MachineryFix

Delta AC drive (VFD) · fault code

VFD-E PHL: Phase loss

PHL on the Delta VFD-E is the “Phase loss” fault. A fault activates the drive's protective function and stops its output to the motor until the fault is reset.

One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.

Code
PHL
Type
Fault (stops the drive)
Drive
Delta VFD-E
Kind of fault
Input phase loss

01 / Causes

What causes PHL

  • An input phase is missing.

02 / Checks

What to check for PHL

In the order Delta Electronics gives them.

  1. 01Check the input phase wiring for loose contacts.

03 / Clearing it

How to clear PHL

  • Remove the cause first, then reset in one of three ways: press the RESET key on the keypad, switch on a terminal set to RESET (one of Pr.04.05 to Pr.04.08 set to 05), or send a RESET command over communication.
  • Wait 5 seconds after a fault has cleared before resetting from the keypad or an input terminal.
  • Make sure the RUN command is off before resetting, or the drive may start straight away.

Clear it once. If PHL comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How input phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure all three phases at the drive input terminals with the drive running under load.
  2. 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
  3. 03Tighten and inspect supply terminals for heat damage.

05 / Repair

When PHL means a repair

If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.

If PHL keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Input phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F20 DC ripple too high
Siemens SINAMICS G120F30011 Line phase failure
Siemens SINAMICS V90F30011 Line phase failure in main circuit
Siemens MICROMASTER 440F0020 Line supply phase missing
ABB ACS355F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS
Delta C2000OrP Phase loss protection
Delta ASDA-B2AL022 Main circuit power lack phase
Schneider Electric Altivar ATV320PHF Input phase loss error
INVT Goodrive20 (GD20)SPI Phase loss on input side
Yaskawa V1000PF Input Phase Loss
Yaskawa A1000PF Input Phase Loss
Yaskawa GA500PF Input Phase Loss
Siemens MICROMASTER 430F0020 Line supply phase missing
INVT Goodrive200A (GD200A)SPI Phase loss on input side
Mitsubishi Electric FR-D700E.ILF Input phase loss
Danfoss VLT Micro Drive FC 51Alarm 4 Mains phase loss

07 / More codes

Other VFD-E codes

Source

Delta Electronics, VFD-E Series User Manual, Revision Jan. 2012 (08EE), Chapter 6, Fault Code Information and Maintenance.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

PHL won't clear? Get a technician who knows the VFD-E.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.