Updated
Check these first
- 01Control power missing — A blown control fuse, a failed 24V/SMPS supply or a tripped control MCB means the PLC and contactors never get power.
- 02Safety circuit open — An E-stop latched in, a tripped safety relay, an open guard interlock or a light-curtain fault holds the start circuit open by design.
- 03Incoming supply fault — A lost phase, a tripped upstream breaker or a loose incoming termination.
- 04Control transformer / PLC fault — A failed control transformer, a PLC sitting in STOP, or a corrupted program means the start logic never executes even though power is present.
- 05Motor protection latched — An overload relay, motor-protection circuit breaker or drive fault that hasn't been reset will block start until the underlying trip is cleared.
01 / Overview
Machine Won't Start
A machine that's completely dead — no HMI, no contactors pulling in, nothing — is almost always a supply, safety-circuit or control-power problem rather than a failure of the machine itself. The trick is working the chain from incoming supply through to the start command in order, instead of guessing.
Every machine has a start chain: the incoming supply feeds a main breaker, which feeds the control power, which energises the safety circuit, which allows the PLC or start circuit to pull in the drive or contactor, which finally runs the motor. A break anywhere in that chain leaves the machine dead, and the symptom looks the same whichever link has failed. That is why checking in order works and guessing doesn't.
The table below follows the chain from the supply end. Most no-starts are found in the first four steps, and most of those checks can be made by a plant electrician with a multimeter and the panel drawings. Where a step needs the panel opened live, lockout, or the PLC software, it is marked, and that is the point to call a controls engineer.
02 / Diagnosis
Likely causes
The handful of things that actually cause this — in the order we rule them out.
Control power missing
A blown control fuse, a failed 24V/SMPS supply or a tripped control MCB means the PLC and contactors never get power. The main motor supply can be perfectly healthy while nothing responds.
Safety circuit open
An E-stop latched in, a tripped safety relay, an open guard interlock or a light-curtain fault holds the start circuit open by design. One open contact anywhere in the string stops everything.
Incoming supply fault
A lost phase, a tripped upstream breaker or a loose incoming termination. Three-phase gear will often sit dead or trip immediately on a single-phasing supply.
Control transformer / PLC fault
A failed control transformer, a PLC sitting in STOP, or a corrupted program means the start logic never executes even though power is present.
Motor protection latched
An overload relay, motor-protection circuit breaker or drive fault that hasn't been reset will block start until the underlying trip is cleared.
02b / In order
Work through it in this order
Each check either clears a link in the chain or tells you where the fault is.
| Check | If it's OK | If it isn't |
|---|---|---|
| 01Is the supply present on all three phases at the machine's incoming terminals? | Move on to the main breaker. | The fault is upstream: a tripped feeder breaker, a blown fuse or a loose incoming termination. Check the distribution board before the machine. |
| 02Is the main breaker or isolator closed, and has anything tripped? | Move on to control power. | Find out why it tripped before resetting. An immediate re-trip means a short or earth fault downstream. |
| 03Is control power present: control fuses intact, 24 V DC at the power supply output, and the control transformer secondary live? | Move on to the safety chain. | A blown control fuse or failed 24 V supply explains a completely dead machine with a healthy main supply. Look for what blew it: a shorted sensor cable or coil is common. |
| 04Are all E-stops released, guards closed and the safety relay reset (its output LEDs lit)? | Move on to the start permissives. | Follow the safety string contact by contact. One open door switch or latched E-stop anywhere holds the whole machine off by design. |
| 05Is the PLC in RUN with no fault LED, and are the start permissives on the HMI or PLC all made? | Move on to the drive or contactor. | A PLC in STOP, a lost program or a missing permissive such as low air pressure, lube level or a tool not clamped will block the start without any power fault. |
| 06Does the drive show ready with no fault, and is the motor overload reset? | Check the start command itself: the push button, the run signal to the drive and the motor connections. | Note the drive fault code or overload trip, and find the cause before resetting. A drive that faults on every start points at the drive, motor or cable. |
| 07Does the contactor pull in or the drive output rise when start is pressed? | The fault is at the motor or mechanical load: an open motor winding, a seized load or a brake not releasing. | The start signal isn't reaching the contactor coil or drive input. Trace it back through the start circuit. |
Stuck at one of these steps? Send the machine and what you've found so far.
WhatsApp the fault03 / Onsite
What our technician checks
A methodical path to root cause — not a scattergun of part swaps.
- 01Confirm incoming three-phase supply, phase balance and neutral/earth
- 02Verify control power — fuses, control MCB, 24V/SMPS supply and control transformer
- 03Walk the safety string: E-stops, safety relays, guard interlocks, light curtains
- 04Check PLC state (RUN/STOP), diagnostic buffer and start-permissive logic
- 05Read any drive/overload trips and clear only after finding the cause
03b / Safety
What you can check, and what needs lockout
Safe for a plant electrician
- Check whether other machines on the same feeder are also dead, which points at the supply rather than the machine.
- Look at breakers, overload relays and fuse indicators through the panel door window or with the panel isolated, and note anything tripped.
- Release E-stops one by one, close every guard and press the safety reset, watching the safety relay LEDs.
- Read the HMI alarm screen, the PLC status LEDs and any drive keypad, and photograph them before resetting anything.
- Check the obvious permissives: air pressure, lubrication level, coolant level and any selector switch left in manual or local.
Needs lockout or a controls engineer
- Measuring voltages inside a live panel, which needs a competent person, the right meter category and PPE.
- Replacing fuses or breakers that blew or tripped without a known cause; the cause has to be found first.
- Going online to the PLC, forcing inputs or editing logic.
- Any work on a drive, which holds a dangerous charge in its DC bus after isolation.
03c / Local conditions
Why it happens in Hyderabad plants
Supply dips and phase loss are common on Hyderabad industrial feeders, especially during the evening peak and storms. Machines with phase-failure relays or drives with input phase monitoring refuse to start on an unbalanced supply, so a machine that won't start at 7 pm but starts the next morning often has nothing wrong with it.
Panel heat in April to June trips control power supplies, overload relays and drives that run close to their limits. A no-start that clears after the panel door has been left open for an hour points to cooling, not to a failed part.
During the monsoon, condensation in panels and junction boxes on machines left off overnight causes earth faults and tripped control circuits at the first start of the day. Dust from cement, stone and textile work does the same to sensors and limit switches, leaving a permissive that never makes.
04 / Fix it
Related services
The services that resolve this fault.
05 / Questions
Frequently asked questions
My machine is completely dead — where do you even start?+
The main supply is fine but nothing happens when I press start. Why?+
The machine starts and immediately stops. Is that the same fault?+
The machine won't start only after a power cut. Why?+
When should we stop troubleshooting and call someone?+