Siemens MICROMASTER 420 fault codes

The MICROMASTER 420 (MM420) is the general-purpose inverter of Siemens' MICROMASTER 4 range, the smaller sibling of the MM440. Siemens' current drives are the SINAMICS range, but MM420 drives still run fans, pumps and conveyors in a great many Indian plants.

An MM420 fault code starts with F and a four-digit number (F0001); alarms start with A (A0501). Below is every fault and alarm in Siemens' MM420 parameter list, with the causes and checks Siemens gives.

01 / Reading codes

Reading and clearing MICROMASTER 420 codes

The BOP or AOP shows a fault as F followed by four digits, for example F0001, and an alarm as A followed by four digits, for example A0501.

On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset. An alarm is a warning shown while the inverter keeps running; some alarms reduce the pulse or output frequency to protect the inverter.

  • Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none), the time of the fault in r0948 and the number of stored faults in P0952.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

02 / Current and earth faults

Current and earth faults

CodeNameKind
F0001OvercurrentFault · Overcurrent
A0501Current limit valueAlarm · Overcurrent

03 / Voltage and supply

Voltage and supply

CodeNameKind
F0002OvervoltageFault · DC bus overvoltage
F0003UndervoltageFault · DC bus undervoltage
A0502Overvoltage limit valueAlarm · DC bus overvoltage
A0503Undervoltage limit valueAlarm · DC bus undervoltage
A0910Vdc-max controller disabled/switched-outAlarm · DC bus overvoltage
A0911Vdc-max controller activeAlarm · DC bus overvoltage
A0912Vdc-min controller activeAlarm · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
F0004Inverter overtemperatureFault · Drive overtemperature
F0005Inverter I2tFault · Drive overload
F0011Motor overtemperature I2tFault · Motor overload or overtemperature
A0504Inverter overtemperatureAlarm · Drive overtemperature
A0505Inverter I2tAlarm · Drive overload
A0511Motor overtemperature I2tAlarm · Motor overload or overtemperature

05 / Motor and load

Motor and load

CodeNameKind
F0221PID feedback below the minimum valueFault · Process limit
F0222PID feedback above maximum valueFault · Process limit
F0422No load applied to inverterNo load is connected to the inverter, so some functions may not work as they do under normal load. Fault · Load monitoring
A0922No load at the inverterAlarm · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
F0070CB setpoint faultFault · Communication loss
F0071USS (BOP link) setpoint faultNo setpoint arrived over USS (BOP link) within the telegram off time. Check the USS master.Fault · Communication loss
F0072USS (COMM link) setpoint faultNo setpoints arrived over USS (COMM link) within the telegram off time. Check the USS master.Fault · Communication loss
F0080ADC input signal lostFault · Analog signal loss
F0085External faultAn external fault was commanded through a terminal input. Remove the terminal input that triggers the fault.Fault · External fault
A0700CB alarm 1The parameter or configuration settings from the PROFIBUS master are invalid. Correct the PROFIBUS configuration.Alarm · Communication loss
A0701CB alarm 2Specific to the communications module (CB). See the CB user manual.Alarm · Communication loss
A0702CB alarm 3The link to PROFIBUS is interrupted. Check the connector, the cable and the PROFIBUS master.Alarm · Communication loss
A0703CB alarm 4No setpoints, or invalid setpoints (control word = 0), are arriving from the PROFIBUS master. Check the setpoints from the PROFIBUS master, and switch the SIMATIC CPU to RUN.Alarm · Communication loss
A0704CB alarm 5At least one configured internode transmitter is not yet active, or has failed. Activate the internode transmitter.Alarm · Communication loss
A0705CB alarm 6No actual values are arriving from the inverter. The fault is in the inverter.Alarm · Communication loss
A0706CB alarm 7A software error on the PROFIBUS-DP communication board. The fault is on the PROFIBUS-DP board; see its diagnostic parameter for details.Alarm · Communication loss
A0707CB alarm 8Specific to the communications module (CB). See the CB user manual.Alarm · Communication loss
A0708CB alarm 9Specific to the communications module (CB). See the CB user manual.Alarm · Communication loss
A0709CB alarm 10Specific to the communications module (CB). See the CB user manual.Alarm · Communication loss
A0710CB communications errorCommunication with the CB (communications module) is lost. Check the CB hardware.Alarm · Communication loss
A0711CB communications errorThe CB (communications module) reports a communications error. Check the CB parameters.Alarm · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
F0035Restart after nThe automatic restart failed after the number of attempts set in P1211. Fault · Automatic restart limit
F0041Failure, motor data identificationFault · Motor identification
F0051Parameter EEPROM faultFault · Parameter memory
F0052Power stack faultA read error of the power data, or invalid power module data. Replace the drive.Fault · Internal drive fault
F0060Asic time slice overflowAn internal communications failure. If the fault keeps returning, replace the inverter and contact Siemens customer service.Fault · Internal drive fault
F0101Stack overflowA software error or processor failure. Run the self-test routines.Fault · Internal drive fault
F0450Failure BIST testsFault · Internal drive fault
A0541Motor data identification routine activeMotor data identification (P1910) is selected and running. Alarm · Motor identification
A0571Auto restart after fault presentAlarm · Automatic restart limit
A0600RTOS data loss alarmAlarm · Internal drive fault
A0920ADC parameters not correctly setAlarm · Setup
A0921DAC parameters not set properlyAlarm · Setup
A0923JOG counter-clockwise as well as JOG clockwise are requestedJOG clockwise and JOG counter-clockwise (P1055/P1056) are both requested, so the ramp-function generator output is frozen at its present value. Alarm · Setup

Related

Related pages

Source

Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.