The Goodrive200A (GD200A) is INVT's general-purpose open-loop vector VFD for induction motors, the bigger sibling of the GD20 and a common drive on fans, pumps, compressors and machinery in Indian plants.
A GD200A fault shows as a short letter code such as OC1 or OV2. Below is every fault in INVT's GD200A manual, with the causes and solutions INVT gives, and the fault type number a PLC or HMI reads over communication.
01 / Reading codes
Reading and clearing Goodrive200A (GD200A) codes
When the TRIP indicator on the keypad is lit, the keypad shows the fault code, a short letter code such as OC1, OV2 or OL1.
On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.
- After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
- P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.
02 / Current and earth faults
Current and earth faults
| Code | Name | Kind |
|---|---|---|
| OUt1 | Inverter unit U-phase protection | Fault · Output short circuit |
| OUt2 | Inverter unit V-phase protection | Fault · Output short circuit |
| OUt3 | Inverter unit W-phase protection | Fault · Output short circuit |
| OC1 | Overcurrent during acceleration | Fault · Overcurrent |
| OC2 | Overcurrent during deceleration | Fault · Overcurrent |
| OC3 | Overcurrent during constant speed running | Fault · Overcurrent |
| SPO | Phase loss on output side | Fault · Output phase loss |
| ETH1 | To-ground short-circuit fault 1 | Fault · Earth fault |
| ETH2 | To-ground short-circuit fault 2 | Fault · Earth fault |
03 / Voltage and supply
Voltage and supply
| Code | Name | Kind |
|---|---|---|
| OV1 | Overvoltage during acceleration | Fault · DC bus overvoltage |
| OV2 | Overvoltage during deceleration | Fault · DC bus overvoltage |
| OV3 | Overvoltage during constant speed running | Fault · DC bus overvoltage |
| UV | Bus undervoltage | Fault · DC bus undervoltage |
| SPI | Phase loss on input side | Fault · Input phase loss |
| bCE | Braking unit fault | Fault · Braking resistor |
| PoFF | System power failureThe system is powered off, or the bus voltage is too low. Check the supply conditions. | Alarm · DC bus undervoltage |
04 / Temperature and overload
Temperature and overload
05 / Motor and load
Motor and load
| Code | Name | Kind |
|---|---|---|
| OL3 | Electronic overload faultThe VFD gives the overload pre-alarm according to its settings. Check the load and the overload pre-alarm threshold. | Fault · Load monitoring |
| LL | Electronic underload faultThe VFD gives the underload pre-alarm according to its settings. Check the load and the underload pre-alarm thresholds. | Fault · Load monitoring |
06 / Signals and communication
Signals and communication
| Code | Name | Kind |
|---|---|---|
| EF | External faultAn S terminal set as an external fault input has acted. Check the external device's input. | Fault · External fault |
| CE | RS485 communication fault | Fault · Communication loss |
| PIDE | PID feedback offline fault | Fault · Analog signal loss |
| PCE | Keypad communication fault | Fault · Communication loss |
| UPE | Parameter upload error | Fault · Communication loss |
| DNE | Parameter download error | Fault · Communication loss |
07 / Setup, memory and internal
Setup, memory and internal
| Code | Name | Kind |
|---|---|---|
| ItE | Current detection fault | Fault · Internal drive fault |
| tE | Motor autotuning fault | Fault · Motor identification |
| EEP | EEPROM operation fault | Fault · Parameter memory |
| END | Running time reachedThe VFD's actual running time is longer than its internally set running time. Ask the supplier to adjust the preset running time. | Fault · Setup |
Related
Related pages
Source
INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.