The MICROMASTER 420 (MM420) is the general-purpose inverter of Siemens' MICROMASTER 4 range, the smaller sibling of the MM440. Siemens' current drives are the SINAMICS range, but MM420 drives still run fans, pumps and conveyors in a great many Indian plants.
An MM420 fault code starts with F and a four-digit number (F0001); alarms start with A (A0501). Below is every fault and alarm in Siemens' MM420 parameter list, with the causes and checks Siemens gives.
01 / Reading codes
Reading and clearing MICROMASTER 420 codes
The BOP or AOP shows a fault as F followed by four digits, for example F0001, and an alarm as A followed by four digits, for example A0501.
On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset. An alarm is a warning shown while the inverter keeps running; some alarms reduce the pulse or output frequency to protect the inverter.
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none), the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
02 / Current and earth faults
Current and earth faults
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| F0002 | Overvoltage | Fault · DC bus overvoltage |
| F0003 | Undervoltage | Fault · DC bus undervoltage |
| A0502 | Overvoltage limit value | Alarm · DC bus overvoltage |
| A0503 | Undervoltage limit value | Alarm · DC bus undervoltage |
| A0910 | Vdc-max controller disabled/switched-out | Alarm · DC bus overvoltage |
| A0911 | Vdc-max controller active | Alarm · DC bus overvoltage |
| A0912 | Vdc-min controller active | Alarm · DC bus undervoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| F0004 | Inverter overtemperature | Fault · Drive overtemperature |
| F0005 | Inverter I2t | Fault · Drive overload |
| F0011 | Motor overtemperature I2t | Fault · Motor overload or overtemperature |
| A0504 | Inverter overtemperature | Alarm · Drive overtemperature |
| A0505 | Inverter I2t | Alarm · Drive overload |
| A0511 | Motor overtemperature I2t | Alarm · Motor overload or overtemperature |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| F0221 | PID feedback below the minimum value | Fault · Process limit |
| F0222 | PID feedback above maximum value | Fault · Process limit |
| F0422 | No load applied to inverterNo load is connected to the inverter, so some functions may not work as they do under normal load. | Fault · Load monitoring |
| A0922 | No load at the inverter | Alarm · Load monitoring |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| F0070 | CB setpoint fault | Fault · Communication loss |
| F0071 | USS (BOP link) setpoint faultNo setpoint arrived over USS (BOP link) within the telegram off time. Check the USS master. | Fault · Communication loss |
| F0072 | USS (COMM link) setpoint faultNo setpoints arrived over USS (COMM link) within the telegram off time. Check the USS master. | Fault · Communication loss |
| F0080 | ADC input signal lost | Fault · Analog signal loss |
| F0085 | External faultAn external fault was commanded through a terminal input. Remove the terminal input that triggers the fault. | Fault · External fault |
| A0700 | CB alarm 1The parameter or configuration settings from the PROFIBUS master are invalid. Correct the PROFIBUS configuration. | Alarm · Communication loss |
| A0701 | CB alarm 2Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0702 | CB alarm 3The link to PROFIBUS is interrupted. Check the connector, the cable and the PROFIBUS master. | Alarm · Communication loss |
| A0703 | CB alarm 4No setpoints, or invalid setpoints (control word = 0), are arriving from the PROFIBUS master. Check the setpoints from the PROFIBUS master, and switch the SIMATIC CPU to RUN. | Alarm · Communication loss |
| A0704 | CB alarm 5At least one configured internode transmitter is not yet active, or has failed. Activate the internode transmitter. | Alarm · Communication loss |
| A0705 | CB alarm 6No actual values are arriving from the inverter. The fault is in the inverter. | Alarm · Communication loss |
| A0706 | CB alarm 7A software error on the PROFIBUS-DP communication board. The fault is on the PROFIBUS-DP board; see its diagnostic parameter for details. | Alarm · Communication loss |
| A0707 | CB alarm 8Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0708 | CB alarm 9Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0709 | CB alarm 10Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0710 | CB communications errorCommunication with the CB (communications module) is lost. Check the CB hardware. | Alarm · Communication loss |
| A0711 | CB communications errorThe CB (communications module) reports a communications error. Check the CB parameters. | Alarm · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| F0035 | Restart after nThe automatic restart failed after the number of attempts set in P1211. | Fault · Automatic restart limit |
| F0041 | Failure, motor data identification | Fault · Motor identification |
| F0051 | Parameter EEPROM fault | Fault · Parameter memory |
| F0052 | Power stack faultA read error of the power data, or invalid power module data. Replace the drive. | Fault · Internal drive fault |
| F0060 | Asic time slice overflowAn internal communications failure. If the fault keeps returning, replace the inverter and contact Siemens customer service. | Fault · Internal drive fault |
| F0101 | Stack overflowA software error or processor failure. Run the self-test routines. | Fault · Internal drive fault |
| F0450 | Failure BIST tests | Fault · Internal drive fault |
| A0541 | Motor data identification routine activeMotor data identification (P1910) is selected and running. | Alarm · Motor identification |
| A0571 | Auto restart after fault present | Alarm · Automatic restart limit |
| A0600 | RTOS data loss alarm | Alarm · Internal drive fault |
| A0920 | ADC parameters not correctly set | Alarm · Setup |
| A0921 | DAC parameters not set properly | Alarm · Setup |
| A0923 | JOG counter-clockwise as well as JOG clockwise are requestedJOG clockwise and JOG counter-clockwise (P1055/P1056) are both requested, so the ramp-function generator output is frozen at its present value. | Alarm · Setup |
Related
Related pages
Source
Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007