The FR-D700 is Mitsubishi Electric's compact general-purpose inverter (FR-D720, FR-D740, FR-D720S and FR-D710W models), found on conveyors, fans, pumps and small machines across Indian factories.
A tripping FR-D700 shows E. and a short code, such as E.OC1 or E.THM; warnings and messages such as OL, TH or Er1 appear without shutting off the output. Below is every code in Mitsubishi's FR-D700 instruction manual, with its description, check points and corrective actions.
01 / Reading codes
Reading and clearing FR-D700 codes
The operation panel shows a fault as E. followed by a short code, for example E.OC1 (overcurrent during acceleration). The FR-PU04 and FR-PU07 parameter units show a text name instead, such as OC During Acc.
On a fault the inverter trips (shuts off its output) and outputs a fault signal until it is reset. Error messages, warnings and the fan alarm are shown while the inverter keeps its output on.
- When a fault occurs the inverter trips and outputs a fault signal; warnings, the fan alarm and error messages do not shut off the output.
- Resetting the inverter clears the electronic thermal relay function's accumulated data.
- E.OHT (external thermal relay) does not restart the inverter on its own, even if the relay contacts reset automatically: the inverter has to be reset.
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| OL | Stall prevention (overcurrent) | Alarm · Overcurrent |
| E.OC1 | Overcurrent trip during acceleration | Fault · Overcurrent |
| E.OC2 | Overcurrent trip during constant speed | Fault · Overcurrent |
| E.OC3 | Overcurrent trip during deceleration or stop | Fault · Overcurrent |
| E.GF | Output side earth (ground) fault overcurrent at startAn earth (ground) fault on the inverter's output (load) side let an earth fault overcurrent flow at start, so the inverter tripped. Check the motor and its cable for an earth fault, and repair it. | Fault · Earth fault |
| E.LF | Output phase loss | Fault · Output phase loss |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| oL | Stall prevention (overvoltage) | Alarm · DC bus overvoltage |
| RB | Regenerative brake pre-alarm | Alarm · Braking resistor |
| UV | Undervoltage | Alarm · DC bus undervoltage |
| E.OV1 | Regenerative overvoltage trip during acceleration | Fault · DC bus overvoltage |
| E.OV2 | Regenerative overvoltage trip during constant speed | Fault · DC bus overvoltage |
| E.OV3 | Regenerative overvoltage trip during deceleration or stop | Fault · DC bus overvoltage |
| E.ILF | Input phase loss | Fault · Input phase loss |
| E.BE | Brake transistor alarm detection | Fault · Braking resistor |
04 / Temperature and overload
Temperature and overload
| Code | Name | Kind |
|---|---|---|
| TH | Electronic thermal relay function pre-alarm | Alarm · Motor overload or overtemperature |
| FN | Fan alarmOn an inverter with a cooling fan, the fan has stopped because of a fault, or runs differently from the Pr. 244 cooling fan operation selection. Check the cooling fan for a fault, and contact Mitsubishi. | Alarm · Cooling fan |
| E.THT | Inverter overload trip (electronic thermal O/L relay function) | Fault · Drive overload |
| E.THM | Motor overload trip (electronic thermal O/L relay function) | Fault · Motor overload or overtemperature |
| E.FIN | Heatsink overheat | Fault · Drive overtemperature |
| E.PTC | PTC thermistor operation | Fault · Temperature sensor signal |
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| E.OLT | Stall prevention stopStall prevention brought the output frequency down to 1 Hz and it stayed there for 3 seconds, so the inverter tripped. Check whether the motor is used under overload, and reduce the load (check the Pr. 22 stall prevention operation level setting). | Fault · Motor stall |
| E.CDO | Output current detection value exceededThe output current exceeded the Pr. 150 output current detection level. Check Pr. 150 (output current detection level), Pr. 151 (signal delay time), Pr. 166 (signal retention time) and Pr. 167 (output current detection operation selection). | Fault · Load monitoring |
06 / Signals and communication
Signals and communication
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| HOLD | Operation panel lockOperation lock mode is set, so operations other than the stop key are invalid. Press the MODE key for 2 seconds to release the lock. | Alarm · Setup |
| LOCD | Password lockedThe password function is active, so displaying and setting parameters is restricted. Enter the password in Pr. 297 (password lock/unlock) to unlock it before operating. | Alarm · Setup |
| Er1 | Write disable error | Alarm · Setup |
| Er2 | Write error during operation | Alarm · Setup |
| Er3 | Calibration errorThe analog input bias and gain calibration values are too close together. Check the calibration settings C3, C4, C6 and C7. | Alarm · Setup |
| Er4 | Mode designation error | Alarm · Setup |
| Err. | Inverter resetA reset is being executed through the RES signal, or a reset command from communication or the PU; it also shows when the power is switched off. Turn off the reset command. | Alarm · Setup |
| MT | Maintenance signal outputThe inverter's cumulative energisation time has reached the set time: the Pr. 503 maintenance timer is larger than the Pr. 504 maintenance timer alarm output set time. Setting 0 in Pr. 503 (maintenance timer) clears the signal. | Alarm · Setup |
| E.PE | Parameter storage device fault (control circuit board) | Fault · Parameter memory |
| E.RET | Retry count excessOperation could not be resumed within the number of retries set, so the inverter tripped. Find and remove the cause of the fault that came before this one. | Fault · Automatic restart limit |
| E.CPU | CPU fault | Fault · Internal drive fault |
| E.IOH | Inrush current limit circuit fault | Fault · Internal drive fault |
| E.AIE | Analog input fault | Fault · Setup |
Related
Related pages
Source
Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007