Delta AC drive (VFD) · fault code

VFD-E oL: Overload

oL on the Delta VFD-E is the “Overload” fault. A fault activates the drive's protective function and stops its output to the motor until the fault is reset.

The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.

Code
oL
Type
Fault (stops the drive)
Drive
Delta VFD-E
Kind of fault
Drive overload

01 / Causes

What causes oL

  • The drive detected excessive output current. The drive can withstand up to 150% of its rated current for at most 60 seconds.

02 / Checks

What to check for oL

In the order Delta Electronics gives them.

  1. 01Check whether the motor is overloaded.
  2. 02Reduce the torque compensation setting in Pr.07.02.
  3. 03Use the next larger drive.

03 / Clearing it

How to clear oL

  • Remove the cause first, then reset in one of three ways: press the RESET key on the keypad, switch on a terminal set to RESET (one of Pr.04.05 to Pr.04.08 set to 05), or send a RESET command over communication.
  • Wait 5 seconds after a fault has cleared before resetting from the keypad or an input terminal.
  • Make sure the RUN command is off before resetting, or the drive may start straight away.

Clear it once. If oL comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overload faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Record the running current and compare it with the drive's rated current.
  2. 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
  3. 03Check acceleration time and boost settings; long periods at high torque add up quickly.

05 / Repair

When oL means a repair

If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.

If oL keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Drive overload: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F5 Inverter I2t · A505 Inverter I2t
Siemens SINAMICS G120F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t
Siemens SINAMICS V90F30005 Power unit: Overload I2t
Siemens MICROMASTER 440F0005 Inverter I2T · A0505 Inverter I2T
Allen-Bradley PowerFlex 525F064 Drive Overload
Delta C2000oL Over load · oL3 Overload protection at low frequency
Hitachi WJ200E38 Low-speed overload protection
INVT Goodrive20 (GD20)OL2 VFD overload
Yaskawa V1000oL2 Drive Overload
Yaskawa A1000oL2 Drive Overload
Yaskawa GA500oL2 Drive Overload
Siemens MICROMASTER 420F0005 Inverter I2t · A0505 Inverter I2t
Siemens MICROMASTER 430F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle
Siemens SINAMICS G110F0005 Inverter I2t · A0505 Inverter I2t
INVT Goodrive200A (GD200A)OL2 VFD overload
Mitsubishi Electric FR-D700E.THT Inverter overload trip (electronic thermal O/L relay function)
Danfoss VLT Micro Drive FC 51Alarm 9 Inverter overloaded

07 / More codes

Other VFD-E codes

Source

Delta Electronics, VFD-E Series User Manual, Revision Jan. 2012 (08EE), Chapter 6, Fault Code Information and Maintenance.