The V1000 is Yaskawa's compact vector control AC drive, for induction motors and, in open loop vector for PM, permanent magnet motors.

V1000 codes are short letter codes on the digital operator, such as oC, ov, GF, oL1 or CPF06. Below are the faults, minor faults and alarms, operator programming errors (oPE) and Auto-Tuning errors in Yaskawa's V1000 technical manual that the manual prints as text, with the causes and solutions Yaskawa gives for each.

01 / Reading codes

Reading and clearing V1000 codes

The digital operator shows the fault code, for example oC or Uv1. For a fault the ALM LED stays lit; if it flashes, the drive has a minor fault or alarm instead. Some conditions, such as overvoltage or an external fault, can raise either, so note which.

A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes. A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

02 / Current and earth faults

Current and earth faults

CodeNameKind
GFGround FaultFault · Earth fault
LFOutput Phase LossFault · Output phase loss
LF2Output current imbalanceFault · Output phase loss
oCOvercurrentFault · Overcurrent
SCIGBT Short CircuitFault · Output short circuit
HCACurrent AlarmAlarm · Overcurrent

03 / Voltage and supply

Voltage and supply

CodeNameKind
oL7High-Slip Braking oLFault · Braking resistor
ovOvervoltageFault · DC bus overvoltage
PFInput Phase LossFault · Input phase loss
rHBraking Resistor OverheatFault · Braking resistor
rrDynamic Braking TransistorFault · Braking resistor
Uv1DC Bus UndervoltageFault · DC bus undervoltage
Uv2Control Power Supply Voltage FaultFault · DC bus undervoltage
UvUndervoltageAlarm · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
oHHeatsink OverheatFault · Drive overtemperature
oH1Overheat 1 (Heatsink Overheat)Fault · Drive overtemperature
oH3Motor Overheat Alarm (PTC Input)Fault · Motor overload or overtemperature
oH4Motor Overheat Fault (PTC Input)Fault · Motor overload or overtemperature
oL1Motor OverloadFault · Motor overload or overtemperature
oL2Drive OverloadFault · Drive overload
LT-1Cooling Fan Maintenance TimeAlarm · Cooling fan

