VLT Micro Drive FC 51 Alarm 4: Mains phase loss

Alarm 4 on the Danfoss VLT Micro Drive FC 51 is the “Mains phase loss” alarm. On an alarm the drive trips: the motor coasts and the alarm flashes until it is reset after the cause is removed. A trip lock, used where the fault could damage the drive or connected parts, can only be reset by switching the power off and on.

One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.

Code
Alarm 4
Type
Alarm (stops the drive)
Drive
Danfoss VLT Micro Drive FC 51
Kind of fault
Input phase loss

01 / Causes

What causes Alarm 4

  • A phase is missing on the supply side.
  • The supply voltage imbalance is too high.
  • A fault in the drive's input rectifier.

02 / Checks

What to check for Alarm 4

In the order Danfoss gives them.

  1. 01Check the supply voltage and the supply currents to the drive.
  2. 02The fault may come from mains distortion; a Danfoss line filter may cure it.

Also in the manual

  • Danfoss marks this code as both warning and alarm: a warning comes before the alarm, or a parameter selects which one is shown.
  • Table 6.1 marks its warning, alarm and trip lock as depending on 14-12, the parameter it references.

03 / Clearing it

How to clear Alarm 4

  • Once the cause is removed, reset an alarm by pressing [Reset], through a digital input set to Reset, or over serial communication. After a manual reset, press [Reset], [Auto On] or [Hand On] to restart the motor.
  • An alarm that will not reset either still has its cause present, or is trip-locked: switch the mains off, switch it back on, then reset.
  • Alarms that are not trip-locked can also be reset automatically with 14-20 Reset Mode (automatic restart is then possible).

Clear it once. If Alarm 4 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How input phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure all three phases at the drive input terminals with the drive running under load.
  2. 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
  3. 03Tighten and inspect supply terminals for heat damage.

05 / Repair

When Alarm 4 means a repair

If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.

If Alarm 4 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Danfoss drives, and they arrive knowing what to look for.

06 / Other drives

Input phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F20 DC ripple too high
Siemens SINAMICS G120F30011 Line phase failure
Siemens SINAMICS V90F30011 Line phase failure in main circuit
Siemens MICROMASTER 440F0020 Line supply phase missing
ABB ACS355F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS
Delta VFD-EPHL Phase loss
Delta C2000OrP Phase loss protection
Delta ASDA-B2AL022 Main circuit power lack phase
Schneider Electric Altivar ATV320PHF Input phase loss error
INVT Goodrive20 (GD20)SPI Phase loss on input side
Yaskawa V1000PF Input Phase Loss
Yaskawa A1000PF Input Phase Loss
Yaskawa GA500PF Input Phase Loss
Siemens MICROMASTER 430F0020 Line supply phase missing
INVT Goodrive200A (GD200A)SPI Phase loss on input side
Mitsubishi Electric FR-D700E.ILF Input phase loss

07 / More codes

Other VLT Micro Drive FC 51 codes

Source

Danfoss, VLT Micro Drive FC 51 Programming Guide, 12/2014, MG02C702, Chapter 6, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Danfoss and is not its authorised service partner.