MachineryFix

AC drive (VFD) · 159 codes

Yaskawa A1000 fault codes

The A1000 is Yaskawa's high performance vector control AC drive, running induction and permanent magnet motors in open and closed loop, with option ports CN5-A, CN5-B and CN5-C for encoder and communication cards.

A1000 fault codes are short letter codes on the digital operator, such as oC, ov, GF, oL1 or CPF06, and many are shared with Yaskawa's V1000. Below is every fault, alarm, operator programming error (oPE) and Auto-Tuning error (End, Er) that the A1000 quick start guide prints as text, with the causes and solutions Yaskawa gives.

01 / Reading codes

Reading and clearing A1000 codes

The digital operator shows the fault code, for example oC or Uv1. A fault stops the drive and switches the fault relay output MA-MB-MC.

A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again. An alarm is a protection function that does not necessarily stop the drive: the ALM light blinks and the code flashes, and a multi-function output set to H2-oo = 10 closes. Once the cause is removed, the drive returns to the state it was in before the alarm.

  • Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
  • Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.

02 / Current and earth faults

Current and earth faults

CodeNameKind
GFGround FaultFault · Earth fault
LFOutput Phase LossFault · Output phase loss
LF2Output Current ImbalanceFault · Output phase loss
LF3Power Unit Output Phase Loss 3A phase was lost on the output side of the power unit (models 4A0930 and 4A1200; enabled with L8-78 = 1). Fault · Output phase loss
oCOvercurrentFault · Overcurrent
SCOutput Short Circuit or IGBT FaultA short circuit or ground fault was detected (software PRG 1015 and later). The fault cannot be reset, to prevent damage to the internal circuits. Fault · Output short circuit
UnbCCurrent UnbalanceThe current flow became unbalanced (models 4A0930 and 4A1200). Fault · Output phase loss
HCACurrent AlarmThe drive current went above the overcurrent warning level (150% of rated current). Alarm · Overcurrent

03 / Voltage and supply

Voltage and supply

CodeNameKind
boLBraking Transistor Overload FaultThe braking transistor reached its overload level. Fault · Braking resistor
oL7High Slip Braking oLDuring High Slip Braking the output frequency stayed constant for longer than n3-04. Fault · Braking resistor
ovOvervoltageFault · DC bus overvoltage
PFInput Phase LossFault · Input phase loss
rFBraking Resistor FaultFault · Braking resistor
rHBraking Resistor OverheatFault · Braking resistor
rrDynamic Braking TransistorFault · Braking resistor
Uv1DC Bus UndervoltageFault · DC bus undervoltage
Uv2Control Power Supply Voltage FaultFault · DC bus undervoltage
UvUndervoltageAlarm · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
FAnInternal Fan FaultFault · Cooling fan
oHHeatsink OverheatFault · Drive overtemperature
oH1Overheat 1 (Heatsink Overheat)Fault · Drive overtemperature
oH3Motor Overheat Alarm (PTC Input)Fault · Motor overload or overtemperature
oH4Motor Overheat Fault (PTC Input)Fault · Motor overload or overtemperature
oH5Motor Overheat (NTC Input)The motor temperature went above L1-16 (L1-18 for motor 2) on models 4A0930 and 4A1200. Reduce the load.Fault · Motor overload or overtemperature
oL1Motor OverloadFault · Motor overload or overtemperature
oL2Drive OverloadFault · Drive overload
THoThermistor DisconnectThe thermistor that measures motor temperature is disconnected (models 4A0930 and 4A1200). Fault · Temperature sensor signal
LT-1Cooling Fan Maintenance TimeThe cooling fan has reached 90% of its expected life and may need replacing. Replace the cooling fan, then set o4-03 to 0 to reset the maintenance monitor.Alarm · Cooling fan
oH2Heatsink Overheat WarningA Heatsink Overheat Warning was input to a multi-function input, S1 to S8 (H1-oo = B). Alarm · Drive overtemperature

