INVT AC drive (VFD) · fault code

Goodrive200A (GD200A) SPO: Phase loss on output side

SPO on the INVT Goodrive200A (GD200A) is the “Phase loss on output side” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.

The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.

Code
SPO
Type
Fault (stops the drive)
Drive
INVT Goodrive200A (GD200A)
Kind of fault
Output phase loss

01 / Causes

What causes SPO

  • A phase is lost on output U, V or W, or the motor's three phases are unbalanced.

02 / Checks

What to check for SPO

In the order INVT gives them.

  1. 01Check the output wiring.
  2. 02Check the motor and its cable.

Also in the manual

  • Over communication this fault reads as type 14.

03 / Clearing it

How to clear SPO

  • After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
  • P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.

Clear it once. If SPO comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
  2. 02Inspect any contactor, isolator or junction box in the motor circuit.
  3. 03Measure winding resistance phase to phase at the motor.

05 / Repair

When SPO means a repair

When cable, connections and windings are all good, an output phase in the drive itself may be open.

If SPO keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Output phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A922 No load applied to inverter
Siemens SINAMICS G120F30015 Motor cable phase failure
Siemens SINAMICS V90F7410 Current controller output limited · F30015 Phase failure motor cable
Siemens MICROMASTER 440F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter
Allen-Bradley PowerFlex 525F021 Output Ph Loss
ABB ACS355F0034 MOTOR PHASE
Delta C2000OPHL Output phase loss
Delta ASDA-B2AL031 Incorrect wiring of the motor power line U, V, W, GND
Schneider Electric Altivar ATV320OPF1 Single output phase loss error · OPF2 Output phase loss error
INVT Goodrive20 (GD20)SPO Phase loss on output side
Yaskawa V1000LF Output Phase Loss · LF2 Output current imbalance
Yaskawa A1000LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance
Yaskawa GA500LF Output Phase Loss · LF2 Output Current Imbalance
Siemens MICROMASTER 430F0023 Output fault · A0523 Output fault
Mitsubishi Electric FR-D700E.LF Output phase loss
Danfoss VLT Micro Drive FC 51Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing

07 / More codes

Other Goodrive200A (GD200A) codes

Source

INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SPO won't clear? Get a technician who knows the Goodrive200A (GD200A).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.