MICROMASTER 430 F0222: PID feedback above maximum value

F0222 on the Siemens MICROMASTER 430 is the “PID feedback above maximum value” fault. On a fault the inverter switches off and shows the fault code; most MM430 faults use Siemens' reaction STOP II (F0012 uses STOP I). It will not run until the fault is reset.

A process value the drive controls (a PID feedback such as pressure or flow) went outside its set limits, or a pump protection function tripped.

Code
F0222
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 430
Kind of fault
Process limit

01 / Causes

What causes F0222

  • The PID feedback is above the maximum value in P2267.

02 / Checks

What to check for F0222

In the order Siemens gives them.

  1. 01Change the value of P2267.
  2. 02Adjust the feedback gain.

03 / Clearing it

How to clear F0222

  • Reset a fault by switching the power off and on, by pressing the Fn key on the BOP-2, or through the fault acknowledge sources P2103 and P2104.
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949; P0952 clears the complete fault memory.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0222 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How process limit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the process itself: a closed valve, an empty tank, a blocked line.
  2. 02Check the feedback transmitter and its wiring.
  3. 03Check the limit and gain settings in the drive.

05 / Repair

When F0222 means a repair

Usually a process or sensor problem rather than the drive.

If F0222 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Process limit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F221 PID feedback below minimum value · F222 PID feedback above maximum value · F410 Cavitation protection failure · A930 Cavitation protection warn
Siemens SINAMICS G120F07426 Technology controller actual value limited · F07445 PID autotuning canceled · A07444 PID autotuning is activated
Siemens MICROMASTER 440F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value
ABB ACS355A2018 PID SLEEP
Delta VFD-EFbE PID feedback signal error
Yaskawa V1000FbH Excessive PID Feedback · FbL PID Feedback Loss
Yaskawa A1000FbH Excessive PID Feedback · FbL PID Feedback Loss
Yaskawa GA500CP1 Comparator 1 Limit Fault · CP2 Comparator 2 Limit Fault · FbH Excessive PID Feedback · FbL PID Feedback Loss
Siemens MICROMASTER 420F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value

07 / More codes

Other MICROMASTER 430 codes

Source

Siemens, MICROMASTER 430 Parameter List, Issue 10/06, 6SE6400-5AF00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007