Goodrive200A (GD200A) SPI: Phase loss on input side

SPI on the INVT Goodrive200A (GD200A) is the “Phase loss on input side” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.

One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.

Code
SPI
Type
Fault (stops the drive)
Drive
INVT Goodrive200A (GD200A)
Kind of fault
Input phase loss

01 / Causes

What causes SPI

  • A phase is lost, or fluctuates violently, on inputs R, S and T.

02 / Checks

What to check for SPI

In the order INVT gives them.

  1. 01Check the input power.
  2. 02Check the installation wiring.

Also in the manual

  • Over communication this fault reads as type 13.

03 / Clearing it

How to clear SPI

  • After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
  • P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.

Clear it once. If SPI comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How input phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure all three phases at the drive input terminals with the drive running under load.
  2. 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
  3. 03Tighten and inspect supply terminals for heat damage.

05 / Repair

When SPI means a repair

If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.

If SPI keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Input phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F20 DC ripple too high
Siemens SINAMICS G120F30011 Line phase failure
Siemens SINAMICS V90F30011 Line phase failure in main circuit
Siemens MICROMASTER 440F0020 Line supply phase missing
ABB ACS355F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS
Delta VFD-EPHL Phase loss
Delta C2000OrP Phase loss protection
Delta ASDA-B2AL022 Main circuit power lack phase
Schneider Electric Altivar ATV320PHF Input phase loss error
INVT Goodrive20 (GD20)SPI Phase loss on input side
Yaskawa V1000PF Input Phase Loss
Yaskawa A1000PF Input Phase Loss
Yaskawa GA500PF Input Phase Loss
Siemens MICROMASTER 430F0020 Line supply phase missing
Mitsubishi Electric FR-D700E.ILF Input phase loss
Danfoss VLT Micro Drive FC 51Alarm 4 Mains phase loss

07 / More codes

Other Goodrive200A (GD200A) codes

Source

INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SPI won't clear? Get a technician who knows the Goodrive200A (GD200A).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.