MachineryFix

Delta AC drive (VFD) · fault code

VFD-E PGEr: PG feedback signal error

PGEr on the Delta VFD-E is the “PG feedback signal error” fault. A fault activates the drive's protective function and stops its output to the motor until the fault is reset.

The speed or position feedback from the encoder is missing or does not agree with what the drive expects.

Code
PGEr
Type
Fault (stops the drive)
Drive
Delta VFD-E
Kind of fault
Encoder signal

01 / Causes

What causes PGEr

  • The PG (encoder) feedback signal is faulty.

02 / Checks

What to check for PGEr

In the order Delta Electronics gives them.

  1. 01Check the wiring of the PG card.
  2. 02Try another PG card.

03 / Clearing it

How to clear PGEr

  • Remove the cause first, then reset in one of three ways: press the RESET key on the keypad, switch on a terminal set to RESET (one of Pr.04.05 to Pr.04.08 set to 05), or send a RESET command over communication.
  • Wait 5 seconds after a fault has cleared before resetting from the keypad or an input terminal.
  • Make sure the RUN command is off before resetting, or the drive may start straight away.

Clear it once. If PGEr comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How encoder signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
  2. 02Check the encoder's supply voltage.
  3. 03Check the encoder settings (type, pulses per revolution) in the drive.

05 / Repair

When PGEr means a repair

A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.

If PGEr keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Encoder signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V90F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error
Siemens MICROMASTER 440F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder
Allen-Bradley PowerFlex 525F091 Encoder Loss
ABB ACS355F0023 ENCODER ERR · A2024 ENCODER ERROR
Delta C2000PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off
Delta ASDA-B2AL004 Motor combination error · AL011 Encoder error · AL018 Abnormal signal output · AL024 Encoder initial magnetic field error · AL025 The internal of the encoder is in error · AL026 Unreliable internal data of the encoder
Hitachi WJ200E80 Encoder disconnection
Schneider Electric Altivar ATV320SPF Encoder feedback loss error
Yaskawa V1000dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG)
Yaskawa A1000dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed
Yaskawa GA500dEv Speed Deviation · oS Overspeed · PGo Encoder (PG) Feedback Loss
Siemens MICROMASTER 430F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder

07 / More codes

Other VFD-E codes

Source

Delta Electronics, VFD-E Series User Manual, Revision Jan. 2012 (08EE), Chapter 6, Fault Code Information and Maintenance.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

PGEr won't clear? Get a technician who knows the VFD-E.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.