HCA on the Yaskawa V1000 is the “Current Alarm” alarm. A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).
The drive measured output current above its trip limit and switched its transistors off, usually within microseconds, to protect itself. The current came from somewhere: a short or earth fault in the cable or motor, a load that needed more torque than the ramp allowed, or motor data that does not match the motor.
- Code
- HCA
- Type
- Alarm (warning)
- Drive
- Yaskawa V1000
- Kind of fault
- Overcurrent
01 / Causes
What causes HCA
- The drive current went above the overcurrent warning level (150% of rated current).
- Too heavy a load, acceleration or deceleration too short, or a special or oversized motor.
02 / Checks
What to check for HCA
In the order Yaskawa gives them.
- 01Measure the motor current, and reduce the load or use a larger drive.
- 02Calculate the torque needed for acceleration and the load's inertia; if it is not right, lengthen C1-01 to C1-08 or use a larger drive.
- 03Check the motor capacity and use a motor within the drive's allowed range.
03 / Clearing it
How to clear HCA
A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).
If HCA stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How overcurrent faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note when it trips: at start, during acceleration, at steady speed or while stopping. A trip at the instant of start points at the cable or motor; a trip during acceleration points at the ramp or the load.
- 02With the supply isolated and the DC bus discharged, disconnect the motor cable at the drive and insulation-test the cable and motor windings to earth and between phases.
- 03Measure winding resistance phase to phase. The three readings should match closely; an unbalanced reading means a winding fault.
- 04Turn the load by hand where it is safe to do so, to rule out a seized bearing, jammed conveyor or dragging brake.
- 05Compare the motor rating plate with the motor parameters in the drive, then run the drive with the motor disconnected if the manual allows it. A trip with no motor connected points at the drive's output stage.
05 / Repair
When HCA means a repair
If the drive trips on overcurrent with the motor disconnected, or the trip comes back the moment the drive is enabled with a healthy motor and cable, the output stage (IGBT module or its gate drive) has usually failed. That is a bench repair, not a setting.
If HCA keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Overcurrent: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F1 Overcurrent · A501 Current limit |
| Siemens SINAMICS G120 | F07801 Motor overcurrent · F30001 Overcurrent · A07409 V/f control, current limiting controller active |
| Siemens SINAMICS V90 | F7801 Motor overcurrent · F30001 Power unit: Overcurrent · A30031 Hardware current limiting in phase U |
| Siemens MICROMASTER 440 | F0001 Overcurrent · F0022 Hardware monitoring active · A0501 Current limit value |
| Allen-Bradley PowerFlex 525 | F012 HW OverCurrent · F063 SW OverCurrent |
| ABB ACS355 | F0001 OVERCURRENT · A2001 OVERCURRENT |
| Delta VFD-E | oc Over-current · ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during constant speed |
| Delta C2000 | ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during steady operation · ocS Over-current at stop |
| Delta ASDA-B2 | AL001 Over current |
| Hitachi WJ200 | E01 Over-current event while at constant speed · E02 Over-current event during deceleration · E03 Over-current event during acceleration · E04 Over-current event during other conditions |
| Schneider Electric Altivar ATV320 | OCF Overcurrent error |
| INVT Goodrive20 (GD20) | OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running |
| Yaskawa A1000 | oC Overcurrent · HCA Current Alarm |
| Yaskawa GA500 | oC Overcurrent · oC2 Overcurrent2 · HCA High Current Alarm |
| Siemens MICROMASTER 420 | F0001 Overcurrent · A0501 Current limit value |
| Siemens MICROMASTER 430 | F0001 Overcurrent · A0501 Current limit value |
| Siemens SINAMICS G110 | F0001 Overcurrent · A0501 Current limit |
| INVT Goodrive200A (GD200A) | OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running |
| Mitsubishi Electric FR-D700 | E.OC1 Overcurrent trip during acceleration · E.OC2 Overcurrent trip during constant speed · E.OC3 Overcurrent trip during deceleration or stop · OL Stall prevention (overcurrent) |
| Danfoss VLT Micro Drive FC 51 | Alarm 13 Over current · Warning 59 Current limit |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007