Goodrive200A (GD200A) OL2: VFD overload

OL2 on the INVT Goodrive200A (GD200A) is the “VFD overload” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.

The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.

Code
OL2
Type
Fault (stops the drive)
Drive
INVT Goodrive200A (GD200A)
Kind of fault
Drive overload

01 / Causes

What causes OL2

  • Acceleration is too fast.
  • The motor is restarted while still rotating.
  • The supply voltage is too low.
  • The load is too heavy.
  • The power rating is too small.

02 / Checks

What to check for OL2

In the order INVT gives them.

  1. 01Lengthen the acceleration time.
  2. 02Avoid restarting after a stop while the motor turns.
  3. 03Check the supply voltage.
  4. 04Choose a VFD with a larger power rating.
  5. 05Choose a suitable motor.

Also in the manual

  • Over communication this fault reads as type 12.

03 / Clearing it

How to clear OL2

  • After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
  • P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.

Clear it once. If OL2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overload faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Record the running current and compare it with the drive's rated current.
  2. 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
  3. 03Check acceleration time and boost settings; long periods at high torque add up quickly.

05 / Repair

When OL2 means a repair

If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.

If OL2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Drive overload: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F5 Inverter I2t · A505 Inverter I2t
Siemens SINAMICS G120F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t
Siemens SINAMICS V90F30005 Power unit: Overload I2t
Siemens MICROMASTER 440F0005 Inverter I2T · A0505 Inverter I2T
Allen-Bradley PowerFlex 525F064 Drive Overload
Delta VFD-EoL Overload
Delta C2000oL Over load · oL3 Overload protection at low frequency
Hitachi WJ200E38 Low-speed overload protection
INVT Goodrive20 (GD20)OL2 VFD overload
Yaskawa V1000oL2 Drive Overload
Yaskawa A1000oL2 Drive Overload
Yaskawa GA500oL2 Drive Overload
Siemens MICROMASTER 420F0005 Inverter I2t · A0505 Inverter I2t
Siemens MICROMASTER 430F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle
Siemens SINAMICS G110F0005 Inverter I2t · A0505 Inverter I2t
Mitsubishi Electric FR-D700E.THT Inverter overload trip (electronic thermal O/L relay function)
Danfoss VLT Micro Drive FC 51Alarm 9 Inverter overloaded

07 / More codes

Other Goodrive200A (GD200A) codes

Source

INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

OL2 won't clear? Get a technician who knows the Goodrive200A (GD200A).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.