Alarm 11 on the Danfoss VLT Micro Drive FC 51 is the “Motor thermistor over temperature” alarm. On an alarm the drive trips: the motor coasts and the alarm flashes until it is reset after the cause is removed. A trip lock, used where the fault could damage the drive or connected parts, can only be reset by switching the power off and on.
The drive has lost the signal from a temperature sensor: the heat sink sensor inside the drive, or the motor's own sensor. Without it the drive cannot protect itself or the motor.
- Code
- Alarm 11
- Type
- Alarm (stops the drive)
- Drive
- Danfoss VLT Micro Drive FC 51
- Kind of fault
- Temperature sensor signal
01 / Causes
What causes Alarm 11
- The motor thermistor reports overtemperature, or the thermistor may be disconnected.
02 / Checks
What to check for Alarm 11
In the order Danfoss gives them.
- 01Check for motor overheating.
- 02Check whether the motor is mechanically overloaded.
Also in the manual
- Danfoss marks this code as both warning and alarm: a warning comes before the alarm, or a parameter selects which one is shown.
- 1-90 Motor Thermal Protection selects whether the drive gives a warning or an alarm.
03 / Clearing it
How to clear Alarm 11
- Once the cause is removed, reset an alarm by pressing [Reset], through a digital input set to Reset, or over serial communication. After a manual reset, press [Reset], [Auto On] or [Hand On] to restart the motor.
- An alarm that will not reset either still has its cause present, or is trip-locked: switch the mains off, switch it back on, then reset.
- Alarms that are not trip-locked can also be reset automatically with 14-20 Reset Mode (automatic restart is then possible).
Clear it once. If Alarm 11 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How temperature sensor signal faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01For a motor sensor, check its wiring to the drive and measure the sensor's resistance.
- 02For the drive's own heat sink sensor, there is nothing to adjust from outside.
05 / Repair
When Alarm 11 means a repair
A lost heat sink sensor signal inside the drive needs the unit opened and repaired.
If Alarm 11 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Danfoss drives, and they arrive knowing what to look for.
06 / Other drives
Temperature sensor signal: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F12 Inverter temperature signal lost · A507 Inverter temperature signal lost |
| Siemens SINAMICS G120 | F07016 Motor temperature sensor fault · A03520 Temperature sensor fault · A07015 Motor temperature sensor alarm · A30920 Temperature sensor fault |
| Siemens MICROMASTER 440 | F0012 No inverter temperature signal · F0015 No motor temperature signal |
| ABB ACS355 | F0018 THERM FAIL |
| Delta VFD-E | cF3.4 IGBT overheat (temperature sensor) · cF3.5 Power board overheat (temperature sensor) |
| Delta C2000 | tH1o IGBT temperature detection failure · tH2o Capacitor hardware error |
| Schneider Electric Altivar ATV320 | INFB Internal error 11 (Temperature) · PTFL DI6=PTC probe error |
| Yaskawa A1000 | THo Thermistor Disconnect |
| Siemens MICROMASTER 430 | F0012 No inverter temperature signal · F0015 No motor temperature signal |
| Mitsubishi Electric FR-D700 | E.PTC PTC thermistor operation |
07 / More codes
Other VLT Micro Drive FC 51 codes
Source
Danfoss, VLT Micro Drive FC 51 Programming Guide, 12/2014, MG02C702, Chapter 6, Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Danfoss and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007