MICROMASTER 430 F0022: Hardware monitoring active

F0022 on the Siemens MICROMASTER 430 is the “Hardware monitoring active” fault. On a fault the inverter switches off and shows the fault code; most MM430 faults use Siemens' reaction STOP II (F0012 uses STOP I). It will not run until the fault is reset.

The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.

Code
F0022
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 430
Kind of fault
Output short circuit

01 / Causes

What causes F0022

  • DC link overcurrent, meaning an IGBT short circuit (sizes A to F).
  • A braking chopper short circuit (sizes A to F).
  • An earth fault (sizes A to C).
  • The I/O module is not inserted correctly (sizes A to E).
  • On sizes FX and GX: a UCE fault (fault value r0949 = 12, 13 or 14), or an I2C bus error (r0949 = 21; switch off and on again).

02 / Checks

What to check for F0022

In the order Siemens gives them.

  1. 01First find out whether the fault is permanent (the inverter cannot start without it) or sporadic.
  2. 02Permanent fault: check the I/O module is inserted correctly.
  3. 03Permanent fault: check for an earth fault or short circuit at the inverter output or an IGBT, by disconnecting the motor cable.
  4. 04If the fault still occurs with every external cable except the supply disconnected, the drive is very probably defective and must be repaired.
  5. 05Sporadic fault: treat it as an overcurrent; likely causes are sudden load changes, mechanical obstructions or very short ramp-up times.

Also in the manual

  • These faults share one signal in the power module, so the drive cannot tell which of them actually occurred.

03 / Clearing it

How to clear F0022

  • Reset a fault by switching the power off and on, by pressing the Fn key on the BOP-2, or through the fault acknowledge sources P2103 and P2104.
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949; P0952 clears the complete fault memory.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0022 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output short circuit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
  2. 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
  3. 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
  4. 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.

05 / Repair

When F0022 means a repair

If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.

If F0022 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Output short circuit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07807 Short-circuit detected
Allen-Bradley PowerFlex 525F041 Phase UV Short · F042 Phase UW Short · F043 Phase VW Short
ABB ACS355F0004 SHORT CIRC
Delta C2000occ IGBT short circuit between upper bridge and lower bridge
Delta ASDA-B2AL083 Servo drive outputs excessive current
Schneider Electric Altivar ATV320HDF IGBT desaturation error · SCF1 Motor short circuit error · SCF5 Motor short circuit error
INVT Goodrive20 (GD20)OUt1 Inverter unit U phase protection · OUt2 Inverter unit V phase protection · OUt3 Inverter unit W phase protection
Yaskawa V1000SC IGBT Short Circuit
Yaskawa A1000SC Output Short Circuit or IGBT Fault
Yaskawa GA500SC Short Circuit/IGBT Failure
INVT Goodrive200A (GD200A)OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection
Danfoss VLT Micro Drive FC 51Alarm 16 Short circuit

07 / More codes

Other MICROMASTER 430 codes

Source

Siemens, MICROMASTER 430 Parameter List, Issue 10/06, 6SE6400-5AF00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0022 won't clear? Get a technician who knows the MICROMASTER 430.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.