The Goodrive20 (GD20) is INVT's general-purpose AC drive, common on pumps, fans, conveyors and machines. Its keypad shows faults as short codes such as OC1 for overcurrent during acceleration, OV2 for overvoltage during deceleration or OUt1 for U-phase protection.

Below is every fault in the fault table of INVT's GD20 manual (version V2.1), with the possible causes and the solutions INVT gives for each.

01 / Reading codes

Reading and clearing Goodrive20 (GD20) codes

When the TRIP indicator is on, the keypad shows the fault code. Function codes P07.27 to P07.32 record the last six faults, and P07.33 to P07.56 record the drive's running data at the last three faults.

A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset. PoFF is a state the keypad shows while the system power is off or the DC voltage is low, not a fault.

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

02 / Current and earth faults

Current and earth faults

CodeNameKind
OUt1Inverter unit U phase protectionFault · Output short circuit
OUt2Inverter unit V phase protectionFault · Output short circuit
OUt3Inverter unit W phase protectionFault · Output short circuit
OC1Overcurrent during accelerationFault · Overcurrent
OC2Overcurrent during decelerationFault · Overcurrent
OC3Overcurrent during constant speed runningFault · Overcurrent
SPOPhase loss on output sideFault · Output phase loss
ETH1To-ground short-circuit fault 1Fault · Earth fault
ETH2To-ground short-circuit fault 2Fault · Earth fault

03 / Voltage and supply

Voltage and supply

CodeNameKind
OV1Overvoltage during accelerationFault · DC bus overvoltage
OV2Overvoltage during decelerationFault · DC bus overvoltage
OV3Overvoltage during constant speed runningFault · DC bus overvoltage
UVBus undervoltageThe supply voltage is too low. Check the supply line's input power.Fault · DC bus undervoltage
SPIPhase loss on input sideFault · Input phase loss
bCEBraking unit faultFault · Braking resistor
PoFFSystem power offThe system power is off, or the DC voltage is low. Check the supply.Alarm · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
OL1Motor overloadFault · Motor overload or overtemperature
OL2VFD overloadFault · Drive overload
OH1Rectifier module overheatFault · Drive overtemperature
OH2Inverter module overheatFault · Drive overtemperature

05 / Motor and load

Motor and load

CodeNameKind
OL3Electronic overloadThe VFD reports the overload pre-alarm at the set value. Check the load and the overload pre-alarm threshold.Fault · Load monitoring
dEuSpeed deviation faultFault · Motor stall
LLElectronic underload faultThe VFD reports the underload pre-alarm at the set value. Check the load and the underload pre-alarm point.Fault · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
EFExternal faultAn SI terminal set as an external fault input operated. Check the external device's input.Fault · External fault
CERS485 communication faultFault · Communication loss
PIDEPID feedback offline faultFault · Analog signal loss
PCEKeypad communication errorFault · Communication loss
UPEParameter upload errorFault · Communication loss
DNEParameter download errorFault · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
ItECurrent detection faultFault · Internal drive fault
tEMotor autotuning faultFault · Motor identification
EEPEEPROM operation faultFault · Parameter memory
ENDRunning time reachedThe VFD's actual running time is above the internal set running time. Ask the supplier to adjust the set running time.Fault · Setup
SToMaladjustment faultFault · Motor identification

Related

Related pages

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007