OL1 on the INVT Goodrive200A (GD200A) is the “Motor overload” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.
The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.
- Code
- OL1
- Type
- Fault (stops the drive)
- Drive
- INVT Goodrive200A (GD200A)
- Kind of fault
- Motor overload or overtemperature
01 / Causes
What causes OL1
- The supply voltage is too low.
- The motor's rated current is set wrongly.
- The motor stalls, or the load changes violently.
02 / Checks
What to check for OL1
In the order INVT gives them.
- 01Check the supply voltage.
- 02Set the motor's rated current again.
- 03Check the load and adjust the torque boost.
Also in the manual
- Over communication this fault reads as type 11.
03 / Clearing it
How to clear OL1
- After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
- P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.
Clear it once. If OL1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor overload or overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare running current with the motor's rating plate current.
- 02Check the motor overload settings in the drive against the rating plate.
- 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
- 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.
05 / Repair
When OL1 means a repair
A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.
If OL1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.
06 / Other drives
Motor overload or overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F11 Motor overtemperature · A511 Motor overtemperature I2t |
| Siemens SINAMICS G120 | F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature |
| Siemens SINAMICS V90 | F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature |
| Siemens MICROMASTER 440 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Allen-Bradley PowerFlex 525 | F007 Motor Overload |
| ABB ACS355 | F0009 MOT OVERTEMP · A2010 MOTOR TEMP |
| Delta VFD-E | oL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection |
| Delta C2000 | EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating |
| Delta ASDA-B2 | AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload |
| Hitachi WJ200 | E05 Overload protection · E35 Thermistor |
| Schneider Electric Altivar ATV320 | OLF Motor overload error · OTFL DI6=PTC overheat error |
| INVT Goodrive20 (GD20) | OL1 Motor overload |
| Yaskawa V1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Yaskawa A1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload |
| Yaskawa GA500 | oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Siemens MICROMASTER 420 | F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t |
| Siemens MICROMASTER 430 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Siemens SINAMICS G110 | F0011 Motor over temperature I2t · A0511 Motor over temperature I2t |
| Mitsubishi Electric FR-D700 | E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 10 Motor ETR over temperature |
07 / More codes
Other Goodrive200A (GD200A) codes
Source
INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007