FbE on the Delta VFD-E is the “PID feedback signal error” alarm. A warning (CExx, FbE, AUE) is shown on the keypad. What the drive does next depends on its settings: Pr.09.02 for communication errors and Pr.10.09 for PID feedback errors.
A process value the drive controls (a PID feedback such as pressure or flow) went outside its set limits, or a pump protection function tripped.
- Code
- FbE
- Type
- Alarm (warning)
- Drive
- Delta VFD-E
- Kind of fault
- Process limit
01 / Causes
What causes FbE
- The analog PID feedback signal is abnormal (judged against Pr.10.16).
02 / Checks
What to check for FbE
In the order Delta Electronics gives them.
- 01Check the PID feedback setting (Pr.10.01) and the AVI/ACI wiring.
- 02Check the system's response time against the PID feedback signal detection time (Pr.10.08).
Also in the manual
- Pr.10.09 sets the reaction: 0 warns and ramps to stop, 1 warns and coasts to stop, 2 warns and keeps running (the warning clears once the feedback is normal). With 0 or 1, press RESET to clear it.
03 / Clearing it
How to clear FbE
A warning (CExx, FbE, AUE) is shown on the keypad. What the drive does next depends on its settings: Pr.09.02 for communication errors and Pr.10.09 for PID feedback errors.
If FbE stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How process limit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the process itself: a closed valve, an empty tank, a blocked line.
- 02Check the feedback transmitter and its wiring.
- 03Check the limit and gain settings in the drive.
05 / Repair
When FbE means a repair
Usually a process or sensor problem rather than the drive.
If FbE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Process limit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F221 PID feedback below minimum value · F222 PID feedback above maximum value · F410 Cavitation protection failure · A930 Cavitation protection warn |
| Siemens SINAMICS G120 | F07426 Technology controller actual value limited · F07445 PID autotuning canceled · A07444 PID autotuning is activated |
| Siemens MICROMASTER 440 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
| ABB ACS355 | A2018 PID SLEEP |
| Yaskawa V1000 | FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Yaskawa A1000 | FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Yaskawa GA500 | CP1 Comparator 1 Limit Fault · CP2 Comparator 2 Limit Fault · FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Siemens MICROMASTER 420 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
| Siemens MICROMASTER 430 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
07 / More codes
Other VFD-E codes
Source
Delta Electronics, VFD-E Series User Manual, Revision Jan. 2012 (08EE), Chapter 6, Fault Code Information and Maintenance.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007