The V1000 is Yaskawa's compact vector control AC drive, for induction motors and, in open loop vector for PM, permanent magnet motors.
V1000 codes are short letter codes on the digital operator, such as oC, ov, GF, oL1 or CPF06. Below are the faults, minor faults and alarms, operator programming errors (oPE) and Auto-Tuning errors in Yaskawa's V1000 technical manual that the manual prints as text, with the causes and solutions Yaskawa gives for each.
01 / Reading codes
Reading and clearing V1000 codes
The digital operator shows the fault code, for example oC or Uv1. For a fault the ALM LED stays lit; if it flashes, the drive has a minor fault or alarm instead. Some conditions, such as overvoltage or an external fault, can raise either, so note which.
A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes. A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
02 / Current and earth faults
Current and earth faults
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| oL7 | High-Slip Braking oL | Fault · Braking resistor |
| ov | Overvoltage | Fault · DC bus overvoltage |
| PF | Input Phase Loss | Fault · Input phase loss |
| rH | Braking Resistor Overheat | Fault · Braking resistor |
| rr | Dynamic Braking Transistor | Fault · Braking resistor |
| Uv1 | DC Bus Undervoltage | Fault · DC bus undervoltage |
| Uv2 | Control Power Supply Voltage Fault | Fault · DC bus undervoltage |
| Uv | Undervoltage | Alarm · DC bus undervoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| oH | Heatsink Overheat | Fault · Drive overtemperature |
| oH1 | Overheat 1 (Heatsink Overheat) | Fault · Drive overtemperature |
| oH3 | Motor Overheat Alarm (PTC Input) | Fault · Motor overload or overtemperature |
| oH4 | Motor Overheat Fault (PTC Input) | Fault · Motor overload or overtemperature |
| oL1 | Motor Overload | Fault · Motor overload or overtemperature |
| oL2 | Drive Overload | Fault · Drive overload |
| LT-1 | Cooling Fan Maintenance Time | Alarm · Cooling fan |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| FbH | Excessive PID Feedback | Fault · Process limit |
| FbL | PID Feedback Loss | Fault · Process limit |
| oL3 | Overtorque Detection 1 | Fault · Load monitoring |
| oL4 | Overtorque Detection 2 | Fault · Load monitoring |
| oL5 | Mechanical Weakening Detection 1Overtorque occurred matching the mechanical weakening conditions set in L6-08. Check for the cause of the mechanical weakening. | Fault · Load monitoring |
| STo | Motor Pull Out or Step Out Detection | Fault · Motor stall |
| UL3 | Undertorque Detection 1 | Fault · Load monitoring |
| UL4 | Undertorque Detection 2 | Fault · Load monitoring |
| UL5 | Mechanical Weakening Detection 2Undertorque matched the mechanical weakening conditions set in L6-08. Check the load side for problems. | Fault · Load monitoring |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| bUS | Option Communication Error | Fault · Communication loss |
| CE | MEMOBUS/Modbus Communication Error | Fault · Communication loss |
| dEv | Speed Deviation (for Simple V/f with PG) | Fault · Encoder signal |
| dWFL | DriveWorksEZ FaultA fault was output by the DriveWorksEZ program. Correct the cause of the fault. | Fault · External fault |
| E5 | MECHATROLINK Watchdog Timer ErrorNo data arrived from the PLC, so the watchdog timer timed out. Execute DISCONNECT or ALM_CLR, then issue a CONNECT or SYNC_SET command and proceed to phase 3. | Fault · Communication loss |
| EF0 | Option Card External Fault | Fault · External fault |
| EF1 | External Fault (input terminal S1) | Fault · External fault |
| EF2 | External Fault (input terminal S2) | Fault · External fault |
| EF3 | External Fault (input terminal S3) | Fault · External fault |
| EF4 | External Fault (input terminal S4) | Fault · External fault |
| EF5 | External Fault (input terminal S5) | Fault · External fault |
| EF6 | External Fault (input terminal S6) | Fault · External fault |
| EF7 | External Fault (input terminal S7) | Fault · External fault |
