bCE on the INVT Goodrive200A (GD200A) is the “Braking unit fault” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.
The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.
- Code
- bCE
- Type
- Fault (stops the drive)
- Drive
- INVT Goodrive200A (GD200A)
- Kind of fault
- Braking resistor
01 / Causes
What causes bCE
- A fault in the braking circuit, or the braking transistor is damaged.
- The external braking resistor's resistance is too low.
02 / Checks
What to check for bCE
In the order INVT gives them.
- 01Check the braking unit and replace the braking transistor.
- 02Increase the braking resistance.
Also in the manual
- Over communication this fault reads as type 23.
03 / Clearing it
How to clear bCE
- After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
- P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.
Clear it once. If bCE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How braking resistor faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
- 02Check the resistor's resistance against the drive manual's minimum.
- 03Check the resistor for heat damage and its wiring for loose terminals.
05 / Repair
When bCE means a repair
A burnt resistor or a shorted braking transistor in the drive has to be replaced.
If bCE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.
06 / Other drives
Braking resistor: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A535 Braking resistor overload |
| Siemens SINAMICS G120 | F07806 Regenerative power limit exceeded |
| Siemens SINAMICS V90 | A52901 Braking resistor reaches alarm threshold |
| Siemens MICROMASTER 440 | A0535 Brake resistor hot |
| Delta C2000 | bF Brake transistor error |
| Delta ASDA-B2 | AL005 Regeneration error · AL085 Regeneration error |
| Hitachi WJ200 | E06 Braking resistor overload protection |
| INVT Goodrive20 (GD20) | bCE Braking unit fault |
| Yaskawa V1000 | oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| Yaskawa A1000 | boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| Yaskawa GA500 | boL Braking Transistor Overload Fault · oL7 High Slip Braking Overload · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor Fault |
| Mitsubishi Electric FR-D700 | E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low |
07 / More codes
Other Goodrive200A (GD200A) codes
Source
INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007