MachineryFix

Yaskawa AC drive (VFD) · alarm code

V1000 HbbF: Safe Disable Signal Input

HbbF on the Yaskawa V1000 is the “Safe Disable Signal Input” alarm. A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).

The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.

Code
HbbF
Type
Alarm (warning)
Drive
Yaskawa V1000
Kind of fault
Safety input

01 / Causes

What causes HbbF

  • The Safe Disable input hardware is defective: one of the channels is faulty.

02 / Checks

What to check for HbbF

In the order Yaskawa gives them.

  1. 01Replace the drive.

03 / Clearing it

How to clear HbbF

A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).

If HbbF stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How safety input faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
  2. 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.

05 / Repair

When HbbF means a repair

Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.

If HbbF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Safety input: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F01600 STOP A initiated · F01625 Sign-of-life error in the Safety data · F01650 Acceptance test required · F01659 Write task for parameter rejected · F30600 STOP A triggered · A01666 Static 1 signal at the F-DI for safe acknowledgement
Siemens SINAMICS V90F1611 SI CU: Defect detected · A52902 Emergency missing
Allen-Bradley PowerFlex 525F059 Safety Open · F111 Safety Hardware
ABB ACS355F0044 SAFE TORQUE OFF · F0045 STO1 LOST · F0046 STO2 LOST · A2023 EMERGENCY STOP · A2035 SAFE TORQUE OFF
Delta C2000STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3
Delta ASDA-B2AL013 Emergency stop
Hitachi WJ200E37 Safe Stop
Schneider Electric Altivar ATV320SAFF Safety function detected error
Yaskawa A1000Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input
Yaskawa GA500SCF Safety Circuit Fault · SToF Safe Torque OFF Hardware
Mitsubishi Electric FR-D700E.SAF Safety circuit fault · SA Safety stop

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

HbbF won't clear? Get a technician who knows the V1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.