| oFA00 | Option Card Connection Error at Option Port CN5The option card is not compatible with the drive. Use a compatible option card. | Fault · Communication loss |
| oFA01 | Option Card FaultThe option card is not connected properly. Turn the power off and reconnect the option card. | Fault · Communication loss |
| oFA03 | Option Card FaultThe option card's self-diagnostics found an error: the card or hardware is damaged. Replace the option card and contact Yaskawa. | Fault · Communication loss |
| oFA04 | Option Card FaultAn error writing to the option card's memory: the card or hardware is damaged. Replace the option card and contact Yaskawa. | Fault · Communication loss |
| oPr | External Digital Operator Connection Fault | Fault · Communication loss |
| oS | Overspeed (Simple V/f with PG) | Fault · Encoder signal |
| PGo | PG Disconnect (for Simple V/f with PG) | Fault · Encoder signal |
| AEr | Station Address Setting ErrorThe option card's node address (CC-Link, CANopen or MECHATROLINK) is outside the allowed range. Set F6-10 correctly for a CC-Link card, F6-20 for a MECHATROLINK card, or F6-35 for a CANopen card. | Alarm · Communication loss |
| bb | Baseblock | Alarm · External fault |
| CALL | Serial Communication Transmission Error | Alarm · Communication loss |
| CyC | MECHATROLINK Comm. Cycle Setting ErrorThe controller uses a communication cycle outside the MECHATROLINK option unit's allowed range. Set the controller's communication cycle within the option unit's allowed range. | Alarm · Communication loss |
| dnE | Drive Disabled | Alarm · External fault |
| Hbb | Safe Disable Signal Input | Alarm · Safety input |
| HbbF | Safe Disable Signal Input | Alarm · Safety input |
| oH2 | Drive Overheat WarningAn external device sent a Drive Overheat Warning to a multi-function input (H1-oo = B). Find the device that raised the warning; fixing it clears the warning. | Alarm · External fault |
| PASS | MEMOBUS/Modbus Comm. Test Mode CompleteThe MEMOBUS/Modbus self-test finished normally. Nothing to fix: this confirms the test passed. | Alarm · Communication loss |
| SE | MEMOBUS/Modbus Communication Test Mode ErrorA digital input set to the Modbus test (67H) was closed while the drive was running. Stop the drive and run the test again. | Alarm · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| CF | Control Fault | Fault · Setup |
| CoF | Current Offset Fault | Fault · Internal drive fault |
| CPF02 | A/D Conversion Error | Fault · Internal drive fault |
| CPF03 | PWM Data ErrorThe PWM data is faulty: the drive hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF06 | EEPROM Data Error | Fault · Parameter memory |
| CPF07 | Terminal Board Communications Error | Fault · Internal drive fault |
| CPF08 | EEPROM Serial Communication Fault | Fault · Internal drive fault |
| CPF11 | RAM FaultThe hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF12 | FLASH Memory FaultA problem with the ROM (FLASH memory): the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF13 | Watchdog Circuit ExceptionA self-diagnostic problem: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF14 | Control Circuit FaultA CPU error, for example from noise: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF16 | Clock FaultA standard clock error: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF17 | Timing FaultA timing error in an internal process: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF18 | Control Circuit FaultA CPU error from a non-maskable interrupt, for example triggered by noise: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF19 | Control Circuit FaultA CPU error (manual reset due to noise or similar): the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF20 | RAM, FLASH, watchdog or clock faultOne of a RAM fault, FLASH memory error, watchdog circuit exception or clock error: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF21 | RAM, FLASH, watchdog or clock faultOne of a RAM fault, FLASH memory error, watchdog circuit exception or clock error: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF22 | A/D Conversion FaultAn A/D conversion error: the control circuit is damaged. Cycle power to the drive; if the fault continues, replace the drive. | Fault · Internal drive fault |
