The SINAMICS G110 is Siemens' compact, single-phase-supply inverter for small motors, used on small conveyors, pumps, fans and packaging machines. It shares its fault numbering with the MICROMASTER 4 range, with extra codes for copying parameters through the BOP.
A G110 fault code starts with F and a four-digit number (F0001); alarms start with A (A0501). Below is every fault and alarm in Siemens' G110 parameter list, with the causes and checks Siemens gives.
01 / Reading codes
Reading and clearing SINAMICS G110 codes
The BOP shows a fault as F followed by four digits, for example F0001, and an alarm as A followed by four digits, for example A0501.
On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset. An alarm is a warning shown while its condition lasts; the inverter keeps running.
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP, or use digital input 2 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none).
- Alarm codes are stored in r2110 (A0503 is stored as 503). An alarm shows as long as its condition lasts and disappears when the condition ends; alarms cannot be switched off.
02 / Current and earth faults
Current and earth faults
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| F0002 | Overvoltage | Fault · DC bus overvoltage |
| F0003 | Undervoltage | Fault · DC bus undervoltage |
| A0502 | Overvoltage limitThe overvoltage limit is reached; this can happen during ramp-down when the Vdc controller is disabled (P1240 = 0). If the warning stays on, check the drive's input voltage. | Alarm · DC bus overvoltage |
| A0503 | Undervoltage limit | Alarm · DC bus undervoltage |
| A0910 | Vdc-max controller de-activated | Alarm · DC bus overvoltage |
| A0911 | Vdc-max controller active | Alarm · DC bus overvoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| F0004 | Inverter over temperature | Fault · Drive overtemperature |
| F0005 | Inverter I2t | Fault · Drive overload |
| F0011 | Motor over temperature I2t | Fault · Motor overload or overtemperature |
| A0505 | Inverter I2tThe warning level is exceeded; the current is reduced if set up to do so (P0610 = 1). Check the duty cycle is within the specified limits. | Alarm · Drive overload |
| A0511 | Motor over temperature I2t | Alarm · Motor overload or overtemperature |
05 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| F0072 | USS setpoint faultNo setpoint values arrived over USS during the telegram off time. Check the USS master. | Fault · Communication loss |
| F0085 | External faultAn external fault was triggered through the terminal inputs. Disable the terminal input that triggers the fault. | Fault · External fault |
06 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| F0051 | Parameter EEPROM fault | Fault · Parameter memory |
| F0052 | Power stack faultA read failure of the power stack information, or invalid data. Replace the drive. | Fault · Internal drive fault |
| F0055 | BOP-EEPROM fault | Fault · Parameter memory |
| F0056 | BOP not fittedParameter cloning was started without a BOP fitted. Fit the BOP and try again. | Fault · Setup |
| F0057 | BOP fault | Fault · Setup |
| F0058 | BOP contents incompatibleParameter cloning was started with a BOP whose contents came from another type of drive. Download to the BOP from this type of drive. | Fault · Setup |
| F0060 | Asic timeout | Fault · Internal drive fault |
| F0100 | Watchdog reset | Fault · Internal drive fault |
| F0101 | Stack overflowA software error or processor failure. Run the self-test routines. | Fault · Internal drive fault |
| A0920 | ADC parameters not set properlyADC parameters are set to identical values, which gives illogical results. Check P0757, P0758, P0759 and P0760. | Alarm · Setup |
| A0923 | Both JOG left and JOG right are requestedJOG right and JOG left are both requested, which freezes the ramp-function generator output at its present value. Do not press JOG right and JOG left at the same time. | Alarm · Setup |
Related
Related pages
Source
Siemens, SINAMICS G110 Parameter List, Issue 11/2004, 6SL3298-0BA11-0BP0, Section 2, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.