The two common electrical temperature sensors in industry: RTDs change resistance with temperature, thermocouples generate a small voltage.
01 / Definition
What a RTD and Thermocouple Temperature Sensors is
An RTD (resistance temperature detector) works on the fact that a metal's resistance rises with temperature. The industry standard Pt100 has 100 Ω at 0 °C and rises by roughly 0.39 Ω per degree. It is accurate and stable, and best for moderate temperatures. A thermocouple uses the Seebeck effect: two different metals joined at the hot end produce a small voltage depending on the temperature difference between that junction and the other end. Thermocouples are rugged, fast and reach far higher temperatures, which is why furnaces and moulding barrels use types K and J.
Most temperature errors come from the wiring and settings, not the sensor. A thermocouple must be extended with matching compensating cable of the right type and polarity, or the reading shifts. A two-wire RTD adds the cable's own resistance to the reading. And a controller or PLC input set for the wrong sensor type gives a steady, believable but wrong value.
Also called
02 / Anatomy
The parts that matter
The components a technician reaches for when this machine stops working.
Sensing element
A platinum RTD element or a thermocouple junction, usually inside a sheath with mineral insulation.
Thermowell
A protective tube in the process; it lets the sensor be removed without opening the line, but slows the response.
Head and terminal block
Where the sensor wires land, often with a head-mounted transmitter.
Extension or compensating cable
Copper for RTDs; matching thermocouple alloy cable for thermocouples.
Transmitter or input card
Converts the resistance or millivolts to temperature, applying linearisation and cold junction compensation.
03 / Applications
Where it is used
Ovens, furnaces, injection moulding barrels, heat exchangers, boilers, cold rooms, bearing and winding temperature on motors.
04 / Failure modes
How it fails
What actually goes wrong on Indian shop floors, and what each fault looks like to the operator.
FM_01
Open sensor
A broken element or wire; most inputs show a burnout value, far over or under range.
FM_02
Wrong compensating cable
Copper or the wrong thermocouple type in the run gives a steady error that changes with ambient temperature.
FM_03
Reversed thermocouple polarity
The reading moves the wrong way as the process heats.
FM_04
Moisture in the head or sheath
Leakage to earth gives low, erratic RTD readings.
FM_05
Wrong input type configured
A Pt100 read as a thermocouple, or type J as type K, gives a plausible but wrong value.
05 / Onsite
What our technician checks
A methodical path to root cause, not a scattergun of part swaps.
- 01Disconnect an RTD and measure its resistance; compare with the table value for the present temperature
- 02For a thermocouple, measure the millivolts and check them against the type's table
- 03Confirm the input or transmitter is configured for the right sensor type
- 04Check the extension cable type and polarity for thermocouples
- 05Use three- or four-wire RTD connections on long runs
- 06Check the sensor reaches the bottom of the thermowell
06 / Get it fixed
Related services
The MachineryFix services that cover this equipment.
07 / Questions
Frequently asked questions
Should I use an RTD or a thermocouple?+
RTDs for accuracy and stability up to moderate temperatures; thermocouples for high temperatures, fast response or rough duty.
Why does my temperature reading change when the panel door is open?+
The cold junction temperature has changed, typically because a thermocouple was extended with ordinary copper cable instead of compensating cable.
What does a reading of 'burnout' or maximum mean?+
The input sees an open circuit: the sensor or its wiring is broken.
What is a 3-wire RTD for?+
The third wire lets the instrument measure and cancel the resistance of the cable, which a 2-wire connection adds to the reading as an error.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007