05 / Motor and load

Motor and load

CodeNameKind
FbHExcessive PID FeedbackFault · Process limit
FbLPID Feedback LossFault · Process limit
LSoLSo FaultPull-out was detected at low speed: a wrong motor code, too heavy a load, the motor pole position detected wrongly, or L8-93, L8-94 and L8-95 set wrongly. Enter the correct motor code in E5-01; for special motors, enter all E5 parameters from the test report.Fault · Motor stall
oL3Overtorque Detection 1Fault · Load monitoring
oL4Overtorque Detection 2The current stayed above Torque Detection Level 2 (L6-05) for longer than L6-06. Check L6-05 and L6-06.Fault · Load monitoring
oL5Mechanical Weakening Detection 1Overtorque occurred matching the conditions set in L6-08. Fault · Load monitoring
SToPull-Out DetectionThe motor pulled out of step: it went past its pull-out torque. Fault · Motor stall
UL3Undertorque Detection 1Fault · Load monitoring
UL4Undertorque Detection 2The current stayed below Torque Detection Level 2 (L6-05) for longer than L6-06. Fault · Load monitoring
UL5Mechanical Weakening Detection 2The operating conditions matched those set in L6-08. Fault · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
bUSOption Communication ErrorFault · Communication loss
CEMEMOBUS/Modbus Communication ErrorFault · Communication loss
dEvSpeed DeviationIn control modes with PG (and AOLV/PM), the difference between the speed reference and speed feedback stayed above F1-10 for longer than F1-11. Fault · Encoder signal
dv1Z Pulse FaultIn CLV/PM, the motor turned a full revolution without the Z pulse being detected. Fault · Encoder signal
dv2Z Pulse Noise Fault DetectionIn CLV/PM, the Z pulse was more than 5 degrees out of phase for 10 consecutive revolutions. Fault · Encoder signal
dv3Inversion DetectionIn CLV/PM, torque reference and acceleration were in opposite directions and the speed reference and actual speed differed by more than 30%, the number of times set in F1-18. Fault · Encoder signal
dv4Inversion Prevention DetectionIn CLV/PM, the encoder pulses show the motor turning against the speed reference (pulse count set in F1-19; set F1-19 to 0 to disable where reverse rotation is normal). Fault · Encoder signal
dWALDriveWorksEZ FaultA fault output by the DriveWorksEZ program. Fault · External fault
dWFLDriveWorksEZ FaultA fault output by the DriveWorksEZ program. Fault · External fault
E5MECHATROLINK Watchdog Timer ErrorNo data arrived from the PLC, so the watchdog timer timed out. Execute DISCONNECT or ALM_CLR, then issue a CONNECT or SYNC_SET command and proceed to phase 3 (see the SI-T3 option manual).Fault · Communication loss
EF0Option Card External FaultFault · External fault
EF1External Fault (input terminal S1)Fault · External fault
EF2External Fault (input terminal S2)Fault · External fault
EF3External Fault (input terminal S3)Fault · External fault
EF4External Fault (input terminal S4)Fault · External fault
EF5External Fault (input terminal S5)Fault · External fault
EF6External Fault (input terminal S6)Fault · External fault
EF7External Fault (input terminal S7)Fault · External fault
EF8External Fault (input terminal S8)Fault · External fault
oFA00Option Card Connection Error at Option Port CN5-AThe option card in CN5-A is not compatible. Fault · Communication loss
oFA01Option Card Fault at Option Port CN5-AThe option card in CN5-A is not connected properly. Turn off the power and reconnect the option card, making sure it is fixed properly.Fault · Communication loss
oFb00Option Card Fault at Option Port CN5-BThe option card in CN5-B is not compatible. Fault · Communication loss
oFb01Option Card Fault at Option Port CN5-BThe option card in CN5-B is not connected properly. Fault · Communication loss
oFb02Option Card Fault at Option Port CN5-BThe same type of option card is already connected. Fault · Communication loss
oFC00Option Card Connection Error at Option Port CN5-CThe option card in CN5-C is not compatible. Fault · Communication loss
oFC01Option Card Fault at Option Port CN5-CThe option card in CN5-C is not connected properly. Fault · Communication loss
oFC02Option Card Fault at Option Port CN5-CThe same type of option card is already connected. Fault · Communication loss
oPrExternal Digital Operator Connection FaultFault · Communication loss
oSOverspeedThe motor speed feedback went above the F1-08 setting. Fault · Encoder signal
PGoPG DisconnectNo PG pulses arrived for longer than the time set in F1-14 (any control mode using a PG option card). Fault · Encoder signal
PGoHPG Hardware FaultWith a PG-X3 option card, the PG cable is not connected properly. Fault · Encoder signal
SvEZero Servo FaultThe position deviated during zero servo. Fault · Encoder signal
AErStation Address Setting ErrorThe option card's node address is outside the acceptable range (CC-Link, CANopen, MECHATROLINK). Alarm · Communication loss
bbBaseblockThe drive's output is interrupted by an external baseblock signal. Alarm · External fault
CALLSerial Communication Transmission ErrorAlarm · Communication loss
CyCMECHATROLINK Comm. Cycle Setting ErrorA communication cycle setting error was detected. Alarm · Communication loss
