MachineryFix

Delta AC drive (VFD) · fault code

VFD-E AErr: ACI signal error

AErr on the Delta VFD-E is the “ACI signal error” fault. A fault activates the drive's protective function and stops its output to the motor until the fault is reset.

An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.

Code
AErr
Type
Fault (stops the drive)
Drive
Delta VFD-E
Kind of fault
Analog signal loss

01 / Causes

What causes AErr

  • The analog current input (ACI) signal is faulty.

02 / Checks

What to check for AErr

In the order Delta Electronics gives them.

  1. 01Check the ACI wiring.

03 / Clearing it

How to clear AErr

  • Remove the cause first, then reset in one of three ways: press the RESET key on the keypad, switch on a terminal set to RESET (one of Pr.04.05 to Pr.04.08 set to 05), or send a RESET command over communication.
  • Wait 5 seconds after a fault has cleared before resetting from the keypad or an input terminal.
  • Make sure the RUN command is off before resetting, or the drive may start straight away.

Clear it once. If AErr comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How analog signal loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure the signal at the drive terminals while the system runs.
  2. 02Check the wiring back to the source for breaks and loose terminals.
  3. 03Check the transmitter or the PLC's analog output that supplies the signal.

05 / Repair

When AErr means a repair

If the signal is correct at the terminals, the drive's analog input may have failed.

If AErr keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Analog signal loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F80 Signal lost on analog input
Siemens SINAMICS G120F03505 Analog input, wire break
Siemens MICROMASTER 440F0080 ADC input signal lost
Allen-Bradley PowerFlex 525F029 Analog In Loss
ABB ACS355F0007 AI1 LOSS · F0008 AI2 LOSS · A2006 AI1 LOSS · A2007 AI2 LOSS
Delta C2000AFE PID loss ACI · ACE ACI loss
Schneider Electric Altivar ATV320LFF3 AI3 4-20mA loss error
INVT Goodrive20 (GD20)PIDE PID feedback offline fault
Siemens MICROMASTER 420F0080 ADC input signal lost
Siemens MICROMASTER 430F0080 ADC input signal lost
INVT Goodrive200A (GD200A)PIDE PID feedback offline fault
Danfoss VLT Micro Drive FC 51Alarm 2 Live zero error

07 / More codes

Other VFD-E codes

Source

Delta Electronics, VFD-E Series User Manual, Revision Jan. 2012 (08EE), Chapter 6, Fault Code Information and Maintenance.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

AErr won't clear? Get a technician who knows the VFD-E.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.