MachineryFix

INVT AC drive (VFD) · fault code

Goodrive200A (GD200A) bCE: Braking unit fault

bCE on the INVT Goodrive200A (GD200A) is the “Braking unit fault” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.

The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.

Code
bCE
Type
Fault (stops the drive)
Drive
INVT Goodrive200A (GD200A)
Kind of fault
Braking resistor

01 / Causes

What causes bCE

  • A fault in the braking circuit, or the braking transistor is damaged.
  • The external braking resistor's resistance is too low.

02 / Checks

What to check for bCE

In the order INVT gives them.

  1. 01Check the braking unit and replace the braking transistor.
  2. 02Increase the braking resistance.

Also in the manual

  • Over communication this fault reads as type 23.

03 / Clearing it

How to clear bCE

  • After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
  • P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.

Clear it once. If bCE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How braking resistor faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
  2. 02Check the resistor's resistance against the drive manual's minimum.
  3. 03Check the resistor for heat damage and its wiring for loose terminals.

05 / Repair

When bCE means a repair

A burnt resistor or a shorted braking transistor in the drive has to be replaced.

If bCE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Braking resistor: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A535 Braking resistor overload
Siemens SINAMICS G120F07806 Regenerative power limit exceeded
Siemens SINAMICS V90A52901 Braking resistor reaches alarm threshold
Siemens MICROMASTER 440A0535 Brake resistor hot
Delta C2000bF Brake transistor error
Delta ASDA-B2AL005 Regeneration error · AL085 Regeneration error
Hitachi WJ200E06 Braking resistor overload protection
INVT Goodrive20 (GD20)bCE Braking unit fault
Yaskawa V1000oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa A1000boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa GA500boL Braking Transistor Overload Fault · oL7 High Slip Braking Overload · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor Fault
Mitsubishi Electric FR-D700E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low

07 / More codes

Other Goodrive200A (GD200A) codes

Source

INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

bCE won't clear? Get a technician who knows the Goodrive200A (GD200A).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.