MachineryFix

INVT AC drive (VFD) · fault code

Goodrive200A (GD200A) OL1: Motor overload

OL1 on the INVT Goodrive200A (GD200A) is the “Motor overload” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.

The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.

Code
OL1
Type
Fault (stops the drive)
Drive
INVT Goodrive200A (GD200A)
Kind of fault
Motor overload or overtemperature

01 / Causes

What causes OL1

  • The supply voltage is too low.
  • The motor's rated current is set wrongly.
  • The motor stalls, or the load changes violently.

02 / Checks

What to check for OL1

In the order INVT gives them.

  1. 01Check the supply voltage.
  2. 02Set the motor's rated current again.
  3. 03Check the load and adjust the torque boost.

Also in the manual

  • Over communication this fault reads as type 11.

03 / Clearing it

How to clear OL1

  • After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
  • P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.

Clear it once. If OL1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor overload or overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare running current with the motor's rating plate current.
  2. 02Check the motor overload settings in the drive against the rating plate.
  3. 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
  4. 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.

05 / Repair

When OL1 means a repair

A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.

If OL1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Motor overload or overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F11 Motor overtemperature · A511 Motor overtemperature I2t
Siemens SINAMICS G120F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature
Siemens SINAMICS V90F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature
Siemens MICROMASTER 440F0011 Motor overtemperature · A0511 Motor overtemperature
Allen-Bradley PowerFlex 525F007 Motor Overload
ABB ACS355F0009 MOT OVERTEMP · A2010 MOTOR TEMP
Delta VFD-EoL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection
Delta C2000EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating
Delta ASDA-B2AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload
Hitachi WJ200E05 Overload protection · E35 Thermistor
Schneider Electric Altivar ATV320OLF Motor overload error · OTFL DI6=PTC overheat error
INVT Goodrive20 (GD20)OL1 Motor overload
Yaskawa V1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Yaskawa A1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload
Yaskawa GA500oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Siemens MICROMASTER 420F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t
Siemens MICROMASTER 430F0011 Motor overtemperature · A0511 Motor overtemperature
Siemens SINAMICS G110F0011 Motor over temperature I2t · A0511 Motor over temperature I2t
Mitsubishi Electric FR-D700E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 10 Motor ETR over temperature

07 / More codes

Other Goodrive200A (GD200A) codes

Source

INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

OL1 won't clear? Get a technician who knows the Goodrive200A (GD200A).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.