F0035 on the ABB ACS355 is the “OUTP WIRING” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.
The drive found its power wiring connected the wrong way, such as the incoming supply landed on the motor terminals. Running it like that can destroy the drive.
- Code
- F0035
- Type
- Fault (stops the drive)
- Drive
- ABB ACS355
- Kind of fault
- Power wiring
01 / Causes
What causes F0035
- The input power and motor cables may be swapped: the supply connected to the drive's motor terminals.
- The fault can also be raised on a delta-grounded supply with a long motor cable of high capacitance.
02 / Checks
What to check for F0035
In the order ABB gives them.
- 01Check the input power connections are not connected to the drive's output.
- 02On a delta-grounded supply with a high-capacitance motor cable, the check can be turned off with parameter 3023 WIRING FAULT.
Also in the manual
- Over a fieldbus, the drive reports this fault as code FF95.
- ABB lists this as a programmable fault function: parameters 3023 decide whether the condition is reported and how the drive reacts.
03 / Clearing it
How to clear F0035
- Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
- If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
- Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.
Clear it once. If F0035 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How power wiring faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate the supply and confirm the incoming supply is on the drive's input terminals and the motor on its output terminals.
- 02Check any recent changes to the panel: a replaced drive or rewired terminal strip is the usual source.
05 / Repair
When F0035 means a repair
Correct the wiring before powering up again. A drive that was run with the supply on its output may need its power section checked.
If F0035 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007