05 / Motor and load

Motor and load

CodeNameKind
FbHExcessive PID FeedbackFault · Process limit
FbLPID Feedback LossFault · Process limit
oL3Overtorque Detection 1Fault · Load monitoring
oL4Overtorque Detection 2Fault · Load monitoring
oL5Mechanical Weakening Detection 1Overtorque occurred matching the mechanical weakening conditions set in L6-08. Check for the cause of the mechanical weakening.Fault · Load monitoring
SToMotor Pull Out or Step Out DetectionFault · Motor stall
UL3Undertorque Detection 1Fault · Load monitoring
UL4Undertorque Detection 2Fault · Load monitoring
UL5Mechanical Weakening Detection 2Undertorque matched the mechanical weakening conditions set in L6-08. Check the load side for problems.Fault · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
bUSOption Communication ErrorFault · Communication loss
CEMEMOBUS/Modbus Communication ErrorFault · Communication loss
dEvSpeed Deviation (for Simple V/f with PG)Fault · Encoder signal
dWFLDriveWorksEZ FaultA fault was output by the DriveWorksEZ program. Correct the cause of the fault.Fault · External fault
E5MECHATROLINK Watchdog Timer ErrorNo data arrived from the PLC, so the watchdog timer timed out. Execute DISCONNECT or ALM_CLR, then issue a CONNECT or SYNC_SET command and proceed to phase 3.Fault · Communication loss
EF0Option Card External FaultFault · External fault
EF1External Fault (input terminal S1)Fault · External fault
EF2External Fault (input terminal S2)Fault · External fault
EF3External Fault (input terminal S3)Fault · External fault
EF4External Fault (input terminal S4)Fault · External fault
EF5External Fault (input terminal S5)Fault · External fault
EF6External Fault (input terminal S6)Fault · External fault
EF7External Fault (input terminal S7)Fault · External fault
oFA00Option Card Connection Error at Option Port CN5The option card is not compatible with the drive. Use a compatible option card.Fault · Communication loss
oFA01Option Card FaultThe option card is not connected properly. Turn the power off and reconnect the option card.Fault · Communication loss
oFA03Option Card FaultThe option card's self-diagnostics found an error: the card or hardware is damaged. Replace the option card and contact Yaskawa.Fault · Communication loss
oFA04Option Card FaultAn error writing to the option card's memory: the card or hardware is damaged. Replace the option card and contact Yaskawa.Fault · Communication loss
oPrExternal Digital Operator Connection FaultFault · Communication loss
oSOverspeed (Simple V/f with PG)Fault · Encoder signal
PGoPG Disconnect (for Simple V/f with PG)Fault · Encoder signal
AErStation Address Setting ErrorThe option card's node address (CC-Link, CANopen or MECHATROLINK) is outside the allowed range. Set F6-10 correctly for a CC-Link card, F6-20 for a MECHATROLINK card, or F6-35 for a CANopen card.Alarm · Communication loss
bbBaseblockAlarm · External fault
CALLSerial Communication Transmission ErrorAlarm · Communication loss
CyCMECHATROLINK Comm. Cycle Setting ErrorThe controller uses a communication cycle outside the MECHATROLINK option unit's allowed range. Set the controller's communication cycle within the option unit's allowed range.Alarm · Communication loss
dnEDrive DisabledAlarm · External fault
HbbSafe Disable Signal InputAlarm · Safety input
HbbFSafe Disable Signal InputAlarm · Safety input
oH2Drive Overheat WarningAn external device sent a Drive Overheat Warning to a multi-function input (H1-oo = B). Find the device that raised the warning; fixing it clears the warning.Alarm · External fault
PASSMEMOBUS/Modbus Comm. Test Mode CompleteThe MEMOBUS/Modbus self-test finished normally. Nothing to fix: this confirms the test passed.Alarm · Communication loss
SEMEMOBUS/Modbus Communication Test Mode ErrorA digital input set to the Modbus test (67H) was closed while the drive was running. Stop the drive and run the test again.Alarm · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
CFControl FaultFault · Setup
CoFCurrent Offset FaultFault · Internal drive fault
CPF02A/D Conversion ErrorFault · Internal drive fault
CPF03PWM Data ErrorThe PWM data is faulty: the drive hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF06EEPROM Data ErrorFault · Parameter memory
CPF07Terminal Board Communications ErrorFault · Internal drive fault
CPF08EEPROM Serial Communication FaultFault · Internal drive fault
CPF11RAM FaultThe hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF12FLASH Memory FaultA problem with the ROM (FLASH memory): the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF13Watchdog Circuit ExceptionA self-diagnostic problem: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF14Control Circuit FaultA CPU error, for example from noise: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF16Clock FaultA standard clock error: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF17Timing FaultA timing error in an internal process: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF18Control Circuit FaultA CPU error from a non-maskable interrupt, for example triggered by noise: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF19Control Circuit FaultA CPU error (manual reset due to noise or similar): the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF20RAM, FLASH, watchdog or clock faultOne of a RAM fault, FLASH memory error, watchdog circuit exception or clock error: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF21RAM, FLASH, watchdog or clock faultOne of a RAM fault, FLASH memory error, watchdog circuit exception or clock error: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF22A/D Conversion FaultAn A/D conversion error: the control circuit is damaged. Cycle power to the drive; if the fault continues, replace the drive.Fault · Internal drive fault
CPF23PWM Feedback FaultA PWM feedback error: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF24Drive Capacity Signal FaultAt power-up the drive read a capacity that does not exist: the hardware is damaged. Replace the drive.Fault · Internal drive fault
CPF25Terminal Board Not ConnectedThe terminal board is not connected correctly. Reconnect the terminal board to its connector on the drive, then cycle power.Fault · Internal drive fault
ErrEEPROM Write ErrorFault · Parameter memory
nSENode Setup ErrorA terminal assigned to the node setup function closed during run, or a run command was given while node setup was active. Check whether a run command came by mistake from the terminals or a communication option.Fault · Setup
SErToo Many Speed Search RestartsFault · Automatic restart limit
Uv3Undervoltage 3 (Inrush Prevention Circuit Fault)Fault · Internal drive fault
CrSTCan Not ResetAlarm · Setup
EFForward/Reverse Run Command Input ErrorAlarm · Setup
LT-2Capacitor Maintenance TimeAlarm · Internal drive fault
LT-3Soft Charge Bypass Relay Maintenance TimeThe DC bus soft charge relay has reached 90% of its expected performance life. Replace the control board or the whole drive; contact Yaskawa for control board replacement.Alarm · Internal drive fault
LT-4IGBT Maintenance Time (50%)The IGBTs have reached 50% of their expected performance life. Check the load, carrier frequency and output frequency.Alarm · Internal drive fault
rUnMotor Switch during RunA motor switch command was given while running. Change the operating pattern so motors are switched only while the drive is stopped.Alarm · Setup
TrPCIGBT Maintenance Time (90%)The IGBTs have reached 90% of their expected performance life. Replace the drive.Alarm · Internal drive fault
oPE01Drive Capacity Setting FaultThe drive capacity setting (o2-04) does not match the drive's actual capacity. Correct o2-04.Fault · Setup
oPE02Parameter Range Setting ErrorFault · Setup
oPE03Multi-Function Input Selection ErrorFault · Setup
oPE04Initialization requiredFault · Setup
oPE05Run Command/Frequency Reference Source Selection ErrorFault · Setup
oPE07Multi-Function Analog Input Selection ErrorFault · Setup
oPE08Parameter Selection ErrorFault · Setup
oPE09PID Control Selection FaultFault · Setup
oPE10V/f Data Setting ErrorFault · Setup
oPE11Carrier Frequency Setting ErrorFault · Setup
oPE13Pulse Monitor Selection ErrorThe pulse train monitor scaling is 0 (H6-07 = 0) while H6-06 is not 000, 031, 101, 102, 105 or 116. Change H6-07, or set H6-06 to 000, 031, 101, 102, 105 or 116.Fault · Setup
End1Excessive V/f SettingAlarm · Motor identification
End2Motor Iron-Core Saturation CoefficientAlarm · Motor identification
End3Rated Current Setting AlarmAlarm · Motor identification
Er-01Motor Data ErrorFault · Motor identification
Er-02Minor FaultFault · Motor identification
Er-03STOP Button InputAuto-Tuning was cancelled with the STOP button. Auto-Tuning did not complete and must be performed again.Fault · Motor identification
Er-04Line-to-Line Resistance ErrorFault · Motor identification
Er-05No-Load Current ErrorFault · Motor identification
Er-08Rated Slip ErrorFault · Motor identification
Er-09Acceleration ErrorFault · Motor identification
Er-11Motor Speed FaultFault · Motor identification
Er-12Current Detection ErrorFault · Motor identification

Related

Related pages

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.