F0452 on the Siemens MICROMASTER 430 is the “Load torque fault detected” fault. On a fault the inverter switches off and shows the fault code; most MM430 faults use Siemens' reaction STOP II (F0012 uses STOP I). It will not run until the fault is reset.
The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.
- Code
- F0452
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 430
- Kind of fault
- Load monitoring
01 / Causes
What causes F0452
- The load conditions at the motor point to a load torque fault, such as a broken belt, or a mechanical fault.
02 / Checks
What to check for F0452
In the order Siemens gives them.
- 01Check the mechanical drive train for braking, failure or damage, and lubricate it if needed.
- 02With an external encoder, check the load torque monitoring delay time P2192.
- 03When running within a specific speed range, check the load torque monitoring settings P2182 to P2190 (frequency points and upper and lower torque thresholds 1 to 3) and the delay time P2192.
03 / Clearing it
How to clear F0452
- Reset a fault by switching the power off and on, by pressing the Fn key on the BOP-2, or through the fault acknowledge sources P2103 and P2104.
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949; P0952 clears the complete fault memory.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0452 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How load monitoring faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the mechanics: belts, couplings, gearbox and the driven machine.
- 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.
05 / Repair
When F0452 means a repair
Usually a mechanical repair on the machine, not the drive.
If F0452 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Load monitoring: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F452 Load monitoring trip · A952 Load monitoring warning |
| Siemens SINAMICS G120 | F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high |
| Siemens SINAMICS V90 | F7901 Motor overspeed |
| Siemens MICROMASTER 440 | F0452 Load torque fault detected · A0952 Load fault detected |
| Allen-Bradley PowerFlex 525 | F015 Load Loss |
| ABB ACS355 | F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD |
| Delta C2000 | ot1 Over torque 1 · ot2 Over torque 2 · uC Under current |
| Delta ASDA-B2 | AL007 Over speed · AL030 Motor crash error |
| Hitachi WJ200 | E81 Excessive speed |
| Schneider Electric Altivar ATV320 | DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error |
| INVT Goodrive20 (GD20) | OL3 Electronic overload · LL Electronic underload fault |
| Yaskawa V1000 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Yaskawa A1000 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Yaskawa GA500 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Siemens MICROMASTER 420 | F0422 No load applied to inverter · A0922 No load at the inverter |
| INVT Goodrive200A (GD200A) | OL3 Electronic overload fault · LL Electronic underload fault |
| Mitsubishi Electric FR-D700 | E.CDO Output current detection value exceeded |
07 / More codes
Other MICROMASTER 430 codes
Source
Siemens, MICROMASTER 430 Parameter List, Issue 10/06, 6SE6400-5AF00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007