Danfoss VLT Micro Drive FC 51 alarm codes

The VLT Micro Drive FC 51 is Danfoss' compact frequency converter for small motors, used on pumps, fans, conveyors and small machines.

The FC 51 numbers its warnings and alarms (Alarm 13 is over current, Alarm 14 an earth fault). Below is every code in Danfoss' FC 51 programming guide, with its description, the troubleshooting steps Danfoss gives and, where the guide names one, the parameter that controls it.

01 / Reading codes

Reading and clearing VLT Micro Drive FC 51 codes

A warning or alarm lights the matching LED on the front of the drive (warning yellow, alarm flashing red) and shows its code number on the display. Alarm, warning and extended status words can also be read over serial bus or fieldbus (16-90, 16-92, 16-94).

On an alarm the drive trips: the motor coasts and the alarm flashes until it is reset after the cause is removed. A trip lock, used where the fault could damage the drive or connected parts, can only be reset by switching the power off and on. A warning stays active while its cause is present; the motor may keep running.

  • Once the cause is removed, reset an alarm by pressing [Reset], through a digital input set to Reset, or over serial communication. After a manual reset, press [Reset], [Auto On] or [Hand On] to restart the motor.
  • An alarm that will not reset either still has its cause present, or is trip-locked: switch the mains off, switch it back on, then reset.
  • Alarms that are not trip-locked can also be reset automatically with 14-20 Reset Mode (automatic restart is then possible).

02 / Current and earth faults

Current and earth faults

CodeNameKind
Alarm 13Over currentAlarm · Overcurrent
Alarm 14Earth (ground) faultAlarm · Earth fault
Alarm 16Short circuitThere is a short circuit in the motor or the motor wiring. Switch off the power to the drive and repair the short circuit.Alarm · Output short circuit
Alarm 30Motor phase U missingMotor phase U between the drive and the motor is missing. Switch off the power to the drive and check motor phase U.Alarm · Output phase loss
Alarm 31Motor phase V missingMotor phase V between the drive and the motor is missing. Switch off the power to the drive and check motor phase V.Alarm · Output phase loss
Alarm 32Motor phase W missingMotor phase W between the drive and the motor is missing. Switch off the power to the drive and check motor phase W.Alarm · Output phase loss
Alarm 44Earth fault 2Alarm · Earth fault
Warning 59Current limitWarning · Overcurrent

03 / Voltage and supply

Voltage and supply

CodeNameKind
Alarm 4Mains phase lossAlarm · Input phase loss
Alarm 7DC overvoltageAlarm · DC bus overvoltage
Alarm 8DC under voltageAlarm · DC bus undervoltage
Alarm 25Brake resistor short circuitThe brake resistor, monitored during operation, has short-circuited; the brake function is disabled and the drive keeps running without it. Switch off the power to the drive and replace the brake resistor (see 2-15 Brake Check).Alarm · Braking resistor
Alarm 27Brake chopper faultThe brake transistor, monitored during operation, has short-circuited: the brake function is disabled, but substantial power still flows to the brake resistor even when it is inactive. Switch off the power to the drive and remove the brake resistor.Alarm · Braking resistor
Alarm 28Brake check failedThe brake resistor is not connected or not working. Alarm · Braking resistor
Alarm 63Mechanical brake lowThe actual motor current did not exceed the brake release current within the start delay time window. Alarm · Braking resistor

04 / Temperature and overload

Temperature and overload

CodeNameKind
Alarm 9Inverter overloadedAlarm · Drive overload
Alarm 10Motor ETR over temperatureAlarm · Motor overload or overtemperature
Alarm 11Motor thermistor over temperatureAlarm · Temperature sensor signal
Alarm 29Heat sink temperatureAlarm · Drive overtemperature

05 / Motor and load

Motor and load

CodeNameKind
Warning 12Torque limitWarning · Motor stall

06 / Signals and communication

Signals and communication

CodeNameKind
Alarm 2Live zero errorThe signal on terminal 53 or 60 is below 50% of the value set in 6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low Current or 6-22 Terminal 60 Low Current. Alarm · Analog signal loss
Alarm 17Control word timeoutAlarm · Communication loss
Error 84The connection between drive and LCP is lost Try refitting the LCP gently.Warning · Communication loss
Error 90Parameter database busyThe LCP and the RS-485 connection are trying to update parameters at the same time. Warning · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
Alarm 38Internal faultAlarm · Internal drive fault
Alarm 46Gate drive voltage faultThe supply on the power card is out of range. The switch-mode power supply (SMPS) on the power card generates three supplies: 24 V, 5 V and ±18 V. Check for a defective power card.Alarm · Internal drive fault
Alarm 47Control voltage faultAlarm · Internal drive fault
Alarm 51AMT check Unom and InomThe motor voltage, motor current and motor power settings are wrong. Check the settings in 1-20 to 1-25.Alarm · Motor identification
Alarm 52AMT low InomAlarm · Motor identification
Alarm 53AMT motor too bigAlarm · Motor identification
Alarm 54AMT motor too smallAlarm · Motor identification
Alarm 55AMT parameter out of rangeThe motor's parameter values are outside the acceptable range, so automatic motor tuning does not run. Alarm · Motor identification
Alarm 80Drive initialised to default valueThe parameter settings were initialised to default settings after a manual reset. Reset the unit to clear the alarm.Alarm · Setup
Error 85Button disabled See parameter group 0-4* LCP.Warning · Setup
Error 86Copy failAn error occurred while copying from the drive to the LCP, or the other way round. Warning · Parameter memory
Error 87LCP data invalidWhen copying from the LCP: the LCP holds erroneous data, or no data was uploaded to it. Warning · Parameter memory
Error 88LCP data not compatibleWhen copying from the LCP: the data is being moved between drives with major differences in software version. Warning · Parameter memory
Error 89Parameter read onlyAn attempt was made to write to a read-only parameter. Warning · Setup
Error 91Parameter value is not valid in this modeAn attempt was made to write an illegal value to a parameter. Warning · Setup
Error 92Parameter value exceeds the min/max limitsAn attempt was made to set a value outside the parameter's range. Warning · Setup

Related

Related pages

Source

Danfoss, VLT Micro Drive FC 51 Programming Guide, 12/2014, MG02C702, Chapter 6, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Danfoss and is not its authorised service partner.