MachineryFix

Siemens AC drive (VFD) · fault code

MICROMASTER 430 F0090: Signal loss, encoder

F0090 on the Siemens MICROMASTER 430 is the “Signal loss, encoder” fault. On a fault the inverter switches off and shows the fault code; most MM430 faults use Siemens' reaction STOP II (F0012 uses STOP I). It will not run until the fault is reset.

The speed or position feedback from the encoder is missing or does not agree with what the drive expects.

Code
F0090
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 430
Kind of fault
Encoder signal

01 / Causes

What causes F0090

  • The encoder signal between the encoder and the inverter is interrupted.
  • The difference between the setpoint and the actual frequency is too large.

02 / Checks

What to check for F0090

In the order Siemens gives them.

  1. 01Check whether an encoder is fitted; if not, set P0400 = 0.
  2. 02Check the connection between the encoder and the inverter.
  3. 03Check whether the encoder is faulty: select P1300 = 0 (fixed speed) and watch the encoder signal in r0061.
  4. 04Increase the encoder signal thresholds in P0492 and P0494.

03 / Clearing it

How to clear F0090

  • Reset a fault by switching the power off and on, by pressing the Fn key on the BOP-2, or through the fault acknowledge sources P2103 and P2104.
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949; P0952 clears the complete fault memory.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0090 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How encoder signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
  2. 02Check the encoder's supply voltage.
  3. 03Check the encoder settings (type, pulses per revolution) in the drive.

05 / Repair

When F0090 means a repair

A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.

If F0090 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Encoder signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V90F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error
Siemens MICROMASTER 440F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder
Allen-Bradley PowerFlex 525F091 Encoder Loss
ABB ACS355F0023 ENCODER ERR · A2024 ENCODER ERROR
Delta VFD-EPGEr PG feedback signal error
Delta C2000PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off
Delta ASDA-B2AL004 Motor combination error · AL011 Encoder error · AL018 Abnormal signal output · AL024 Encoder initial magnetic field error · AL025 The internal of the encoder is in error · AL026 Unreliable internal data of the encoder
Hitachi WJ200E80 Encoder disconnection
Schneider Electric Altivar ATV320SPF Encoder feedback loss error
Yaskawa V1000dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG)
Yaskawa A1000dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed
Yaskawa GA500dEv Speed Deviation · oS Overspeed · PGo Encoder (PG) Feedback Loss

07 / More codes

Other MICROMASTER 430 codes

Source

Siemens, MICROMASTER 430 Parameter List, Issue 10/06, 6SE6400-5AF00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0090 won't clear? Get a technician who knows the MICROMASTER 430.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.