HbbSafe Disable Signal InputBoth Safe Disable input channels are open. Alarm · Safety input
HbbFSafe Disable Signal InputOne Safe Disable channel is open while the other is closed. Alarm · Safety input
PASSMEMOBUS/Modbus Comm. Test Mode CompleteThe MEMOBUS/Modbus test finished normally: the test was successful. Alarm · Communication loss
SEMEMOBUS/Modbus Communication Test Mode ErrorA digital input set to 67H (MEMOBUS/Modbus test) was closed while the drive was running. Stop the drive and run the test again.Alarm · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
CFControl FaultThe torque limit was reached continuously for three seconds after a stop command, and the drive could not decelerate, in Open Loop Vector control. Fault · Setup
CoFCurrent Offset FaultThe drive started while the current detection circuit had failed, or while voltage was still induced in the motor (coasting or after rapid deceleration). If the run command was given while the motor was coasting, enable Speed Search at start (b3-01 = 1) or use Speed Search 1 or 2 on a multi-function input (H1-oo = 61 or 62).Fault · Internal drive fault
CPF02A/D Conversion ErrorAn A/D conversion or control circuit error: the control circuit is damaged. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF03Control Board Connection ErrorFault · Internal drive fault
CPF06EEPROM Memory Data ErrorFault · Parameter memory
CPF07Terminal Board Connection ErrorA faulty connection between the terminal board and the control board. Turn the power off and reconnect the terminal board.Fault · Internal drive fault
CPF08Terminal Board Connection ErrorA faulty connection between the terminal board and the control board. Turn the power off and reconnect the terminal board.Fault · Internal drive fault
CPF11RAM FaultA self-diagnostic error in the control circuit, or a damaged connector on the operator. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF12FLASH Memory FaultA problem with the ROM (FLASH memory). Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF13Watchdog Circuit ExceptionA self-diagnostics problem. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF14Control Circuit FaultA CPU error, for example from interference. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF16Clock FaultA standard clock error. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF17Timing FaultA timing error in an internal process. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF18Control Circuit FaultA CPU error from a non-maskable interrupt, for example triggered by interference. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF19Control Circuit FaultA CPU error (manual reset due to interference or similar). Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF20Control Circuit ErrorThe hardware is damaged. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF21Control Circuit ErrorThe hardware is damaged. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF22Hybrid IC FailureA hybrid IC failure on the power board. Cycle power; if it continues, replace the power board or the whole drive.Fault · Internal drive fault
CPF23Control Board Connection ErrorA connection error between the control board and the drive: the hardware is damaged. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF24Drive Unit Signal FaultThe drive capacity could not be detected correctly at power-up: the hardware is damaged. Cycle power to the drive; if the problem continues, replace the control board or the whole drive (contact Yaskawa for control board replacement).Fault · Internal drive fault
CPF25Terminal Board Not ConnectedThe terminal board is not connected correctly. Reconnect the terminal board to its connector on the drive, then cycle power.Fault · Internal drive fault
dv7Initial Polarity Estimation TimeoutThe initial polarity estimation timed out (drive software PRG 1015 and later). Fault · Motor identification
dWF1EEPROM Memory DriveWorksEZ Data ErrorThe DriveWorksEZ program saved to EEPROM is faulty. Fault · Parameter memory
ErrEEPROM Write ErrorFault · Parameter memory
nSENode Setup ErrorA terminal assigned to the node setup function closed during run, a run command was given while node setup was active, or overcurrent occurred during overexcitation deceleration. Stop the drive when using the node setup function.Fault · Setup
SErToo Many Speed Search RestartsFault · Automatic restart limit
Uv3Undervoltage 3 (Soft-Charge Bypass Relay Fault)Fault · Internal drive fault
Uv4Gate Drive Board UndervoltageThe voltage in the gate drive board circuit dropped (models 4A0930 and 4A1200). Fault · Internal drive fault
voFOutput Voltage Detection FaultA problem with the voltage on the drive's output side: damaged hardware, or the internal module or protection board affected by abnormal ambient conditions. Lower the ambient temperature.Fault · Internal drive fault
CrSTCannot ResetAlarm · Setup
dnEDrive DisabledDrive Enable is set on a multi-function input (H1-oo = 6A) and that signal was switched off. Check the operation sequence.Alarm · Setup
EFForward/Reverse Run Command Input ErrorForward run and reverse run were both closed for longer than 0.5 s: a sequence error. The motor ramps to stop. Check the forward and reverse command sequence and correct it.Alarm · Setup
