Control Unit.Fault · Internal drive fault
F01512An attempt has been made to establish a conversion factor for scaling which does not exist Create the scaling, or check the transferred value.Fault · Setup
A01590Motor maintenance interval elapsed Carry out the maintenance and reset the maintenance interval (p0651).Alarm · Setup
F01662Error, internal communicationsFault · Internal drive fault
F06310Supply voltage (p0210) incorrectly setFault · Setup
F07086Switching over units: Parameter limit violation Check the adapted parameter values and correct them if needed.Fault · Setup
F07088Switching over units: Parameter limit violation Check the adapted parameter values and correct them if needed.Fault · Setup
F07320Automatic restart abortedFault · Automatic restart limit
A07321Automatic restart active None needed: the drive switches back on by itself once the voltage recovers or the causes of pending faults are removed.Alarm · Automatic restart limit
F07330Search current measured too lowFault · Setup
A07927DC braking active None needed.Alarm · Setup
A07980Rotary measurement activated None needed.Alarm · Motor identification
A07981No enabling for rotary measurementAlarm · Motor identification
A07991Motor identification activated Switch on the motor to identify the motor data.Alarm · Motor identification
F13100Know-how protection: Copy protection errorFault · Parameter memory
F13101Know-how protection: Copy protection cannot be activated Insert a valid memory card.Fault · Parameter memory
F30022Power Module: Monitoring UCE Check or replace the Power Module.Fault · Internal drive fault
F30052Incorrect Power Module data Replace the Power Module, or upgrade the Control Unit firmware.Fault · Internal drive fault
F30053Error in FPGA data Replace the Power Module.Fault · Internal drive fault
F30074Communications error between Control Unit and Power ModuleFault · Internal drive fault
F30662CU hardware fault Switch the Control Unit off and on again, upgrade the firmware, or contact technical support.Fault · Internal drive fault
F30664CU power up aborted Switch the Control Unit off and on again, upgrade the firmware, or contact technical support.Fault · Internal drive fault
F30850Software fault in the Power Module Replace the Power Module, or contact technical support.Fault · Internal drive fault

Related

Related pages

Source

Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007