SP9112 on the FANUC 0i-D is the “CONV. EX. DISCHARGE POW.” alarm. An alarm stops operation until its cause is removed and it is cleared.
The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.
- Code
- SP9112
- Type
- Alarm (stops the machine)
- Control
- FANUC 0i-D, 0i Mate-D
- Kind of fault
- Braking resistor
01 / Causes
What causes SP9112
- Too much regenerative power in the power supply (power supply shows 8).
02 / Checks
What to check for SP9112
In the order FANUC gives them.
- 01Check the regenerative resistance.
- 02Check the motor selection.
- 03Replace the power supply.
Also in the manual
- The spindle amplifier shows b2 (red LED).
03 / Clearing it
How to clear SP9112
- Remove the cause, then press RESET on the MDI panel.
- PW alarms need the power switched off and on again.
- After an absolute position alarm such as DS0300, the alarm clears once the axis has returned to its reference position; after an encoder or motor change, the reference position must be set again.
Clear it once. If SP9112 comes straight back, stop resetting and find the cause: repeated resets on servo and spindle alarms can turn a cable or motor fault into a damaged amplifier.
04 / On site
How braking resistor faults are traced on site
General practice for this kind of alarm on CNC machines, in the order a technician works. Switch off and let the servo and spindle amplifiers' DC link discharge before touching terminals.
- 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
- 02Check the resistor's resistance against the drive manual's minimum.
- 03Check the resistor for heat damage and its wiring for loose terminals.
05 / Repair
When SP9112 means a repair
A burnt resistor or a shorted braking transistor in the drive has to be replaced.
If SP9112 keeps returning, send the alarm number, a photo of the alarm screen and what the machine was doing when it stopped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on FANUC CNC systems, and they arrive knowing what to look for.