Alarm 29 on the Danfoss VLT Micro Drive FC 51 is the “Heat sink temperature” alarm. On an alarm the drive trips: the motor coasts and the alarm flashes until it is reset after the cause is removed. A trip lock, used where the fault could damage the drive or connected parts, can only be reset by switching the power off and on.

The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.

Code
Alarm 29
Type
Alarm (stops the drive)
Drive
Danfoss VLT Micro Drive FC 51
Kind of fault
Drive overtemperature

01 / Causes

What causes Alarm 29

  • The heat sink's maximum temperature has been exceeded. The fault does not reset until the heat sink cools below a set temperature; the trip and reset points depend on the drive's power size.

02 / Checks

What to check for Alarm 29

In the order Danfoss gives them.

  1. 01Check whether the ambient temperature is too high.
  2. 02Check whether the motor cables are too long.
  3. 03Check the airflow clearance above and below the drive.
  4. 04Check the airflow around the drive is not blocked.
  5. 05Check for a damaged heat sink fan.
  6. 06Check for a dirty heat sink.

Also in the manual

  • Trip lock: the alarm can only be reset after switching the mains supply off and on.
  • Table 6.1 names this code Power board over temp.

03 / Clearing it

How to clear Alarm 29

  • Once the cause is removed, reset an alarm by pressing [Reset], through a digital input set to Reset, or over serial communication. After a manual reset, press [Reset], [Auto On] or [Hand On] to restart the motor.
  • An alarm that will not reset either still has its cause present, or is trip-locked: switch the mains off, switch it back on, then reset.
  • Alarms that are not trip-locked can also be reset automatically with 14-20 Reset Mode (automatic restart is then possible).

Clear it once. If Alarm 29 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
  2. 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
  3. 03Measure the temperature inside the panel and check the panel fans and filters.
  4. 04Check the switching frequency against the factory setting and the load current against the drive's rating.

05 / Repair

When Alarm 29 means a repair

A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.

If Alarm 29 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Danfoss drives, and they arrive knowing what to look for.

06 / Other drives

Drive overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning
Siemens SINAMICS G120F30004 Inverter overtemperature · F30035 Overtemperature, intake air · F30036 Overtemperature, inside area · F30037 Rectifier overtemperature · A05000 Power Module overtemperature · A05001 Power Module overtemperature
Siemens SINAMICS V90F30004 Drive heat sink overtemperature · F30036 Internal overtemperature · A1009 Control module overtemperature · A5000 Drive heat sink overtemperature
Siemens MICROMASTER 440F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high
Allen-Bradley PowerFlex 525F008 Heatsink OvrTmp · F009 CC OvrTmp
ABB ACS355F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP
Delta VFD-EoH1 IGBT overheat · oH2 Power board overheat
Delta C2000oH1 IGBT overheating · oH2 Heatsink overheating
Delta ASDA-B2AL016 IGBT overheat
Hitachi WJ200E21 Inverter thermal trip
Schneider Electric Altivar ATV320OHF Drive overheating error · TJF IGBT overheating
INVT Goodrive20 (GD20)OH1 Rectifier module overheat · OH2 Inverter module overheat
Yaskawa V1000oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat)
Yaskawa A1000oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) · oH2 Heatsink Overheat Warning
Yaskawa GA500oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B)
Siemens MICROMASTER 420F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens MICROMASTER 430F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens SINAMICS G110F0004 Inverter over temperature
INVT Goodrive200A (GD200A)OH1 Rectifier module overheating · OH2 Inverter module overheat
Mitsubishi Electric FR-D700E.FIN Heatsink overheat

07 / More codes

Other VLT Micro Drive FC 51 codes

Source

Danfoss, VLT Micro Drive FC 51 Programming Guide, 12/2014, MG02C702, Chapter 6, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Danfoss and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

Alarm 29 won't clear? Get a technician who knows the VLT Micro Drive FC 51.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.