VFD trips on overvoltage when stopping or slowing down?

Updated

Check these first

  1. 01Deceleration ramp too short for the load — A high-inertia load set to stop in a few seconds returns energy faster than the bus can hold it.
  2. 02Braking resistor open, missing or undersized — Where a resistor is fitted, a burnt-out element, a loose connection or a resistor too small for the duty leaves the energy nowhere to go.
  3. 03Braking chopper not enabled or failed — Some drives need the chopper enabled in parameters, and a failed chopper transistor leaves a healthy resistor unused.
  4. 04Overhauling load — A load that drives the motor even at steady speed, such as a lowering hoist or a downhill conveyor, regenerates continuously, not just when stopping.
  5. 05High supply voltage — A supply running at the top of its tolerance leaves less headroom on the DC bus, so a trip that is marginal at normal voltage appears at night or on light-load days.

01 / Overview

VFD Trips on Deceleration

When a drive slows a motor faster than the load would coast down, the motor acts as a generator and pushes energy back into the drive. That energy charges the DC bus capacitors, and if the voltage climbs past the drive's limit, it trips on overvoltage (OV, OU, or a brand-specific code). The trip protects the capacitors and power stage.

So an overvoltage trip that happens while stopping or slowing is rarely a fault in the drive. It is the load, usually a heavy flywheel, fan, centrifuge or conveyor with momentum, returning more energy than the drive can absorb in the time it has been given.

There are three ways out: give the drive more time (a longer deceleration ramp), give the energy somewhere to go (a braking resistor and chopper, or a regenerative unit), or let the drive manage it automatically (overvoltage control that stretches the ramp). Which is right depends on whether the process can tolerate a slower stop.

02 / Diagnosis

Likely causes

The handful of things that actually cause this — in the order we rule them out.

DX_01

Deceleration ramp too short for the load

A high-inertia load set to stop in a few seconds returns energy faster than the bus can hold it. The commonest cause, and the cheapest to fix if the process allows a slower stop.

DX_02

Braking resistor open, missing or undersized

Where a resistor is fitted, a burnt-out element, a loose connection or a resistor too small for the duty leaves the energy nowhere to go. Measure its resistance with the drive isolated.

DX_03

Braking chopper not enabled or failed

Some drives need the chopper enabled in parameters, and a failed chopper transistor leaves a healthy resistor unused.

DX_04

Overhauling load

A load that drives the motor even at steady speed, such as a lowering hoist or a downhill conveyor, regenerates continuously, not just when stopping.

DX_05

High supply voltage

A supply running at the top of its tolerance leaves less headroom on the DC bus, so a trip that is marginal at normal voltage appears at night or on light-load days.

02b / In order

Work through it in this order

Each check either clears a link in the chain or tells you where the fault is.

CheckIf it's OKIf it isn't
01Does the trip happen only while slowing down or stopping?Regeneration is the cause. Continue with the ramp and braking checks.A trip at constant speed points at an overhauling load or high supply voltage.
02Can the process accept a longer stop?Lengthen the deceleration ramp in steps until the trip stops, or enable the drive's overvoltage control. No hardware needed.The energy has to go somewhere: a braking resistor and chopper, or a regenerative unit for frequent or continuous braking.
03Is a braking resistor fitted and does it measure close to its rated resistance?Check that the chopper is enabled and the resistor is sized for the duty: one that runs very hot is undersized.Replace the resistor or repair its wiring, then confirm the chopper works.
04Does the trip continue with a long ramp and a working resistor?Check supply voltage and the drive's DC bus measurement; a drifting measurement circuit can trip early.Solved. Record the final ramp and braking settings in the parameter backup.

Stuck at one of these steps? Send the machine and what you've found so far.

WhatsApp the fault

03 / Onsite

What our technician checks

A methodical path to root cause — not a scattergun of part swaps.

  1. 01Confirm from the fault history that the trip happens while decelerating, not at constant speed
  2. 02Compare the deceleration time with how long the load takes to coast to a stop
  3. 03Check whether a braking resistor is fitted, its resistance and its connections
  4. 04Check the chopper and resistor parameters, and the drive's overvoltage control setting
  5. 05Measure the incoming supply voltage at different times of day

03b / Safety

What you can check, and what needs lockout

Safe for a plant electrician

  • Note whether the trip happens on every stop, only on emergency stops, or only with a full load.
  • Time how long the load takes to coast to a stop with the drive output off; the deceleration ramp cannot sensibly be much shorter without braking.
  • Feel for heat from outside the braking resistor enclosure after a stop, without touching the resistor itself.

Needs lockout or a controls engineer

  • Measuring the braking resistor, which must be done with the drive isolated and the DC bus discharged: the resistor sits at DC bus voltage.
  • Changing ramp, chopper and overvoltage control parameters, which affect how fast the machine stops and may affect safety functions.
  • Sizing a braking resistor or regenerative unit for the load's inertia and duty cycle.

03c / Local conditions

Why it happens in Hyderabad plants

Supply voltage on many Hyderabad industrial feeders rises at night and on Sundays when load is light. A deceleration trip that appears only on the night shift often has this cause.

Fans, centrifuges, flywheel presses and long conveyors in the city's process plants carry a lot of stored energy and are the usual sources of this trip.

04 / Fix it

Related services

The services that resolve this fault.

05 / Questions

Frequently asked questions

Will a longer deceleration time stop the overvoltage trip?+
Usually, yes. A longer ramp lets the load return its energy more slowly, so the DC bus does not overshoot. Lengthen it in steps until the trip stops. If the process needs a fast stop, a braking resistor is the answer instead.
Do we need a braking resistor?+
Only if the load must stop faster than it naturally can without tripping, or if it regenerates continuously, like a lowering hoist. For many fans and pumps a longer ramp or the drive's overvoltage control is enough.
Our braking resistor gets very hot. Is that normal?+
Resistors are designed to run hot, but one that overheats in normal use is undersized for the energy it absorbs, or the deceleration is much more frequent than it was sized for. It needs checking against the duty.
Why does the drive trip only on emergency stop?+
An emergency stop often uses a much faster ramp than a normal stop, so far more energy comes back at once. The braking arrangement has to be sized for that case.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007