The MICROMASTER 430 (MM430) is the pump and fan inverter of Siemens' MICROMASTER 4 range. Its parameter list includes load torque monitoring that catches a broken belt or a dry-running pump, so its codes turn up in water, HVAC and process plants across India.
An MM430 fault code starts with F and a four-digit number (F0001); alarms start with A (A0501). Below is every fault and alarm in Siemens' MM430 parameter list, with the causes and checks Siemens gives.
01 / Reading codes
Reading and clearing MICROMASTER 430 codes
The BOP-2 or AOP shows a fault as F followed by four digits, for example F0001, and an alarm as A followed by four digits, for example A0501.
On a fault the inverter switches off and shows the fault code; most MM430 faults use Siemens' reaction STOP II (F0012 uses STOP I). It will not run until the fault is reset. An alarm is a warning shown while the inverter keeps running; some alarms reduce the pulse or output frequency to protect the inverter.
- Reset a fault by switching the power off and on, by pressing the Fn key on the BOP-2, or through the fault acknowledge sources P2103 and P2104.
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949; P0952 clears the complete fault memory.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| F0001 | Overcurrent | Fault · Overcurrent |
| F0021 | Ground fault | Fault · Earth fault |
| F0022 | Hardware monitoring active | Fault · Output short circuit |
| F0023 | Output fault | Fault · Output phase loss |
| A0501 | Current limit value | Alarm · Overcurrent |
| A0523 | Output faultAn output cable is not connected. The alarm can be suppressed. | Alarm · Output phase loss |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| F0002 | Overvoltage | Fault · DC bus overvoltage |
| F0003 | Undervoltage | Fault · DC bus undervoltage |
| F0020 | Line supply phase missingOne of the three input phases is missing while the pulses are enabled and a load is present. Check the power connections. | Fault · Input phase loss |
| A0502 | Overvoltage limit value | Alarm · DC bus overvoltage |
| A0503 | Undervoltage limit value | Alarm · DC bus undervoltage |
| A0910 | Vdc-max controller disabled/switched-out | Alarm · DC bus overvoltage |
| A0911 | Vdc-max controller active | Alarm · DC bus overvoltage |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| F0004 | Inverter overtemperature | Fault · Drive overtemperature |
| F0005 | Inverter I2t | Fault · Drive overload |
| F0011 | Motor overtemperature | Fault · Motor overload or overtemperature |
| F0012 | No inverter temperature signalA broken wire to the inverter's heatsink temperature sensor. Replace the inverter. | Fault · Temperature sensor signal |
| F0015 | No motor temperature signalThe motor temperature sensor is short-circuited or open-circuited. | Fault · Temperature sensor signal |
| A0504 | Inverter overtemperature | Alarm · Drive overtemperature |
| A0505 | Inverter I2t | Alarm · Drive overload |
| A0506 | Inverter load duty cycleThe difference between the heatsink and IGBT temperatures exceeds the alarm limits. Make sure the load duty cycle and load surges are within the permitted limits. | Alarm · Drive overload |
| A0511 | Motor overtemperature | Alarm · Motor overload or overtemperature |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| F0221 | PID feedback below the minimum value | Fault · Process limit |
| F0222 | PID feedback above maximum value | Fault · Process limit |
| F0422 | No load applied to inverterNo load is connected to the inverter, so some functions may not work as they do under normal load. | Fault · Load monitoring |
| F0452 | Load torque fault detected | Fault · Load monitoring |
| A0922 | No load at the inverter | Alarm · Load monitoring |
| A0952 | Load fault detected | Alarm · Load monitoring |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| F0070 | CB setpoint fault | Fault · Communication loss |
| F0071 | USS (BOP link) setpoint faultNo setpoint arrived over USS (BOP link) within the telegram off time. Check the USS master. | Fault · Communication loss |
| F0072 | USS (COMM link) setpoint faultNo setpoints arrived over USS (COMM link) within the telegram off time. Check the USS master. | Fault · Communication loss |
| F0080 | ADC input signal lost | Fault · Analog signal loss |
| F0085 | External faultAn external fault was commanded through a terminal input. Remove the terminal input that triggers the fault. | Fault · External fault |
| F0090 | Signal loss, encoder | Fault · Encoder signal |
| A0590 | Alarm, no signals from the speed encoder | Alarm · Encoder signal |
| A0700 | CB alarm 1The parameter or configuration settings from the PROFIBUS master are invalid. Correct the PROFIBUS configuration. | Alarm · Communication loss |
| A0701 | CB alarm 2Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0702 | CB alarm 3The link to PROFIBUS is interrupted. Check the connector, the cable and the PROFIBUS master. | Alarm · Communication loss |
| A0703 | CB alarm 4No setpoints, or invalid setpoints (control word = 0), are arriving from the PROFIBUS master. Check the setpoints from the PROFIBUS master, and switch the SIMATIC CPU to RUN. | Alarm · Communication loss |
| A0704 | CB alarm 5At least one configured internode transmitter is not yet active, or has failed. Activate the internode transmitter. | Alarm · Communication loss |
| A0705 | CB alarm 6No actual values are arriving from the inverter. The fault is in the inverter. | Alarm · Communication loss |
| A0706 | CB alarm 7A software error on the PROFIBUS-DP communication board. The fault is on the PROFIBUS-DP board; see its diagnostic parameter for details. | Alarm · Communication loss |
| A0707 | CB alarm 8Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0708 | CB alarm 9Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0709 | CB alarm 10Specific to the communications module (CB). See the CB user manual. | Alarm · Communication loss |
| A0710 | CB communications errorCommunication with the CB (communications module) is lost. Check the CB hardware. | Alarm · Communication loss |
| A0711 | CB communications errorThe CB (communications module) reports a communications error. Check the CB parameters. | Alarm · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| F0035 | Restart after nThe automatic restart failed after the number of attempts set in P1211. | Fault · Automatic restart limit |
| F0041 | Failure, motor data identification | Fault · Motor identification |
| F0051 | Parameter EEPROM fault | Fault · Parameter memory |
| F0052 | Power stack faultA read error of the power data, or invalid power module data. Replace the drive. | Fault · Internal drive fault |
| F0053 | I/O EEPROM fault | Fault · Parameter memory |
| F0054 | Incorrect I/O module | Fault · Internal drive fault |
| F0060 | Asic time slice overflowAn internal communications failure. If the fault keeps returning, replace the inverter and contact Siemens customer service. | Fault · Internal drive fault |
| F0101 | Stack overflowA software error or processor failure. Run the self-test routines. | Fault · Internal drive fault |
| F0450 | Failure BIST tests | Fault · Internal drive fault |
| A0522 | Read I2C, time exceededCyclic access to the UCE values and power module data over the I2C bus is faulted (sizes FX and GX only). | Alarm · Internal drive fault |
| A0541 | Motor data identification routine activeMotor data identification (P1910) is selected and running. | Alarm · Motor identification |
| A0571 | Auto restart after fault present | Alarm · Automatic restart limit |
| A0600 | RTOS data loss alarm | Alarm · Internal drive fault |
| A0920 | ADC parameters not correctly set | Alarm · Setup |
| A0921 | DAC parameters not correctly set | Alarm · Setup |
Related
Related pages
Source
Siemens, MICROMASTER 430 Parameter List, Issue 10/06, 6SE6400-5AF00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.