LT-2Capacitor Maintenance TimeThe main circuit and control circuit capacitors have reached 90% of their expected life. Replace the drive.Alarm · Internal drive fault
LT-3Soft Charge Bypass Relay Maintenance TimeThe DC bus soft charge relay has reached 90% of its expected life. Replace the drive.Alarm · Internal drive fault
LT-4IGBT Maintenance Time (50%)The IGBTs have reached 50% of their expected life. Check the load, carrier frequency and output frequency.Alarm · Internal drive fault
rUnMotor Switch during RunA command to switch motors was entered during run. Alarm · Setup
TrPCIGBT Maintenance Time (90%)The IGBTs have reached 90% of their expected life. Replace the drive.Alarm · Internal drive fault
oPE01Drive Capacity Setting FaultThe drive's capacity and the value set in o2-04 do not match. Fault · Setup
oPE02Parameter Range Setting ErrorA parameter is set outside its range; monitor U1-18 shows which. Fault · Setup
oPE03Multi-Function Input Selection ErrorContradictory settings are assigned to multi-function contact inputs H1-01 to H1-08. Fault · Setup
oPE04Initialization RequiredFault · Setup
oPE05Run Command/Frequency Reference Source Selection ErrorFault · Setup
oPE06Control Method Selection ErrorThe control method setting needs correcting. Fault · Setup
oPE07Multi-Function Analog Input Selection ErrorContradictory settings are assigned to analog inputs H3-02, H3-06 and H3-10, or they conflict with PID functions. Fault · Setup
oPE08Parameter Selection ErrorA function is set that cannot be used in the selected motor control method. Fault · Setup
oPE09PID Control Selection FaultThe PID function selection is incorrect; it needs PID control enabled (b5-01 = 1 to 4). Fault · Setup
oPE10V/f Data Setting ErrorThe V/f pattern does not follow the rule E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 (E3 parameters for motor 2). Fault · Setup
oPE11Carrier Frequency Setting ErrorThe carrier frequency setting needs correcting. Fault · Setup
oPE13Pulse Monitor Selection ErrorThe pulse train monitor selection (H6-06) is set incorrectly. Fault · Setup
oPE15Torque Control Setting ErrorParameters are set that are not allowed together with Torque Control. Fault · Setup
oPE16Energy Savings Constants ErrorFault · Setup
oPE18Online Tuning Parameter Setting ErrorThe parameters controlling online tuning are not set correctly. Fault · Setup
oPE20PG-F3 Setting ErrorThe encoder signal frequency is too high. Fault · Setup
End1Excessive V/f SettingFault · Motor identification
End2Motor Iron-Core Saturation CoefficientFault · Motor identification
End3Rated Current Setting AlarmFault · Motor identification
End4Adjusted Slip Calculation ErrorFault · Motor identification
End5Resistance Tuning ErrorFault · Motor identification
End6Leakage Inductance AlarmFault · Motor identification
End7No-Load Current AlarmFault · Motor identification
Er-01Motor Data ErrorFault · Motor identification
Er-02Minor FaultFault · Motor identification
Er-03STOP Button InputAuto-Tuning was cancelled with the STOP button and did not complete. Restart Auto-Tuning.Fault · Motor identification
Er-04Line-to-Line Resistance ErrorFault · Motor identification
Er-05No-Load Current ErrorFault · Motor identification
Er-08Rated Slip ErrorFault · Motor identification
Er-09Acceleration ErrorFault · Motor identification
Er-10Motor Direction ErrorFault · Motor identification
Er-11Motor Speed ErrorFault · Motor identification
Er-12Current Detection ErrorFault · Motor identification
Er-13Leakage Inductance ErrorFault · Motor identification
Er-14Motor Speed Error 2The motor speed went above twice the speed reference's amplitude during Inertia Tuning. Reduce the ASR gain in C5-01.Fault · Motor identification
Er-15Torque Saturation ErrorFault · Motor identification
Er-16Inertia ID ErrorFault · Motor identification
Er-17Reverse Prohibited ErrorReverse rotation is prohibited while Inertia Tuning is being attempted; it cannot run with reverse restricted. If the application can rotate in reverse, set b1-04 to 0 and then perform Inertia Tuning.Fault · Motor identification
Er-18Induction Voltage ErrorThe Back EMF constant (induced voltage) result is outside the allowable range. Double-check the data entered in the T2 parameters and restart Auto-Tuning.Fault · Motor identification
Er-19PM Inductance ErrorTuning tried to set E5-08 or E5-09 to a value outside the allowable range. Double-check the data entered in the T2 parameters and restart Auto-Tuning.Fault · Motor identification
Er-20Stator Resistance ErrorStator resistance tuning tried to set E5-06 to a value outside the allowable range. Double-check the data entered in the T2 parameters and restart Auto-Tuning.Fault · Motor identification
Er-21Z Pulse Correction ErrorFault · Motor identification
Er-25High Frequency Injection Parameter Tuning ErrorThe motor data was incorrect. Perform Stationary Auto-Tuning, then High Frequency Injection Parameter Tuning again; if it continues, high frequency injection control may not be possible with that motor.Fault · Motor identification

Related

Related pages

Source

Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.