0i-D SP9010: LOW VOLT INPUT POWER

SP9010 on the FANUC 0i-D is the “LOW VOLT INPUT POWER” alarm. An alarm stops operation until its cause is removed and it is cleared.

The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.

Code
SP9010
Type
Alarm (stops the machine)
Control
FANUC 0i-D, 0i Mate-D
Kind of fault
DC bus undervoltage

01 / Causes

What causes SP9010

  • The spindle amplifier detected a drop in input voltage.

02 / Checks

What to check for SP9010

In the order FANUC gives them.

  1. 01Check for low input voltage at the power supply.
  2. 02Check the power cable between the amplifiers.
  3. 03The spindle amplifier itself may be at fault.

Also in the manual

  • The spindle amplifier shows 10 (red LED).

03 / Clearing it

How to clear SP9010

  • Remove the cause, then press RESET on the MDI panel.
  • PW alarms need the power switched off and on again.
  • After an absolute position alarm such as DS0300, the alarm clears once the axis has returned to its reference position; after an encoder or motor change, the reference position must be set again.

Clear it once. If SP9010 comes straight back, stop resetting and find the cause: repeated resets on servo and spindle alarms can turn a cable or motor fault into a damaged amplifier.

04 / On site

How dc bus undervoltage faults are traced on site

General practice for this kind of alarm on CNC machines, in the order a technician works. Switch off and let the servo and spindle amplifiers' DC link discharge before touching terminals.

  1. 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
  2. 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
  3. 03Look for loose or heat-discoloured supply terminals.
  4. 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.

05 / Repair

When SP9010 means a repair

A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.

If SP9010 keeps returning, send the alarm number, a photo of the alarm screen and what the machine was doing when it stopped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on FANUC CNC systems, and they arrive knowing what to look for.

06 / More codes

Other 0i-D codes

Source

FANUC, FANUC Series 0i-MODEL D / 0i Mate-MODEL D Maintenance Manual, 03, B-64305EN/03, Appendix A.1 and A.3 (alarm lists); chapter 10 (troubleshooting).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of FANUC and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SP9010 won't clear? Get a technician who knows the 0i-D.

Send the code and what the machine was doing when it stopped. We'll match a technician who works on that control.