MachineryFix

AC drive (VFD) · 32 codes

INVT Goodrive200A (GD200A) fault codes

The Goodrive200A (GD200A) is INVT's general-purpose open-loop vector VFD for induction motors, the bigger sibling of the GD20 and a common drive on fans, pumps, compressors and machinery in Indian plants.

A GD200A fault shows as a short letter code such as OC1 or OV2. Below is every fault in INVT's GD200A manual, with the causes and solutions INVT gives, and the fault type number a PLC or HMI reads over communication.

01 / Reading codes

Reading and clearing Goodrive200A (GD200A) codes

When the TRIP indicator on the keypad is lit, the keypad shows the fault code, a short letter code such as OC1, OV2 or OL1.

On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.

  • After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
  • P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.

02 / Current and earth faults

Current and earth faults

CodeNameKind
OUt1Inverter unit U-phase protectionFault · Output short circuit
OUt2Inverter unit V-phase protectionFault · Output short circuit
OUt3Inverter unit W-phase protectionFault · Output short circuit
OC1Overcurrent during accelerationFault · Overcurrent
OC2Overcurrent during decelerationFault · Overcurrent
OC3Overcurrent during constant speed runningFault · Overcurrent
SPOPhase loss on output sideFault · Output phase loss
ETH1To-ground short-circuit fault 1Fault · Earth fault
ETH2To-ground short-circuit fault 2Fault · Earth fault

03 / Voltage and supply

Voltage and supply

CodeNameKind
OV1Overvoltage during accelerationFault · DC bus overvoltage
OV2Overvoltage during decelerationFault · DC bus overvoltage
OV3Overvoltage during constant speed runningFault · DC bus overvoltage
UVBus undervoltageFault · DC bus undervoltage
SPIPhase loss on input sideFault · Input phase loss
bCEBraking unit faultFault · Braking resistor
PoFFSystem power failureThe system is powered off, or the bus voltage is too low. Check the supply conditions.Alarm · DC bus undervoltage

04 / Temperature and overload

Temperature and overload

CodeNameKind
OL1Motor overloadFault · Motor overload or overtemperature
OL2VFD overloadFault · Drive overload
OH1Rectifier module overheatingFault · Drive overtemperature
OH2Inverter module overheatFault · Drive overtemperature

05 / Motor and load

Motor and load

CodeNameKind
OL3Electronic overload faultThe VFD gives the overload pre-alarm according to its settings. Check the load and the overload pre-alarm threshold.Fault · Load monitoring
LLElectronic underload faultThe VFD gives the underload pre-alarm according to its settings. Check the load and the underload pre-alarm thresholds.Fault · Load monitoring

06 / Signals and communication

Signals and communication

CodeNameKind
EFExternal faultAn S terminal set as an external fault input has acted. Check the external device's input.Fault · External fault
CERS485 communication faultFault · Communication loss
PIDEPID feedback offline faultFault · Analog signal loss
PCEKeypad communication faultFault · Communication loss
UPEParameter upload errorFault · Communication loss
DNEParameter download errorFault · Communication loss

07 / Setup, memory and internal

Setup, memory and internal

CodeNameKind
ItECurrent detection faultFault · Internal drive fault
tEMotor autotuning faultFault · Motor identification
EEPEEPROM operation faultFault · Parameter memory
ENDRunning time reachedThe VFD's actual running time is longer than its internally set running time. Ask the supplier to adjust the preset running time.Fault · Setup

Related

Related pages

Source

INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.