MachineryFix

Yaskawa AC drive (VFD) · alarm code

V1000 LT-1: Cooling Fan Maintenance Time

LT-1 on the Yaskawa V1000 is the “Cooling Fan Maintenance Time” alarm. A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).

The drive's cooling fan has stopped or is not reporting. Running on without it will lead to an overtemperature trip and shortens the life of the power devices.

Code
LT-1
Type
Alarm (warning)
Drive
Yaskawa V1000
Kind of fault
Cooling fan

01 / Causes

What causes LT-1

  • The cooling fan has reached 90% of its expected performance life.

02 / Checks

What to check for LT-1

In the order Yaskawa gives them.

  1. 01Replace the cooling fan and reset the maintenance monitor by setting o4-03 to 0.

Also in the manual

  • An alarm output is only given if a digital output is set to H2-oo = 2F.

03 / Clearing it

How to clear LT-1

A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).

If LT-1 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How cooling fan faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the fan turns, and clear dust or fibre jamming it.
  2. 02Check the fan connector and its supply.

05 / Repair

When LT-1 means a repair

A seized or dead fan is replaced; it is one of the most common wear parts on a drive.

If LT-1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Cooling fan: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F30059 Internal fan defective · A30049 Internal fan defective
Siemens MICROMASTER 440F0030 Fan failed
Yaskawa A1000FAn Internal Fan Fault · LT-1 Cooling Fan Maintenance Time
Yaskawa GA500LT-1 Cooling Fan Maintenance Time
Mitsubishi Electric FR-D700FN Fan alarm

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

LT-1 won't clear? Get a technician who knows the V1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.