PIDE on the INVT Goodrive200A (GD200A) is the “PID feedback offline fault” fault. On a fault the VFD stops its output, the TRIP indicator lights and the keypad shows the fault code until the fault is reset.
An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.
- Code
- PIDE
- Type
- Fault (stops the drive)
- Drive
- INVT Goodrive200A (GD200A)
- Kind of fault
- Analog signal loss
01 / Causes
What causes PIDE
- The PID feedback is offline.
- The PID feedback source has disappeared.
02 / Checks
What to check for PIDE
In the order INVT gives them.
- 01Check the PID feedback signal wires.
- 02Check the PID feedback source.
Also in the manual
- Over communication this fault reads as type 22.
03 / Clearing it
How to clear PIDE
- After the cause is removed, reset the fault with the STOP/RST key, a digital input set for fault reset, or by switching the power off; the motor can then be started again.
- P07.27 to P07.32 record the types of the last six faults, and P07.33 to P07.56 record the running data at the last three faults.
Clear it once. If PIDE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How analog signal loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure the signal at the drive terminals while the system runs.
- 02Check the wiring back to the source for breaks and loose terminals.
- 03Check the transmitter or the PLC's analog output that supplies the signal.
05 / Repair
When PIDE means a repair
If the signal is correct at the terminals, the drive's analog input may have failed.
If PIDE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.
06 / Other drives
Analog signal loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F80 Signal lost on analog input |
| Siemens SINAMICS G120 | F03505 Analog input, wire break |
| Siemens MICROMASTER 440 | F0080 ADC input signal lost |
| Allen-Bradley PowerFlex 525 | F029 Analog In Loss |
| ABB ACS355 | F0007 AI1 LOSS · F0008 AI2 LOSS · A2006 AI1 LOSS · A2007 AI2 LOSS |
| Delta VFD-E | AErr ACI signal error |
| Delta C2000 | AFE PID loss ACI · ACE ACI loss |
| Schneider Electric Altivar ATV320 | LFF3 AI3 4-20mA loss error |
| INVT Goodrive20 (GD20) | PIDE PID feedback offline fault |
| Siemens MICROMASTER 420 | F0080 ADC input signal lost |
| Siemens MICROMASTER 430 | F0080 ADC input signal lost |
| Danfoss VLT Micro Drive FC 51 | Alarm 2 Live zero error |
07 / More codes
Other Goodrive200A (GD200A) codes
Source
INVT, Goodrive200A Series VFD manual, English V3.1, Chapter 8, Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007