| CPF23 | PWM Feedback FaultA PWM feedback error: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF24 | Drive Capacity Signal FaultAt power-up the drive read a capacity that does not exist: the hardware is damaged. Replace the drive. | Fault · Internal drive fault |
| CPF25 | Terminal Board Not ConnectedThe terminal board is not connected correctly. Reconnect the terminal board to its connector on the drive, then cycle power. | Fault · Internal drive fault |
| Err | EEPROM Write Error | Fault · Parameter memory |
| nSE | Node Setup ErrorA terminal assigned to the node setup function closed during run, or a run command was given while node setup was active. Check whether a run command came by mistake from the terminals or a communication option. | Fault · Setup |
| SEr | Too Many Speed Search Restarts | Fault · Automatic restart limit |
| Uv3 | Undervoltage 3 (Inrush Prevention Circuit Fault) | Fault · Internal drive fault |
| CrST | Can Not Reset | Alarm · Setup |
| EF | Forward/Reverse Run Command Input Error | Alarm · Setup |
| LT-2 | Capacitor Maintenance Time | Alarm · Internal drive fault |
| LT-3 | Soft Charge Bypass Relay Maintenance TimeThe DC bus soft charge relay has reached 90% of its expected performance life. Replace the control board or the whole drive; contact Yaskawa for control board replacement. | Alarm · Internal drive fault |
| LT-4 | IGBT Maintenance Time (50%)The IGBTs have reached 50% of their expected performance life. Check the load, carrier frequency and output frequency. | Alarm · Internal drive fault |
| rUn | Motor Switch during RunA motor switch command was given while running. Change the operating pattern so motors are switched only while the drive is stopped. | Alarm · Setup |
| TrPC | IGBT Maintenance Time (90%)The IGBTs have reached 90% of their expected performance life. Replace the drive. | Alarm · Internal drive fault |
| oPE01 | Drive Capacity Setting FaultThe drive capacity setting (o2-04) does not match the drive's actual capacity. Correct o2-04. | Fault · Setup |
| oPE02 | Parameter Range Setting Error | Fault · Setup |
| oPE03 | Multi-Function Input Selection Error | Fault · Setup |
| oPE04 | Initialization required | Fault · Setup |
| oPE05 | Run Command/Frequency Reference Source Selection Error | Fault · Setup |
| oPE07 | Multi-Function Analog Input Selection Error | Fault · Setup |
| oPE08 | Parameter Selection Error | Fault · Setup |
| oPE09 | PID Control Selection Fault | Fault · Setup |
| oPE10 | V/f Data Setting Error | Fault · Setup |
| oPE11 | Carrier Frequency Setting Error | Fault · Setup |
| oPE13 | Pulse Monitor Selection ErrorThe pulse train monitor scaling is 0 (H6-07 = 0) while H6-06 is not 000, 031, 101, 102, 105 or 116. Change H6-07, or set H6-06 to 000, 031, 101, 102, 105 or 116. | Fault · Setup |
| End1 | Excessive V/f Setting | Alarm · Motor identification |
| End2 | Motor Iron-Core Saturation Coefficient | Alarm · Motor identification |
| End3 | Rated Current Setting Alarm | Alarm · Motor identification |
| Er-01 | Motor Data Error | Fault · Motor identification |
| Er-02 | Minor Fault | Fault · Motor identification |
| Er-03 | STOP Button InputAuto-Tuning was cancelled with the STOP button. Auto-Tuning did not complete and must be performed again. | Fault · Motor identification |
| Er-04 | Line-to-Line Resistance Error | Fault · Motor identification |
| Er-05 | No-Load Current Error | Fault · Motor identification |
| Er-08 | Rated Slip Error | Fault · Motor identification |
| Er-09 | Acceleration Error | Fault · Motor identification |
| Er-11 | Motor Speed Fault | Fault · Motor identification |
| Er-12 | Current Detection Error | Fault · Motor identification |
Related
Related pages
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.