F7491 on the Siemens SINAMICS V90 is the “STOP cam minus reached” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.
An axis went past a limit: a software stroke limit stored in the control's parameters, or a hardware limit switch at the end of travel. The control stops feed so the slide does not run into its mechanical end.
- Code
- F7491
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V90, SIMOTICS S-1FL6
- Kind of fault
- Overtravel
01 / Causes
What causes F7491
- The STOP cam minus was reached. If it was reached while travelling in the positive direction, the STOP cam is wired wrongly.
02 / Checks
What to check for F7491
In the order Siemens gives them.
- 01Leave the STOP cam minus in the positive direction and bring the axis back into the valid traversing range.
- 02Check the STOP cam's wiring.
Also in the manual
- Reaction OFF3: the motor stops quickly, as an emergency stop. Acknowledgement IMMEDIATELY: it clears as soon as the cause is removed.
03 / Clearing it
How to clear F7491
- Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
- Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
- If the cause is not removed, the fault can come back after five seconds with no button pressed.
- Alarms acknowledge themselves.
Clear it once. If F7491 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How overtravel faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note the axis and direction the alarm names, and whether it is a software (stored stroke) or hardware (limit switch) overtravel.
- 02For a software overtravel, check that the program, work offsets and tool offsets put the axis where intended, then jog or hand-wheel it back inside the limit and reset.
- 03For a hardware overtravel, check whether the slide really is at the end of travel. If it is, back it off using the machine builder's overtravel release procedure; if it is not, check the limit switch, its dog, the cable and the input signal on the PMC diagnosis screen.
- 04If the alarm came after an encoder, motor or battery change, confirm the reference position before running a program: a shifted reference makes good programs overtravel.
05 / Repair
When F7491 means a repair
Usually an operating or program issue. It points to a repair when an axis trips with the slide nowhere near its limit: a failed limit switch, a broken cable or input, or a lost reference position.
If F7491 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Overtravel: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Delta ASDA-B2 | AL014 Reverse limit error · AL015 Forward limit error |
| Hitachi WJ200 | E83 Positioning range error |
07 / More codes
Other SINAMICS V90 codes
Source
Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.