The VLT Micro Drive FC 51 is Danfoss' compact frequency converter for small motors, used on pumps, fans, conveyors and small machines.
The FC 51 numbers its warnings and alarms (Alarm 13 is over current, Alarm 14 an earth fault). Below is every code in Danfoss' FC 51 programming guide, with its description, the troubleshooting steps Danfoss gives and, where the guide names one, the parameter that controls it.
01 / Reading codes
Reading and clearing VLT Micro Drive FC 51 codes
A warning or alarm lights the matching LED on the front of the drive (warning yellow, alarm flashing red) and shows its code number on the display. Alarm, warning and extended status words can also be read over serial bus or fieldbus (16-90, 16-92, 16-94).
On an alarm the drive trips: the motor coasts and the alarm flashes until it is reset after the cause is removed. A trip lock, used where the fault could damage the drive or connected parts, can only be reset by switching the power off and on. A warning stays active while its cause is present; the motor may keep running.
- Once the cause is removed, reset an alarm by pressing [Reset], through a digital input set to Reset, or over serial communication. After a manual reset, press [Reset], [Auto On] or [Hand On] to restart the motor.
- An alarm that will not reset either still has its cause present, or is trip-locked: switch the mains off, switch it back on, then reset.
- Alarms that are not trip-locked can also be reset automatically with 14-20 Reset Mode (automatic restart is then possible).
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| Alarm 13 | Over current | Alarm · Overcurrent |
| Alarm 14 | Earth (ground) fault | Alarm · Earth fault |
| Alarm 16 | Short circuitThere is a short circuit in the motor or the motor wiring. Switch off the power to the drive and repair the short circuit. | Alarm · Output short circuit |
| Alarm 30 | Motor phase U missingMotor phase U between the drive and the motor is missing. Switch off the power to the drive and check motor phase U. | Alarm · Output phase loss |
| Alarm 31 | Motor phase V missingMotor phase V between the drive and the motor is missing. Switch off the power to the drive and check motor phase V. | Alarm · Output phase loss |
| Alarm 32 | Motor phase W missingMotor phase W between the drive and the motor is missing. Switch off the power to the drive and check motor phase W. | Alarm · Output phase loss |
| Alarm 44 | Earth fault 2 | Alarm · Earth fault |
| Warning 59 | Current limit | Warning · Overcurrent |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| Alarm 4 | Mains phase loss | Alarm · Input phase loss |
| Alarm 7 | DC overvoltage | Alarm · DC bus overvoltage |
| Alarm 8 | DC under voltage | Alarm · DC bus undervoltage |
| Alarm 25 | Brake resistor short circuitThe brake resistor, monitored during operation, has short-circuited; the brake function is disabled and the drive keeps running without it. Switch off the power to the drive and replace the brake resistor (see 2-15 Brake Check). | Alarm · Braking resistor |
| Alarm 27 | Brake chopper faultThe brake transistor, monitored during operation, has short-circuited: the brake function is disabled, but substantial power still flows to the brake resistor even when it is inactive. Switch off the power to the drive and remove the brake resistor. | Alarm · Braking resistor |
| Alarm 28 | Brake check failedThe brake resistor is not connected or not working. | Alarm · Braking resistor |
| Alarm 63 | Mechanical brake lowThe actual motor current did not exceed the brake release current within the start delay time window. | Alarm · Braking resistor |
04 / Temperature and overload
Temperature and overload
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| Warning 12 | Torque limit | Warning · Motor stall |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| Alarm 2 | Live zero errorThe signal on terminal 53 or 60 is below 50% of the value set in 6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low Current or 6-22 Terminal 60 Low Current. | Alarm · Analog signal loss |
| Alarm 17 | Control word timeout | Alarm · Communication loss |
| Error 84 | The connection between drive and LCP is lost Try refitting the LCP gently. | Warning · Communication loss |
| Error 90 | Parameter database busyThe LCP and the RS-485 connection are trying to update parameters at the same time. | Warning · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| Alarm 38 | Internal fault | Alarm · Internal drive fault |
| Alarm 46 | Gate drive voltage faultThe supply on the power card is out of range. The switch-mode power supply (SMPS) on the power card generates three supplies: 24 V, 5 V and ±18 V. Check for a defective power card. | Alarm · Internal drive fault |
| Alarm 47 | Control voltage fault | Alarm · Internal drive fault |
| Alarm 51 | AMT check Unom and InomThe motor voltage, motor current and motor power settings are wrong. Check the settings in 1-20 to 1-25. | Alarm · Motor identification |
| Alarm 52 | AMT low Inom | Alarm · Motor identification |
| Alarm 53 | AMT motor too big | Alarm · Motor identification |
| Alarm 54 | AMT motor too small | Alarm · Motor identification |
| Alarm 55 | AMT parameter out of rangeThe motor's parameter values are outside the acceptable range, so automatic motor tuning does not run. | Alarm · Motor identification |
| Alarm 80 | Drive initialised to default valueThe parameter settings were initialised to default settings after a manual reset. Reset the unit to clear the alarm. | Alarm · Setup |
| Error 85 | Button disabled See parameter group 0-4* LCP. | Warning · Setup |
| Error 86 | Copy failAn error occurred while copying from the drive to the LCP, or the other way round. | Warning · Parameter memory |
| Error 87 | LCP data invalidWhen copying from the LCP: the LCP holds erroneous data, or no data was uploaded to it. | Warning · Parameter memory |
| Error 88 | LCP data not compatibleWhen copying from the LCP: the data is being moved between drives with major differences in software version. | Warning · Parameter memory |
| Error 89 | Parameter read onlyAn attempt was made to write to a read-only parameter. | Warning · Setup |
| Error 91 | Parameter value is not valid in this modeAn attempt was made to write an illegal value to a parameter. | Warning · Setup |
| Error 92 | Parameter value exceeds the min/max limitsAn attempt was made to set a value outside the parameter's range. | Warning · Setup |
Related
Related pages
Source
Danfoss, VLT Micro Drive FC 51 Programming Guide, 12/2014, MG02C702, Chapter 6, Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Danfoss and is not its authorised service partner.